manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security System
  8. •
  9. Honeywell ADEMCO VISTA-10P User manual

Honeywell ADEMCO VISTA-10P User manual

ÊK0736QGjŠ
K0736QG 9/12 Rev A Part 1
TESTING THE SYSTEM
Using the Test mode allows each detection point to be checked for
proper operation. Testing should be conducted weekly to
ensure proper operation.
• The keypad sounds a single beep about every 30 seconds as a
reminder that the system is in the Test mode.
• Alarm messages are not sent to your Central Station while Test
mode is on.
f a problem is experienced with any detection point (no confirming
sounds, no display), call for service immediately.
1. Disarm the system and close all protected windows, doors, etc.
The READY indicator light should come on if all zones are intact
2. Enter your 4-digit Master code + 5 + 0 (walk)
3. Listen. The external sounder should sound for about 1 second
then turn off. f the sounder does not sound, CALL FOR SERV CE.
The “Test in Progress” display appears only on the keypad that
started the test.
4. Fault zones. Open each protected door and window in turn and
listen for three beeps from the keypad. Each faulted detection
point should appear on the display. The display clears when the
door or window is closed.
5. Walk in front of any interior motion detectors (if used) and listen
for three beeps. Each detector should appear on the display when
it is activated. The display clears when no motion is detected. Note
that if wireless motion detectors are used, there is a 3-minute
delay between activations to conserve battery life.
6. Test all smoke detectors
, following the manufacturer's instructions.
7. When all detection points have been checked and are intact
(closed), there should be no zone numbers displayed.
8. Exit test mode: 4-digit code + 1
TROUBLE CONDITIONS
The word CHECK on the keypad's display, accompanied by a
"beeping" at the keypad, indicates a trouble condition in the system
at the displayed zone number sensor and requires your attention.
Determine if the zone(s) displayed are intact and make them so if
they are not. f the display persists, CALL FOR SERV CE.
To silence the beeping for these conditions, press any key.
Typical Trouble conditions include the following:
Trouble Message Meaning
COMM. FA LURE
(or FC)
A failure has occurred in the telephone
communication portion of your system.
SYSTEM LO BAT
(or BAT with no zone No.)
Low system battery condition exists.
LO BAT+ zone descriptor
(or BAT with zone No.)
Low battery condition in the wireless
transmitter. Either replace the battery
yourself, or CALL FOR SERV CE.
Rcvr Jam (or CHECK 90) RF interference in wireless system which may
impede reception from wireless sensors.
ALARM 1xx (or 91)
FAULT 1xx
CHECK 1xx
A communication problem between the control
and a connected device (e.g., RF receiver,
zone expander) where the “xx” indicates the
device address.
MODEM COMM (or CC) ndicates that the control is on-line with the
Central Monitoring Station's remote computer.
BELL FA LURE
(or CHECK 70)
ndicates that the wiring connection to the
external sounder is at fault.
AC LOSS (or NO AC) The system is operating on battery power only
due to an AC power failure.
f only some lights are out on the premises,
check circuit breakers and fuses and reset or
replace as needed.
OPEN C RCU T
(or OC)
The keypad is not receiving signals from the
control.
Long Rng Trbl (or bF) Back-up communication device (if used) has
failed.
TELCO FAULT (or CHECK 94)
The telephone line has a problem.
Busy-Standby
(or d )
f this message remains displayed for more
than 1 minute, system is disabled. CALL FOR
SERV CE.
SETTING THE DATE AND TIME
You can set the time and date by doing the following:
1. +[#] + [6] [3]
(Master Code)
2. Press [∗] when the time/date is displayed.
A cursor appears under the first digit of the hour.
To move cursor ahead, press [∗]. To go back, press [#].
• Enter the 2-digit hour setting.
• Enter the 2-digit minute setting.
• Press [1] for PM or [2] for AM.
• Enter the last two digits of the current year.
• Enter the 2-digit month setting.
• Enter the 2-digit day setting.
3. To exit, press [∗] when cursor is at the last digit, or wait 30
seconds.
NOTES
SERVICING INFORMATION
Your local Honeywell dealer is the person best qualified to service
your alarm system. Arranging some kind of regular service
program with him is advisable. Your local Honeywell dealer is:
Name:
Address:
Phone:
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2012 Honeywell International Inc.
www.honeywell.com/security
ADEMCO VISTA SERIES SECURITY SYSTEMS
VISTA-10P / VISTA-10PSIA
Quick Guide to User Functions
Full User Guide Available Online: This Quick Guide describes the most frequently used features and functions of your system. For
full details of all user functions, please see the system’s User Guide located online at:
http://www.security.honeywell.com/hsc/products. The full version User Guide is also available from your installer upon request.
Congratulations on your ownership of a Honeywell Security System. This system provides:
• Three forms of detection: burglary, fire and emergency (see your installer for which forms of detection are installed)
• At least one keypad which provides control of system and displays system status
• Various sensors for perimeter and interior burglary detection
• Optional smoke or combustion detectors designed to provide early warning in case of fire.
Your system may also be programmed to automatically send alarm and status messages to a Central Monitoring Station.
SYSTEM BASICS
The following is a list of some of the most common features and
functions of your system:
• Several modes of burglary detection: Stay, Night-Stay, Away,
nstant, Maximum.
• Bypass feature lets you bypass selected zones while leaving the
rest of the system armed.
• Chime mode alerts you to the opening of protected doors and
windows while the system is disarmed.
• Fire and carbon monoxide detection are always active (if
installed) and an alarm sounds if a fire or carbon monoxide
condition is detected.
• Panic keys (if programmed) let you manually initiate a fire and
personal alarms using the keypad.
• 4-digit security codes are used in conjunction with keypad
command to perform system functions.
• Each user can be assigned a different security code, each with
different authority levels.
• The system sensing devices have been assigned to various
“zones,” which are specific areas of detection (e.g., front door,
kitchen window, etc.).
• Zone numbers (points of detection) are displayed at the keypad
when an alarm or trouble condition occurs.
• Function keys may have been programmed to perform various
functions. Ask your installer if these keys are active.
• A Scheduling feature can be programmed to automatically
perform certain functions (e.g., arm the system) at a
predetermined time each day. See the full User Guide for details.
ENTRY/EXIT DELAYS
• Entry Delays give you time to disarm the system when you
enter through the designated entrance door.
• You must disarm the system before the entry delay period ends,
or an alarm will occur (keypad beeps during the entry delay
period, reminding you to disarm the system).
• Exit delay gives you time after arming the system to leave
through the designated exit door(s) without setting off an alarm.
f programmed, a slow beeping will sound during the exit delay
period until the last 10 seconds, which then changes to fast
beeping (alerting you to the end of exit delay). f you cannot
leave within this delay time period, you should stop, disarm the
system, and start over to avoid a false alarm.
•
•
•
• See your installer for your delay times. See the full User Guide
for details on Exit Error alarms.
NOTES on BURGLARY DETECTION
• The system must be armed before the burglary detection can
sense intrusions.
• To arm your system, enter your security code followed by the
desired arming key.
• To disarm the system, enter your security code then press the
OFF key.
• When an alarm occurs, the keypad sounds and displays the
zone(s) causing the alarm. The external sounder may also
sound.
• f your system is connected to a Central Monitoring Station, an
alarm message is also sent (delayed 30 seconds by default to
reduce false alarms).
• To stop the alarm sounding, simply disarm the system.
• Me ory of Alar : When an alarm condition occurs, the
keypad displays the number(s) of the zone(s) that caused the
problem, and displays the type of alarm. Clear the Memory of
Alarm display by entering another “off” sequence.
IMPORTANT: f you return to the premises and the
main burglary sounder is on, or the keypad beeps
rapidly upon entering the premises, it indicates that
an alarm has occurred during your absence and an
intruder may still be on the premises. LEAVE
MMED ATELY and CONTACT THE POL CE from a
nearby safe location.
NOTES on FIRE and CO DETECTION
• Your fire alarm system (if installed) is on 24 hours a day, for
continuous detection. n the event of an emergency, the
smoke and heat detectors sound their alarms, triggering a
loud, interrupted pulsed sound from the Keypad(s) and any
external sounders.
• You can silence the alarm at any time by pressing the OFF key
(the security code is not needed to silence fire alarms).
• Carbon monoxide (CO) detectors, if installed, provide
continuous detection. f a high level of carbon monoxide is
detected, an interrupted pulsed alarm sound occurs at the
keypads and the detector(s). mmediately move to a spot
where fresh air is available, preferably outdoors. From a safe
area, call your security service provider for further
instructions. To silence the keypad sounding, press the OFF
key. To silence the detector, see its instructions.
BYPASSING ZONES
Use the 6 BYPASS key when you want to arm your system with one or more zones
intentionally unprotected. The system must be disarmed first.
Mode Press these keys… What happens
BYPASS
ZONES
4-digit code + 6 +
2-digit zone numbers
to be bypassed
• When finished, the keypad will momentarily display
a "Bypass" message for each bypassed zone
number. Wait for all bypassed zones to be displayed.
• Arm the system as usual. When armed, the arming
message is displayed with “ZONE BYPASSED.”
• Bypassed zones are unprotected and will not cause
an alarm if violated.
• The system will not allow fire zones to be bypassed.
• Zones are automatically unbypassed when the
system is disarmed.
• To display bypassed zones prior to arming, enter
your security code and press the BYPASS key.
PANIC KEYS
Your system may have been programmed to use special keys or key pairs to manually
activate emergency (panic) functions as follows:
This Function Key(s)* Sends This Signal** With This Sounding…
Silent Alarm silent alarm no audible alarm; displays, “Press [∗]
to show faults,” indicating that a silent
alarm has been initiated.
Audible Alarm audible alarm a loud, steady alarm at keypad(s) and
at any external sounders that may be
connected.
Personal Alarm auxiliary alarm steady alarm sound at keypad(s), but
not at external bells or sirens.
Fire Alarm fire alarm temporal (pulsing) sound at external
bells and sirens.
* Enter the appropriate keys programmed by your installer for each function (see installer).
** All panic functions send signals to the Central Monitoring Station, if connected.
To activate a Panic Function:
Press and hold down for at least 2 seconds
the programmed lettered key or key pair
for the desired emergency function (or
press both keys of the assigned key pair at
the same time).
Keys Pairs Displayed as Zone
[A] (∗
∗∗
∗/1) 95
[B] (∗
∗∗
∗/#) 99
[C] (3/#) 96
NOTE: The [D] key may be programmed
for other purposes; see your installer.
CHECKING OPEN ZONES
Checking Zones: Before arming your system, all protected doors, windows and other
detection zones must be closed or bypassed; otherwise the keypad displays "Not Ready."
Mode Press these keys… What happens
CHECK
ZONES ∗
∗∗
∗ • Displays all faulted zones.
ARMING THE SYSTEM, CHIME MODE, and CONTROLLING DEVICES
Before arming, close all perimeter doors and windows and make sure the Ready to Arm
message is shown.
After arming, leave the premises through an entry/exit door during the exit delay period and
be sure the door is reclosed to avoid causing an alarm.
Mode Press these keys… When to use an ar ing ode and what happens
STAY
4-digit code + 3
three beeps confirm
• Used when you want to arm the system with
persons staying inside (or if you have pets that are
moving throughout the premises).
• Arms perimeter zones; interior zones left disarmed.
• An alarm sounds if any protected window or non-
entry/exit door is opened.
N GHT-
STAY
4-digit code + 3 3
three beeps confirm
• Use N GHT-STAY mode to provide increased
security while staying inside.
• Arms same as STAY mode, but also arms
preselected interior sensors (set by your installer).
NSTANT
4-digit code + 7
three beeps confirm
• Used when staying inside and do not expect anyone
to use an entry/exit door.
• Same as STAY mode, except entry delay is off.
• An alarm sounds same as STAY mode, and sounds
upon opening entry/exit doors.
AWAY
4-digit code + 2
two beeps confirm
• Used when nobody is staying inside (including pets).
• Arms the entire system (interior and perimeter).
• An alarm sounds if a protected window or any door
is opened, or if any movement is detected inside.
MAX MUM
4-digit code + 4
two beeps confirm
• Used when leaving the premises for extended
periods (e.g., vacation).
• Same as Away mode, except entry delay is off.
• An alarm sounds same as Away mode, and sounds
upon opening entry/exit doors.
QU CK
ARM NG # + arming key
• f programmed, you can press the [#] key in place
of your security code when arming the system
CH ME
MODE
4-digit code + 9
(enter again to turn
Chime mode off)
• Alerts you to the opening of a perimeter door or
window while the system is disarmed.
• Three tones sound at the keypad whenever a
perimeter door or window is opened (interior zones
do not produce a tone when they are faulted).
• Pressing the READY key displays the open zones.
Turning
Devices
On and
Off
Turn ON a Device:
4-digit code + # +
7 + device number
Turn OFF a Device:
4-digit code + # +
8 + device number
• You may be able to override automatically
controlled devices using the Device commands.
• Some devices can be manually turned on or off
using the Device commands.
• Devices are assigned 2-digit device numbers.
• See your nstaller for details on controlling devices.
DISARMING THE SYSTEM and SILENCING ALARMS
The 1 OFF key is used to disarm the system, silence alarm and trouble sounds, and clear
memory of alarm displays.
Mode Press these keys… What happens
D SARM
and
S LENCE
ALARMS
4-digit code + 1
• System is disarmed and alarm sounding is silenced.
• To clear the memory of alarm display (if present),
enter your 4-digit code + 1 again.
• To Silence a Fire Alarm or Carbon Monoxide Alarm
Simply press the 1 key (no code needed)
V20P-Quik-Guide
ARMING
KEYS
BYPASSING
ZONES
CHIME
MODE
QUICK
ARMING
TESTING
THE SYSTEM
ADDING SECURITY
CODES
CHECKING
ZONES
ARMED
READY
ARMING KEYS
(NO DELAY)
DISARM
KEY
OFF
4
7
2
5
8
0
3
6
9
#
1
MAX
INSTANT
READY
AWAY
TEST
CODE
STAY
BYPASS
CHIME
A
B
C
D
• When entering codes and commands, sequential key depressions must be made within 4-5
seconds of one another. f 4-5 seconds elapse without a key depression, the entry will be
aborted and must be repeated from its beginning.
• f you make a mistake while entering a security code, stop, press the ∗
∗∗
∗ key, and then
start over. f you stop in the middle while entering a code, and then immediately start the
entry over, an erroneous code might be entered.
SECURITY CODES
Your installer assigned a master code that is used to perform all system functions.
n addition, other security codes can be assigned for use by other users.
• Only the System Master can assign security codes to users.
• Users are identified by 2-digit user numbers (user numbers 02-17; 02 = master code).
• n addition to a security code, each user is assigned an authority level and various system
attributes. See the full User Guide for definitions of each Authority Level.
• Security codes can be used interchangeably when performing system functions (a system
armed with one security code can be disarmed by a different security code), with the
exception of the Guest and Arm Only codes.
• Security code programming involves these steps:
1. Choose a user number and assign a 4-digit security code.
2. Assign an authority level to that user.
3. Assign other attributes as necessary.
Assigning Security Codes and User Attributes
The following lists the various command strings for adding security codes and attributes.
Function Co ands
Change System
Master Code
Syste Master code + 8 + [02] + new code + new code again
Add Security Code
Master code + 8 + user no. + new user’s security code
The Keypad beeps once to confirm that new user was added.
Assignable user numbers range from 03-17.
Delete Security
Code
Master code + 8 + [user no.] + # 0
The security code and all attributes set for this user number,
including any associated RF keys, are erased from the system.
Authority Level
Master code + 8 + [user no.] + # 1 + auth. level
Authority Levels: 0 = standard user
1 = arm only
2 = guest
3 = duress
Access Group
Master Code + 8 + [user no.] + 8 2 + group (1-8)
You can assign users to a group, then set an access schedule that
defines the times this group of users can operate the system. The
system ignores these users outside the scheduled times.
RF User Number
Master Code + 8 + [user no.] + # 4 + zone no.
Use this command to assign a wireless button device (keyfob) to
this user (keyfob must be enrolled in system first; see installer).
Zone number: enter the zone number assigned to a button on the
keyfob that will be used for arming/disarming by this user.
Pager On/Off
Master Code + 8 + [user no.] + # 5 + 0 or 1
You can program a user so that a message is sent to a pager
whenever this code is used to arm or disarm the system.
Paging On/Off: 1 = allow paging
0 = no paging for this user

Other manuals for ADEMCO VISTA-10P

5

This manual suits for next models

1

Other Honeywell Security System manuals

Honeywell Water Defense RWD41 User manual

Honeywell

Honeywell Water Defense RWD41 User manual

Honeywell ADEMCO VISTA-10P Operating instructions

Honeywell

Honeywell ADEMCO VISTA-10P Operating instructions

Honeywell LYNX Touch L7000 Series User manual

Honeywell

Honeywell LYNX Touch L7000 Series User manual

Honeywell HS321S User manual

Honeywell

Honeywell HS321S User manual

Honeywell AlarmNet 7845GSM User manual

Honeywell

Honeywell AlarmNet 7845GSM User manual

Honeywell ADEMCO 4110XM User manual

Honeywell

Honeywell ADEMCO 4110XM User manual

Honeywell LYNX Touch L7000 Series User manual

Honeywell

Honeywell LYNX Touch L7000 Series User manual

Honeywell Lynx Plus Series User manual

Honeywell

Honeywell Lynx Plus Series User manual

Honeywell LYNX Touch Security System User manual

Honeywell

Honeywell LYNX Touch Security System User manual

Honeywell ADEMCO VISTA-48A User manual

Honeywell

Honeywell ADEMCO VISTA-48A User manual

Honeywell SEF8MA User manual

Honeywell

Honeywell SEF8MA User manual

Honeywell LXL-1000 User manual

Honeywell

Honeywell LXL-1000 User manual

Honeywell 3-144 User manual

Honeywell

Honeywell 3-144 User manual

Honeywell 032211.17 User manual

Honeywell

Honeywell 032211.17 User manual

Honeywell Ademco VISTA-20P User manual

Honeywell

Honeywell Ademco VISTA-20P User manual

Honeywell RF Panic Button V2 User manual

Honeywell

Honeywell RF Panic Button V2 User manual

Honeywell RCWL200A User manual

Honeywell

Honeywell RCWL200A User manual

Honeywell Lynx Plus Series Operating instructions

Honeywell

Honeywell Lynx Plus Series Operating instructions

Honeywell Domonial User manual

Honeywell

Honeywell Domonial User manual

Honeywell L5200 Series User manual

Honeywell

Honeywell L5200 Series User manual

Honeywell INTELLIGUARD 9000 Manual

Honeywell

Honeywell INTELLIGUARD 9000 Manual

Honeywell ESSER IQ8Alarm User manual

Honeywell

Honeywell ESSER IQ8Alarm User manual

Honeywell VISTA-128BPEN Assembly instructions

Honeywell

Honeywell VISTA-128BPEN Assembly instructions

Honeywell Ademco Vista-48 series User manual

Honeywell

Honeywell Ademco Vista-48 series User manual

Popular Security System manuals by other brands

ALAS A.L.A.S. instruction manual

ALAS

ALAS A.L.A.S. instruction manual

DMP Electronics SCS-1R installation guide

DMP Electronics

DMP Electronics SCS-1R installation guide

Defender PHOENIX1 instruction manual

Defender

Defender PHOENIX1 instruction manual

Interlogix Simon XTi-5 Version 2 user guide

Interlogix

Interlogix Simon XTi-5 Version 2 user guide

Velleman MOND1 user manual

Velleman

Velleman MOND1 user manual

Sercomm SD-SRN09 Quick installation guide

Sercomm

Sercomm SD-SRN09 Quick installation guide

Vision Controls Cam SS XP user manual

Vision Controls

Vision Controls Cam SS XP user manual

Easy Clocking EC 200 Basic Software Setup Guide

Easy Clocking

Easy Clocking EC 200 Basic Software Setup Guide

ELRO AS90SRB user manual

ELRO

ELRO AS90SRB user manual

Cisco C395 Hardware installation guide

Cisco

Cisco C395 Hardware installation guide

Apex Digital Defender II owner's manual

Apex Digital

Apex Digital Defender II owner's manual

Petroline-A OK-150 Operation manual

Petroline-A

Petroline-A OK-150 Operation manual

U-Prox KEYFOB user manual

U-Prox

U-Prox KEYFOB user manual

Global GS819 user manual

Global

Global GS819 user manual

GE BA300 Commissioning instructions

GE

GE BA300 Commissioning instructions

Electronic Devices Limited ED510 instruction manual

Electronic Devices Limited

Electronic Devices Limited ED510 instruction manual

Teltonika T-BoxN12R user manual

Teltonika

Teltonika T-BoxN12R user manual

E2S GNExCP6C-PT instruction manual

E2S

E2S GNExCP6C-PT instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.