JUMO dTRANS T08 01 User manual

Zone 2
ZONE 2
JUMO dTRANS T08 XX
Temperature transmitter series 6 mm
707101, 707102, 707111, 707112, 707113, 707131,
707133, 707137
Operating Manual
70710100T90Z001K000
V1.00/EN/00698632

2 V1.00/EN/00698632 - 70710100T90Z001K000
Temperature transmitter series 6 mm
JUMO dTRANS T08 01 / JUMOdTRANST08 02 /
JUMOdTRANST08 11 / JUMOdTRANST08 12 /
JUMOdTRANST08 13 / JUMOdTRANST08 31 /
JUMOdTRANST08 33 / JUMOdTRANST08 37
Table of contents
Warning ................................................................................................ 3
Symbol identification .................................................................................... 3
Safety instructions ...................................................................................... 3
UL installation ....................................................................................... 4
IECEx, ATEX installation in Zone 2 ..................................................................... 4
Flexible supply .......................................................................................... 6
Mounting and demounting of JUMO dTRANS T/S08 ........................................................ 7
Installation on DIN rail / power rail ........................................................................ 8
Supply of power rail ..................................................................................... 8
Marking................................................................................................. 8
Side label ............................................................................................... 9
Applications ............................................................................................ 10
Technical characteristics ................................................................................. 10
Mounting / installation................................................................................... 10
Order codes ............................................................................................. 11
Accessories ............................................................................................. 11
Accessories for power rail devices ........................................................................ 11
Technical data .......................................................................................... 11
Connections ............................................................................................ 15
Front led indications..................................................................................... 16
DIP-switch configuration................................................................................. 17
Default configurations ................................................................................ 17
Temperature range programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

V1.00/EN/00698632 - 70710100T90Z001K000 3
Warning
To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed and
the guidelines followed. The specifications must not be exceeded, and the device must only be applied
as described in the following. Prior to the commissioning of the device, this installation guide must be
examined carefully. Only qualified personnel (technicians) should install this device. If the equipment is
used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired. Until the device is fixed, do not connect hazardous voltages to the device.
To avoid explosion and serious injury: Modules having mechanical failures must be returned to
JUMO GmbH & Co. KG for repair or replacement.
Repair of the device must be done by JUMO GmbH & Co. KG only.
In applications where hazardous voltage is connected to in-/outputs of the device, sufficient spacing or
isolation from wires, terminals and enclosure - to surroundings (incl. neighboring devices), must be
ensured to maintain protection against electric shock.
Potential electrostatic charging hazard. To avoid the risk of explosion due to electrostatic charging of the
enclosure, do not handle the units unless the area is known to be safe, or appropriate safety measures
are taken to avoid electrostatic discharge.
Symbol identification
Triangle with an exclamation mark: Read the manual before installation and commissioning of the
device in order to avoid incidents that could lead to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential requirements of the directives.
Ex devices have been approved acc. to the ATEX directive for use in connection with installations in
explosive areas.
Safety instructions
Receipt and unpacking
Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing
should always follow the device until this has been permanently mounted.
Environment
Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary,
heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation.
The device can be used for Measurement Category II and Pollution Degree 2.
The device is designed to be safe at least under an altitude up to 2 000 m.
GENERAL
CAUTION
HAZARDOUS
VOLTAGE

4 V1.00/EN/00698632 - 70710100T90Z001K000
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to
follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
JUMO GmbH & Co. KG
www.jumo.net
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire
cross section, protective fuse, and location.
Descriptions of input / output and supply connections are shown in this installation guide and on the side label.
The device is provided with field wiring terminals and shall be supplied from a Power Supply having double / reinforced
insulation. A power switch should be easily accessible and close to the device. The power switch shall be marked as the
disconnecting unit for the device.
JUMO dTRANS T/S08 must be mounted on a DIN rail according to EN 60715.
UL installation
Use 60/75°C copper conducters only.
Wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AWG 26-12
UL file number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E201387
The device is an Open Type Listed Process Control Equipment. To prevent injury resulting from accessability to live parts the
equipment must be installed in an enclosure.
The power supply unit must comply with NEC Class 2, as described by the National Electrical Code® (ANSI / NFPA 70).
IECEx, ATEX installation in Zone 2
IECEx DEK 18.0006 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ex nA IIC T4 Gc
DEKRA 18ATEX0007 X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II 3G Ex nA IIC T4 Gc
For safe installation the following must be observed. The device shall only be installed by qualified personnel who are familiar
with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The devices shall be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN60529,
taking into account the environmental conditions under which the equipment will be used.

V1.00/EN/00698632 - 70710100T90Z001K000 5
When the temperature under rated conditions exceeds 70°C at the cable or conduit entry point, or 80°C at the branching point
of the conductors, the temperature specification of the selected cable shall be in compliance with the actual measured
temperature.
Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
For installation on power rail in Zone 2, only Power rail profile (TN: 00697614) supplied by Power connector unit for dTRANS
T/S08 XX (TN: 00697612) is allowed.
To prevent ignition of the explosive atmospheres, disconnect power before servicing and do not separate connectors when
energised and an explosive gas mixture is present.
Do not mount or remove devices from the power rail when an explosive gas mixture is present.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against JUMO
GmbH & Co. KG that would otherwise exist according to the concluded sales agreement.

dTRANS T/S08 PCU
6 V1.00/EN/00698632 - 70710100T90Z001K000
Flexible supply
The technical specifications specifies the maximum required power at nominal operating values, e.g. 24 V supply voltage,
70°C ambient temperature, 600 Ω load, and 20 mA output current.
(*) External fuse characteristics:
The 2.5 A fuse must break after not more than 120 seconds at 6.4 A.
Protective fuse: 2.5 A.*
Power rail solution #1:
Alternately, you can connect 24 VDC to any
one JUMO dTRANS T/S08 device with power
rail connector which will then energize other
units on the rail.
Protective fuse: 2.5 A.*
DIN rail solution - device daisy chain:
The JUMO dTRANS T08 01, T08 02, T08 11, T08 12
and T08 13 can be supplied with 24 VDC ±30% via
direct wiring and a loop between the devices.
Power rail solution #2:
The JUMO dTRANS T/S08 PCU power
connector unit allows easy connection of a
24 VDC / 2.5 A source to the power rail.
Protective fuse: 0.4 A.
Note:
Device type JUMO dTRANS T08 01, T08 02, T08 31, T08 33 and T08 37 can only be supplied
via the DIN rail solution with direct wiring on each device.

V1.00/EN/00698632 - 70710100T90Z001K000 7
Mounting and demounting of JUMO dTRANS T/S08
Picture 1:
Mounting on DIN rail / power rail.
Click the device onto the rail.
Picture 2:
Demounting from DIN rail / power rail.
First, remember to demount the connectors with hazardous voltages.
Detach the device from the DIN rail by lifting the bottom lock.
Picture 3:
Wire size AWG 26-12 / 0.13 x 2.5 mm2stranded wire.
Screw terminal torque 0.5 Nm.

8 V1.00/EN/00698632 - 70710100T90Z001K000
Installation on DIN rail / power rail
The devices in the JUMO dTRANS T/S08 series can be installed on a DIN rail or on a power rail (only JUMO dTRANS T08 11, T08
12 and T08 13). For marine applications the devices must be supported by a module stop (TN: 00697615). Power supply units
can be mounted on the power rail according to customer requirements.
If you want to install a JUMO dTRANS T/S08 device with power rail connectors on a standard DIN rail, the head of the screws
holding the 7.5 mm DIN rail shall be no more than 3.5 mm high in order to avoid short circuit between the power rail
connectors on the device and the screws.
Supply of power rail
It is possible to supply the power rail via the supply terminals.
The terminals can pass a current of max. 400 mA.
Marking
The front cover of the JUMO dTRANS T/S08 devices has been
designed with an area for affixation of a click-on marker. The
area assigned to the marker measures 5 x 7.5 mm. Markers
from Weidmüller’s MultiCard System, type MF 5/7.5, are
suitable.
Screwable module
stop for rail profile
< 3.5 mm
> 24 mm
35 mm

V1.00/EN/00698632 - 70710100T90Z001K000 9
Side label

10 V1.00/EN/00698632 - 70710100T90Z001K000
Temperature transmitter series 6 mm
JUMO dTRANS T08 01 / JUMO dTRANS T08 02 / JUMO dTRANS T08 11 /
JUMOdTRANS T08 12 / JUMO dTRANS T08 13 / JUMO dTRANS T08 31 /
JUMOdTRANS T08 33 / JUMO dTRANS T08 37
• Converts process measurements from Pt100, TC J and K temperature sensors to
voltage or current outputs
• Multiple pre-calibrated temperature ranges are selectable via DIPswitches
• High accuracy, better than 0.05% and excellent 50/60 Hz noise suppression
• Fast signal response time < 30 ms
• JUMO dTRANS T08 13 and T08 37 with HART 7 protocol and fast signal
response time < 60 ms
• HART 7 protocol enables extended device programming for JUMO dTRANS T08
13 and T08 37
• Slimline 6 mm housing
Applications
• The temperature converters measure standard 2-, 3- or 4-wire Pt100 and/or TC J & K temperature sensors, and provides
an analog voltage or current output.
• High 3 port isolation provides surge suppression and protects the control system from transients and noise.
• The loop powered devices have high 2-port galvanic separation to eliminate ground loops.
• The devices can be mounted in the Safe area or in Zone 2 / Division 2 areas.
• Approved for marine applications.
Technical characteristics
• High conversion accuracy, better than 0.05% of span.
• A visible green LED indicates operational status and status of the input sensor.
• All terminals are protected against overvoltage and polarity error.
• Meeting the NAMUR NE21 recommendations, the system JUMO dTRANS T/S08 devices ensure top measurement
performance in harsh EMC environments.
• The devices meet the NAMUR NE43 standard defining out of range and sensor error output values.
• High galvanic isolation of 2.5 kVAC.
• Excellent signal/noise ratio of > 60 dB.
Mounting / installation
• Selectable DIP-mode for easy configuration of more than 1000 factory calibrated measurement ranges with HART read
only feature.
• The narrow 6 mm housing and very low power consumption allows up to 165 units to be mounted per meter of DIN rail,
without any air gap between units.
• Wide temperature operation range of -25...+70°C.

V1.00/EN/00698632 - 70710100T90Z001K000 11
Order codes
Accessories
TN: 00697615 = Screwable module stop for rail profile
Accessories for power rail devices
TN: 00697612 = Power connector unit for JUMO dTRANS T/S08 XX
TN: 00697614 = Power rail profile (7.5 mm / 750 mm)
Technical data
Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25°C to +70°C
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Installation in pollution degree 2 & overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 x 6.1 x 115 mm
Weight approx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 g
DIN rail type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DIN EN 60715 - 35 mm
Wire size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.13...2.5 mm2/ AWG 26...12 stranded wire
Screw terminal torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 Nm
Vibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...25 Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1.6 mm
25...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±4 g
Input Output
LED Supply Isolated HART
TC Pt100 Current
Voltage
J & K Int. CJC Ext.
CJC
2-, 3-,
4-wire Active Passive
JUMO
dTRANS
T08 01
24 VDC
JUMO
dTRANS
T08 02
24 VDC
JUMO
dTRANS
T08 11
24 VDC /
power rail 2.5 kV
JUMO
dTRANS
T08 12
24 VDC /
power rail 2.5 kV
JUMO
dTRANS
T08 13
24 VDC /
power rail 2.5 kV
JUMO
dTRANS
T08 31
Loop-powered 2.5 kV
JUMO
dTRANS
T08 33
Loop-powered
JUMO
dTRANS
T08 37
Loop-powered 2.5 kV

12 V1.00/EN/00698632 - 70710100T90Z001K000
Type Max. power
dissipation Max. required power
JUMO dTRANS T08 01 0.52 0.52
JUMO dTRANS T08 02 0.52 0.52
JUMO dTRANS T08 11 0.70 0.70
JUMO dTRANS T08 12 0.70 0.70
JUMO dTRANS T08 13 0.70 0.70
JUMO dTRANS T08 31 0.80 0.80
JUMO dTRANS T08 33 0.80 0.80
JUMO dTRANS T08 37 0.80 0.80
Common electrical specifications:
Supply voltage, 24 VDC nom. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.8...31.2 VDC
Loop-powered:
JUMO dTRANS T08 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5...35 VDC
JUMO dTRANS T08 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3...35 VDC
JUMO dTRANS T08 37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2...35 VDC
Power requirements:
Max. required power is the maximum power needed at power supply terminals or rail connector.
Max. power dissipation is the maximum power dissipated at nominal operating values.
Isolation voltage, test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 kVAC
Isolation voltage working. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 VAC (reinforced) /
250 VAC (Zone 2, Div. 2)
Double isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input / output 1 / output 2 / supply
Signal dynamics, input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 bit
Signal dynamics, output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 bit
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Min. 60 dB
Incorrect DIP-sw setting identification:
Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 V / 0 mA output; LED 0.5 s / 1 Hz
Loop-powered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 mA output
Response time
Selectable HART read only
mode HART mode
< 30 ms < 300 ms < 60 ms 0.06...60 s
JUMO dTRANS T08 01
JUMO dTRANS T08 02
JUMO dTRANS T08 11
JUMO dTRANS T08 12
JUMO dTRANS T08 13
JUMO dTRANS T08 31
JUMO dTRANS T08 33
JUMO dTRANS T08 37

V1.00/EN/00698632 - 70710100T90Z001K000 13
EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±1% of span
Input specifications:
Specifications for Pt100 input:
Temperature range, Pt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -200...+850°C - IEC 60751
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10°C
Sensor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 150 µA
Sensor cable resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 50 Wper wire
Eect of sensor cable resistance, 3- / 4-wire . . . . . . . . . . . . . . . . . . . < 0.002 Ω / Ω
Sensor error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes - selectable via DIP-switch
Broken sensor detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 800 Ω
Shorted sensor detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 18 Ω
Specifications for TC input:
Temperature range, TC J. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -100...+1200°C - IEC 60584-1
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50°C
Temperature range, TC K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -180...+1372°C - IEC 60584-1
Min. measuring range (span) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50°C
Sensor cable resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 5 kΩ per wire
Cold junction compensation (CJC) accuracy:
Accuracy @ external Pt100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Better than ±0.15°C
Accuracy @ internal CJC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Better than ±2.5°C
Open Thermocouple detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes – selectable via DIP-switch
Internal CJC error detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
External CJC error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes – selectable via DIP-switch
Device Input Basic accuracy General accuracy Temperature coefficient
JUMO dTRANS T08 12,
JUMO dTRANS T08 13,
JUMO dTRANS T08 31,
JUMO dTRANS T08 37
Pt100 ≤ 0.1°C
≤ ± 0.05%
of span
0.02°C/°C (basic) or
≤ ± 0.01% of span / °C
JUMO dTRANS T08 11,
JUMO dTRANS T08 13,
JUMO dTRANS T08 31,
JUMO dTRANS T08 37
TC ≤ 0.5°C 0.1°C/°C (basic) or
≤ ± 0.01% of span / °C
JUMO dTRANS T08 02,
JUMO dTRANS T08 33 Pt100 ≤ 0.2°C ≤ ± 0.1% of
span
0.02°C/°C (basic) or
≤ ± 0.01% of span / °C
JUMO dTRANS T08 01 TC ≤ 1°C 0.1°C/°C (basic) or
≤ ± 0.01% of span / °C

14 V1.00/EN/00698632 - 70710100T90Z001K000
Output specifications:
Updating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 ms
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.01% of span / 100 Ω
of span = of the selected range
Observed authority requirements:
EMC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU
EMC Emission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CISPR 22, Class B
LVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/35/EU
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU
Approvals:
DNV-GL, Ships & Oshore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DNVGL-CG-0339
UL, Standard for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL 61010-1
Safe Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61140
I.S. / Ex approvals:
ATEX 2014/34/EU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEKRA 18ATEX0007 X
IECEx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DEK 18.0006 X
Current output
Active Passive
Selectable NAMUR NE43
Max. load
Invert Range Limit Sensor
error
Range
4...20 mA
JUMO dTRANS
T08 01 0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA ≤ 600 Ω
JUMO dTRANS
T08 02 0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA ≤ 600 Ω
JUMO dTRANS
T08 11 0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA ≤ 600 Ω
JUMO dTRANS
T08 12 0/4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA ≤ 600 Ω
JUMO dTRANS
T08 13 4...20 mA 0/3.8...20.5 mA 0/3.5/23 mA ≤ 600 Ω
JUMO dTRANS
T08 31 4...20 mA 3.8...20.5 mA 3.5 / 23 mA (Vsupply-5.5)/0.023 [Ω]
JUMO dTRANS
T08 33 4...20 mA 3.8...20.5 mA 3.5 / 23 mA (Vsupply-3.3)/0.023 [Ω]
JUMO dTRANS
T08 37 4...20 mA 3.8...20.5 mA 3.5 / 23 mA (Vsupply-6.2)/0.023 [Ω]
Selectable voltage output
Low range High range
Min. load
Range Limit Sensor
error Range Limit Sensor
error
JUMO dTRANS T08 01
JUMO dTRANS T08 02
JUMO dTRANS T08 11
JUMO dTRANS T08 12
0/1...5 V 0/0.875...5.125 V 0/5.5 V 0/2...10 V 0/1.75...10.25 V 0/11 V 10 kΩ

++ - - + -
HART
mA
+
-
+
-
4...20 mA
+
-
V
7
6
8
5
+ -
112 mm
106.5 mm 6.1 mm
107 mm 112 mm
3xxx Housing
115 mm
+
-
+
-2
3
1
4
V1.00/EN/00698632 - 70710100T90Z001K000 15
Connections
Input wiring
Output wiring Supply wiring
*JUMO dTRANS
T08 01 - only
internal CJC
JUMO dTRANS T08 01, JUMO dTRANS T08 02 and JUMO dTRANS T08 33: No galvanic isolation
JUMO dTRANS T08 31 and JUMO dTRANS T08 37: 2 port isolation (reinforced)
JUMO dTRANS T08 11, JUMO dTRANS T08 12 and JUMO dTRANS T08 13: 3 port isolation (reinforced)
External CJC
(2- or 3-wire Pt100)
- - - 3 2 Y* JUMO dTRANS T08 01
1,2 & 3,4 1,2 & 3 2 & 3 - - N JUMO dTRANS T08 02
- - - 3 2 Y JUMO dTRANS T08 11
1,2 & 3,4 1,2 & 3 2 & 3 - - N JUMO dTRANS T08 12
1,2 & 3,4 1,2 & 3 2 & 3 3 2 Y JUMO dTRANS T08 13
1,2 & 3,4 1,2 & 3 2 & 3 3 2 Y JUMO dTRANS T08 31
1,2 & 3,4 1,2 & 3 2 & 3 - - N JUMO dTRANS T08 33
1,2 & 3,4 1,2 & 3 2 & 3 3 2 Y JUMO dTRANS T08 37
+ - TypeCJC
JUMO dTRANS
T08 01 N 5 6 5 6 - - 7 8 N
JUMO dTRANS
T08 02 N 5 6 5 6 - - 7 8 N
JUMO dTRANS
T08 11 N 5 6 5 6 - - 7 8 Y
JUMO dTRANS
T08 12 N 5 6 5 6 - - 7 8 Y
JUMO dTRANS
T08 13 Y 5 6 - - - - 7 8 Y
JUMO dTRANS
T08 31 N - - - - 5 6 - - N
JUMO dTRANS
T08 33 N - - - - 5 6 - - N
JUMO dTRANS
T08 37 Y - - - - 5 6 - - N
JUMO dTRANS
T/S08 PCU N - - - - - - 7 8 Y
24 VDC
Power
rail
+ Vsupply
CJC

16 V1.00/EN/00698632 - 70710100T90Z001K000
Front led indications
For JUMO dTRANS T08 01, JUMO dTRANS T08 02, JUMO dTRANS T08 11,
JUMO dTRANS T08 12 and JUMO dTRANS T08 13
The device is equipped with a green power LED in the front to indicate the operation
status, see the table below.
Condition LED Output Action required
No supply / device error OFF De-energized Connect supply /
replace device
Power-up or restart 1 Flash
(0.5 s OFF + 0.5 s ON) De-energized -
Device OK Flashing 13 Hz
(15 ms ON) Energized -
Incorrect DIP-switch setting Flashing 1 Hz
(500 ms ON) De-energized Correct setting and
re-power device
Sensor error indication Flashing 1 Hz
(15 ms ON) Up- or Downscale Check sensor

V1.00/EN/00698632 - 70710100T90Z001K000 17
DIP-switch configuration
The devices can be configured via DIP-switches. The DIP-switches are located on the side of the device and can be adjusted
with a small screwdriver or other implement.
Default configurations
(Power must be cycled after DIP-switch positions are changed).
JUMO dTRANS T08 02 and
JUMOdTRANS T08 12
Pt100
JUMO dTRANS T08 01 and
JUMOdTRANS T08 11
TC J & K
*JUMO dTRANS T08 01 -
only int CJC
JUMO dTRANS T08 31
Pt100 & TC J/K
JUMO dTRANS T08 13 and
JUMOdTRANS T08 37
Pt100 & TC J/K + HART
JUMO dTRANS T08 33
Pt100
JUMO dTRANS T08 02,
JUMO dTRANS T08 12,
JUMO dTRANS T08 31,
JUMO dTRANS T08 33
JUMO dTRANS T08 01,
JUMO dTRANS T08 11
JUMO dTRANS T08 13,
JUMO dTRANS T08 37
Sensor type Pt100, 3 wire TC K (int. CJC) Pt100, 3 wire
Output range 4...20 mA 4...20 mA 4...20 mA
Error detection Short circuit detection
Broken circuit detection
Short circuit detection Short circuit detection
Broken circuit detection
Error output current 3.5 mA 3.5 mA 3.5 mA
Noise suppression 50 Hz 50 Hz 50 Hz
Input lower limit 0°C 0°C 0°C
Input upper limit 150°C 600°C 150°C
Response time < 30 ms < 30 ms < 60 ms
Configuration mode --DIP switch configuration

18 V1.00/EN/00698632 - 70710100T90Z001K000
Temperature range programming
Please note:
• JUMO dTRANS T08 01 and JUMO dTRANS T08 11 - only TC input available
Valid TC J range: -100...+1200°C = correct DIP-switch setting
Valid TC K range: -180...+1372°C = correct DIP-switch setting
• JUMO dTRANS T08 02, JUMO dTRANS T08 12 and JUMO dTRANS T08 33 - only Pt100 input available
Valid Pt100 range: -200...+850°C = correct DIP-switch setting
• ”Start temp” must be lower than ”End temp” = correct DIP-switch setting
• Power must be cycled after DIP-switch positions are changed

JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Street address:
Moritz-Juchheim-Straße 1
36039 Fulda, Germany
Delivery address:
Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
Email: [email protected]
Internet: www.jumo.net
JUMO House
Temple Bank, Riverway
Harlow, Essex, CM20 2DY, UK
Phone: +44 1279 63 55 33
Fax: +44 1279 62 50 29
Email: [email protected]
Internet: www.jumo.co.uk
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: +1 315 437 5866
Fax: +1 315 437 5860
Email: [email protected]
Internet: www.jumousa.com
This manual suits for next models
7
Table of contents
Other JUMO Transmitter manuals

JUMO
JUMO dTRANS T03 J User manual

JUMO
JUMO dTRANS T06 Ex User manual

JUMO
JUMO HART dTRANS p20 Ex d User manual

JUMO
JUMO dTRANS p02 DELTA User manual

JUMO
JUMO dTRANS T02 PCP User manual

JUMO
JUMO ecoTRANS Lf 01 User manual

JUMO
JUMO TRANS T06 Junior User manual

JUMO
JUMO dTRANS T09 AS User manual

JUMO
JUMO SIRAS P21 DP User manual

JUMO
JUMO 40.2005 User manual

JUMO
JUMO Wtrans B User manual

JUMO
JUMO dTRANS T05 User manual

JUMO
JUMO dTRANS T01 HART User manual

JUMO
JUMO dTRANS T02j User manual

JUMO
JUMO TAROS S46 H User manual

JUMO
JUMO 907021/10 User manual

JUMO
JUMO DELOS SI User manual

JUMO
JUMO dTRANS T07 Reference guide

JUMO
JUMO MIDAS S21 Ex User manual

JUMO
JUMO Wtrans p User manual