manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens LVM User manual

Siemens LVM User manual

Other Siemens Control Unit manuals

Siemens V P45 Series User manual

Siemens

Siemens V P45 Series User manual

Siemens SIMATIC ET 200S User manual

Siemens

Siemens SIMATIC ET 200S User manual

Siemens VGD4 series User manual

Siemens

Siemens VGD4 series User manual

Siemens SIMOTION D4 5-2 Series User manual

Siemens

Siemens SIMOTION D4 5-2 Series User manual

Siemens simatic ET 200MP User manual

Siemens

Siemens simatic ET 200MP User manual

Siemens CLS-1000 Instructions for use

Siemens

Siemens CLS-1000 Instructions for use

Siemens SIRIUS 3RW5 series Technical Document

Siemens

Siemens SIRIUS 3RW5 series Technical Document

Siemens TMM-1 User manual

Siemens

Siemens TMM-1 User manual

Siemens SIMATIC NET 6GK1110-1AA00 User manual

Siemens

Siemens SIMATIC NET 6GK1110-1AA00 User manual

Siemens ASIC SIM 1-2 Parts list manual

Siemens

Siemens ASIC SIM 1-2 Parts list manual

Siemens FC1008-A Manual

Siemens

Siemens FC1008-A Manual

Siemens FDCI723 User manual

Siemens

Siemens FDCI723 User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens Cerberus Pyrotronics LP-30 User manual

Siemens

Siemens Cerberus Pyrotronics LP-30 User manual

Siemens SINUMERIK 880 SW 6 Technical manual

Siemens

Siemens SINUMERIK 880 SW 6 Technical manual

Siemens PSO 4000 User manual

Siemens

Siemens PSO 4000 User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens SIWAREX MS User manual

Siemens

Siemens SIWAREX MS User manual

Siemens SITRANS F M MAG 8000 User manual

Siemens

Siemens SITRANS F M MAG 8000 User manual

Siemens ASIsafe K45 F User manual

Siemens

Siemens ASIsafe K45 F User manual

Siemens 7153 User manual

Siemens

Siemens 7153 User manual

Siemens SIRIUS User manual

Siemens

Siemens SIRIUS User manual

Siemens SINAMICS V60 User manual

Siemens

Siemens SINAMICS V60 User manual

Siemens SINAMICS DCM User manual

Siemens

Siemens SINAMICS DCM User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

SiemensSiemens
SiemensSiemens
Siemens IndustryIndustry
IndustryIndustry
Industry,,
,,
,Inc.Inc.
Inc.Inc.
Inc.
BuildingBuilding
BuildingBuilding
Building
TT
TT
Tecec
ecec
echnologies Dihnologies Di
hnologies Dihnologies Di
hnologies Divisionvision
visionvision
vision
P/N 315-034090-11
INTRODUCTION The Model LVM Live Voice Module from Siemens
Industry, Inc. provides firefighters with a means of
sending live voice messages to specified audio
zones. The LVM has a push-to-talk switch on the
microphone, as well as a retractable coiled cord.
Both the push-to talk switch and the microphone
are supervised.The LVM has a built-in speaker to
preview active tones and messages. Each DAC-
NET in the system (with an LPB) supports up to
five LVMs. Additional LVMs may be
connected remotely using the RNI.
OPERATION
Controls and Indicators The front panel of the LVM contains
six switches and six pairs of LEDS.
Each pair contains one bi-color (red/
green) and one yellow LED. The
functions of the switches and LEDs
are programmed using the Zeus Tool
(Refer to the Zeus Quick Start Guide,
P/N 315-033875). All LEDs can be
programmed ON, OFF, or FLASHING.
These switches are used for manual
control of the voice system.
The functions of the remaining LEDs and push buttons are defined as follows:
PREANNOUNCE TONE (Yellow) When illuminated, indicates that the
preannounce tone is active at the
speakers.
READY TO PAGE (Green) When illuminated, indicates that all
selected zones are ready to be paged.
MONITOR VOLUME These two pushbuttons increase or
decrease the volume of the speaker on
the LVM.
Live Voice Module
Installation Instructions
Model LVM
Figure 1
LVM Live Voice Module
Siemens Industry, Inc.
Building Technologies Division
P/N 315-034090-112
The back of the LVM contains 2 rotary address switches and five diagnostic LEDs,
two plug-in cable connectors for the CAN and two plug-in cable connectors for audio.
(See Figure 2).The function of the diagnostic LEDs are defined as follows:
SCITSONGAIDMVLFONOITPIRCSED
RORRE.ylnoesuyrotcaF
LIAFCIM .detcetedsienohporcimehtfoeruliafanehwydaetsswolgDEL
LIAFNAC .detcetedsikrowt
enNACehtnoeruliafanehwydaetsswolgDEL
LIAFUPC.detcetedsiUPCehtfoeruliafanehwydaetsswolgDEL ot3erugiFnidet
acidnisDELesuacoslalliwnoitidnocliaFUPCehT* .wolleythgil
REWOP.NOsiMVLehtrofrewopehtnehwydaetsswolgDEL
PRE-INSTALLATION Set the board address for the LVM using both of the ten-position rotary switches
located on the back of the board (See Figure 2). Each of these addresses must be a
sub-address of the DAC and must be the same as the addresses assigned in the
Zeus Programming Tool.
Figure 2
LVM Cable Connections, Diagnostics and Address Switches
After setting the address, label each switch or LED. When viewed from the front
panel of the LVM, the labels are on the left and the control switches and LEDs are on
the right.
• Refer to the Zeus configuration for the address of each module and its
assigned functions.
• Remove the label strip from its slot, and type or print a brief function
identifier for each switch.
• After completing the label strip, insert in back into its slot (See Figure 3).
INSTALLATION The LVM mounts to the rear of the inner door in the CAB-1, CAB-2, CAB-3, REMBOX2
or REMBOX4 enclosures. Select the location of the LVM. In CAB-1/-2/-3 it can be
mounted on either side of the PMI/PMI-2, over the two mounting studs in the
desired location. In the REMBOX2/4 the LVM may mount in any of the positions (as
viewed from the front). Secure the LVM to the inner door with the two nuts provided.
(Refer to Figure 4.)
Figure 3
Inserting A Label Into
The Back Of The LVM
*
Siemens Industry, Inc.
Building Technologies Division
P/N 315-034090-113
When selecting the location to mount the LVM, keep in mind that no modules or
power supplies/extenders can be installed in the space on the CAB-MP or
REMBOX-MP directly behind the LVM.
When using a REMBOX 2/4, the OCM-16 and SIM-16 cannot be used.
INNER DOOR
PMI/PMI-2
LVM
Figure 4
Mounting the LVM To The Rear Of The Inner Door
CAN cable CCL, a 30 inch long 6 wire cable, P/N 599-634214, connects the LVM to
the next CAN module or P3 on the CC-5/CC-2 or P4 on the RNI.
A 24 inch long 10 wire audio cable, P/N 555-134260, connects the LVM to P4 on the
CC-5/CC-2, or JP6 on the PMI, or J1 on the PMI-2 or P1 on the RNI. (Refer to Figure 5.)
Make sure that all cables seat fully into their connectors. Secure the cable in the back
box using cable ties and the tie down points in the enclosure.The cable must have
sufficient slack to allow the inner door to open fully without putting stress on the
cable.
WIRING
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
• Each LVM module is a node in the CAN bus.
• Each LVM connects either through the CC-5/CC-2 CAN bus via a plug-in
cable to the DAC or via the RNI.
• Up to 99 CAN modules, in any combination, can be connected to the CAN
bus of each DAC.
• Each LVM module is shipped with one CCL cable.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
P/N 315-034090-11
Siemens Gebäudesicherheit
GmbH & Co. oHG
D-80930 München
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
tnerruCenalPkcaBV420 rewoPtuptuO
tnerruCV42lanimreTwercS xamAm15 DELevitcarepAm1+ riaPkrowteNNAC .xamkaepotk
aepV8
tnerruCenalPkcaBV2.60 .xamAm57 )noissimsnartgsmgnirud(
tnerruCybdnatSV42 xamAm15 DELevitcarepAm1+
NOTES:
1. Five LVMs max. per DAC-NET/LPB.
2. An LVM is not required in the enclosure with the DAC-NET/LPB.
3. Reference RNI Installation Instructions, P/N 315-033420, for complete wiring details.
• Cable connections for the LVM are shown in the following table and in
Figures 5 and 6.
SNOITCENNOCELBACMVL
elbaCnoitpircseD traP rebmuN noitcennoC
LCCgnoL-ELBAC-NAC rotcudnoc-6,.ni03 412436-555NACtx
enehtotMVLehtstcennoC no3Pmorfstcennocroeludom .INRehtno4ProMVLehtot2-CC/5-CC
oiduA elbaC ELBAC-OIDUA rotcu
dnoc-01,.ni42 062431-5552-CC/5-CCaoteludomMVLstcennoC .1PINRro2-IMP/IMPro
TO FMT TO CC-5/-2, PMI/PMI-2 OR RNI*
TO CC-5/-2 OR RNI*TO NEXT CAN MODULE
ERROR
P2
P5
P7
P4 P3
*SEE RNI INSTALLATION INSTRUCTIONS, P/N 315-033420
Figure 5
LVM Wiring
The CAN bus requires a 120 ohm resistance at each end of the loop. Refer to the
DAC-NET Installation Instructions, P/N 315-035100 for details about CAN termination.
Figure 6
Audio and CAN Bus Routing for Multiple LVMs Connected to a Single DAC-NET/LPB
ELECTRICAL RATINGS