ABB OHB Installation and user guide

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
Outdoor SF6 Circuit Outdoor SF6 Circuit
Breaker - TBreaker - T
ype OHBype OHB
Instruction for Storage, Installation, Service and Instruction for Storage, Installation, Service and
MaintenanceMaintenance

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
For your safety!For your safety!
Make sure that the installation site isMake sure that the installation site is
suitable for the electrical apparatus.suitable for the electrical apparatus.
Check that the complete installation,Check that the complete installation,
commissioning & maintenancecommissioning & maintenance
operations are carried out by qualifiedoperations are carried out by qualified
personnel with in-depth knowledge ofpersonnel with in-depth knowledge of
the apparatus.the apparatus.
Strictly follow the information given inStrictly follow the information given in
this instruction manual.this instruction manual.
Ensure compliance with legal guidelinesEnsure compliance with legal guidelines
of the site location as well as safeof the site location as well as safe
work practices.work practices.
Check that the rated performance ofCheck that the rated performance of
the apparatus is not exceeded duringthe apparatus is not exceeded during
service.service.
Pay special attention to the dangerPay special attention to the danger
notes indicated in the manual by thenotes indicated in the manual by the
following symbol:following symbol:
Check that the personnel operating the Check that the personnel operating the
apparatus have thisapparatus have this
instruction manual with them.instruction manual with them.
Strictly follow the instruction to safeguard your own and others' safety!Strictly follow the instruction to safeguard your own and others' safety!
For further information, please contact ABBFor further information, please contact ABB
!!

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
IntroductionIntroduction
This publication contains the informationThis publication contains the information
necessary for installation and commissioningnecessary for installation and commissioning
of OHB outdoor medium voltageof OHB outdoor medium voltage
circuit-breakers. For correct usage of thecircuit-breakers. For correct usage of the
product, please read this manual carefully.product, please read this manual carefully.
For correct mounting of accessories and/orFor correct mounting of accessories and/or
spare parts please refer to tspare parts please refer to t
he relevanthe relevant
instructions. The OHB circuit-breakersinstructions. The OHB circuit-breakers
are designed for various standardare designed for various standard
installation configurations. They do,installation configurations. They do,
however, allow further technical-however, allow further technical-
constructionalvariations (at the customer'sconstructionalvariations (at the customer's
request) to suit special installationrequest) to suit special installation
requirements. For this reason, therequirements. For this reason, the
information given below does not coverinformation given below does not cover
all special configurations.all special configurations.
Apart from this booklet, it is also necessaryApart from this booklet, it is also necessary
to refer to to refer to
the latest technical documentationthe latest technical documentation
available (circuit diagrams, wiring diagrams,available (circuit diagrams, wiring diagrams,
assembly and installation drawings, etc.),assembly and installation drawings, etc.),
especially with regard to any variations fromespecially with regard to any variations from
standardized configurations requested.standardized configurations requested.
Environmental protectionEnvironmental protection
program:program:
The OHB circuit-breakers are manufactured inThe OHB circuit-breakers are manufactured in
accordance with the ISO 14001 Standardsaccordance with the ISO 14001 Standards
(Guidelines for environmental management).(Guidelines for environmental management).
The production processes are carried out inThe production processes are carried out in
compliance with the Standards forcompliance with the Standards for
environmental protection in terms of reductionenvironmental protection in terms of reduction
in energy consumption as well as raw materials in energy consumption as well as raw materials
Assessment of the environmental impact duringAssessment of the environmental impact during
the life cycle of the product (LCA - Life Cyclethe life cycle of the product (LCA - Life Cycle
Assessment), is carried out during the designAssessment), is carried out during the design
stage itself and materials, processes andstage itself and materials, processes and
packing methods were selected to minimizepacking methods were selected to minimize
the same.the same.
Production techniques, which prepare theProduction techniques, which prepare the
products for simple dismantling and separationproducts for simple dismantling and separation
of the components, are used during manufactureof the components, are used during manufacture
of the circuit-breakers. This is to of the circuit-breakers. This is to
recycling at the end of the useful life cycle of therecycling at the end of the useful life cycle of the
apparatus.apparatus.

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
Index
1. Packing and transport
2. Checking on receipt
3. Rating Plate
3. Storage
4. Lifting
5. Description
5.1. Reference Standards
6. Instructions for circuit-breaker operation
6.1. Operating and signaling parts
6.2. Safety indications
6.3. Circuit-breaker closing and
opening operations
7. Installation
7.1. General
7.2. Normal installation conditions
7.3. Preliminary operations
7.4. Preparing the fixing surface and circuit-breaker fixing
7.5. Assembly for the telescopic structure
7.5.1 Details of structure parts
7.5.2 Assembly sequence
7.6. Assembly of the Poles-with-Duct assly on Cabinet
7.6.1 Unpacking of Cabinet
7.6.2 Unpacking of Poles-with-Duct Assembly
7.7. Assembly of Circuit-Breaker of structure
7.8. Power circuit connections
7.9. Earthing
7.10. Auxiliary circuit
connection
7.11. Overall dimensions
8. Commissioning
8.1. General procedures
9. Periodical checks
9.1. General
9.2. Checking program

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
1.Packing and transport:
The circuit breaker is shipped in special
packing c
ases
in the op
en position
with the
springs discharged and with SF6 gas
pressure corresponding to rated pressure in
case of 36kV rated voltage and reduced to
1.5 bar a
bsolute
for 40.5kV ra
ted voltage.
The apparatus is protected by a plastic bag,
to prevent any infiltration of water during the
loading and unloading stages and to keep
the dust off during storage. If provided, the
current transformers, support structure and
hardware , supplied on request, are packed
and shipped separately.
2. Checking on receipt:
Circuit-Breaker is dispatched from factory in
three separate cases containing Duct-&-
Poles, Cabinet with Operating
Mechanism
Drive & third case contains Loose Structure
with necessary hardware.
Also make sure that all the materials
described in the shipping note are included
in the supply.
Before carrying out any operation, always make sure that the operating
mechanism springs are discharge
d and that the
apparatus is in the open
position. On receipt, check the state of
the apparatus, that the packing is
undamaged and that the nameplate data corresponds (see fig. 1) with that
specified in the order acknowledgement and in the delivery note.
possible and in any case within five days
of receipt. The apparatus is only supplied
with the accessories specified at the time
of order and confirmed in the order
acknowledgem
ent sent by
ABB.
The following accompanying documents
are inserted in the shipping packing:
Instruction manual (this document)
Test certificate
Identification tag
Copy of shipping note
Electrical schematic diagram
The following documents are sent prior
to shipment:
Order
acknowledgeme
nt
Original copy of shipping note
Drawings/docume
nts
regarding special
configurations/conditions.
!

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
Rating Plate:
Fig.1 Rating Plate of OHB36 Breaker
3. Storage:
When a long period of storage is
foreseen,
(on request) ABB can provide suitable
packing for the
specified storage conditions.
On receipt the apparatus must be carefully
unpacked and checked as described in
Checking on receipt (chap. 2). If
immediate
installation is not possible, the apparatus
must be packed again, using the original
packing material. Insert hygroscopic
substances inside the packing, with at
well-ventilated, dry, dust-free, non-corrosive
atmosphere, away from any flammable
materials and at a temperature between
5°C and +45 °C. In any
case, avoid any
accidental impacts or positioning which
stresses the structure of the apparatus.

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
Lifting:
Fig.2 Lifting arrangement.

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
5. Description:
The OHB medium voltage
circuit-breakers
for outdoor installation use sulphur
hexafluoride gas as insulating and arc
quenching medium. The mechanical
operating mechanism used is ESH type
with stored energy and free release which
allows opening and closing operations
from local and remote positions. The
operating mechanism, the activating
kinematics of the moving contact , all
the
control and operating circuits and the
anti-condensation heater are located
inside the tight metal cabinet which also
acts as the support for t
he poles and Duct.
The above-mentioned structure is
supported by a frame made of t
elescopic
metal sections, which provides the
flexibility to adjust the height of the
circuit breaker from 3090 to 3990 mm.
The Cabinet has IP 54 degree of
protection (if provided with filters
over the ventilation holes on the
bottom of the box - optional) and is fitted
with a tight door
with inspection window.
The door has a
pad-locking arrangement
Legend [Refer Fig.3]
1. Upper Terminals
2. Porcelain Insulators
3. Lower Terminals
4. Lifting Hooks
5. Supporting Structure
6. Cabinet
7. Inspection window
8. Cross-Angles
5.1. Reference Standards
OHB circuit-breakers comply with the
IEC 62271-100, as well as the r
of the standards of other major
countries.

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
6. Instructions for circuit-breaker operation:
6.1. Operating and signaling parts
Fig. 4 Operating Mechanism & Wiring Plate
Legend
1 Terminal block of the operating and
signaling circuits
2 Thermostat
3 Signaling lamps (on request)
6
Opening
pushbutton
7 Closing pushbutton
8 Circuit-breaker auxiliary contacts
9
Signaling device for circuit-breaker
1
12
3
9
4
5
8
6
7
10
1
1
2

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
!
6.2 Safety indications:
6.3. Circuit-breaker closing and
opening operations
Circuit-breaker operation can be
manual or electrical.
a) Manual operation for spring
charging :
To manually charge the closing springs,
it is necessary to fully insert the
charging lever into the seat (9)
and
turn it clockwise until the yellow
indicator (6) appears. The force which
can normally be applied to the charging
lever fitted is 130 N. In any case, the
maximum force applied must not
exceed 170 N.
b) Electrical operation for spring
charging
On request the circuit-breaker can be
fitted with the following accessories for
electrical operation:
If mechanical operations are to be carried out on the
circuit-
breaker inside the installation area or with the protection nets
removed, pay great attention to the moving parts and to
the
medium voltage line. If the
operations are disabled, do
not force the mechanical interlocks, instead check that the
operation sequence is correct.
no auxiliary supply during charging, the
geared motor stops and then starts
recharging the springs automatically when
the voltage is on again. It is, however,
always possible to complete the charging
operation manually.
c) Circuit-breaker closing
This operation can only be carried out with
the closing springs completely charged. For
manual closing, press the pushbutton (12).
When there is a shunt closing release, t
operation can also be carried out with
remote control by means of a
circuit. The indicator (11) shows that
closing has been
accomplished.
d) Circuit-breaker opening
For manual opening, press the
(13).
When there is a shunt opening release,
the operation can also be carried out
remote control by means of a
The indicator (10) shows that opening has

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
!
7. Installation:
7.1. General
7.2. Normal installation conditions
Maximum ambient air temperature + 40 °C
Minimum ambient air temperature (-) 25
°C
Relative humidity % < 95
Altitude < 1000 m
For other installation conditions, please
follow what is indicated in the
product
Standards. For special installation
requirements please contact us. The areas
where
the power
conductors
or auxiliary
circuit conductors are placed must be
protected against the possible access of
animals, which could cause damage to
equipment as well as the installation.
7.3. Preliminary operations
Clean the insulating parts with clean dry
cloth.
Check that the upper and lower terminals
are clean and free of any
deformation
caused by shocks received during
Correct installation is of prime importance for smooth
operation of the product. The instructions given by the
manufacturer must be carefully studied and followed. It
is good practice to use gloves to
handle the parts during
installation.
7.4. Foundation for circuit-breaker
fixing
The foundation for circuit-breaker fixing
must be made of reinforced concrete and
must be smoothly leveled. The maximum
planarity tolerance allowed is 2 x 1000.
The circuit-breaker can be fixed directly to
the floor by means of
four expansion
anchoring bolts (not supplied) or with log
bolts (not supplied).
In the case of fixing
with expansion bolts,
the HILTY HSA M 20x170 type can be
used. In any case, the expansion
anchoring bolts must be of a suitable
type to resist a vertical
extraction force
of 15 kN and a
horizontal traction force
of 20 kN. Refer Fig.6 for Structure
without CTs & Fig.7 for Structure with CTs.
In the case of fixing
with foundation bolts,
these must be made as per Fig.8
Structur
e without CT
s and
as per

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
7.5. Assembly of the telescopic structure:
7.5.1 Details of Structure parts
Fig. 10 Details of structure (with CT structure)

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
7.5.2 Assembly sequence
Fig. 11 Arragement without CT structure
Fix the Lower Leg Assly as shown in
Fig. 11
Fix M20 Plain Washer
, Spring Washer & Hex
nut or Expansion Bolts in case the
is with expansion Bolts
Keep Nuts slightly loose for flexibility during
entire assembly of structure
Fix Lower Legs of CT Structure Assembly (optional) as
per Fig.12

Outdoor SF6 Circuit Breaker - Type
OHB: Instruction for Storage,
Installation, Service and
Maintenance
Original Title:
ABB Breaker
Uploaded by
Sampath Kumar
Full description
Save
Embed
Print
RELATED TITLES
173 views
0
Share
Power
Transformers
ABB Motor
Starting Br
ABB Protection
Transformers
ABB
0
Fig
13
Circuit
Breaker
Structure
Assembly
Fig.14Pitch
for
adapting
required
Now fix Cross-Support Angles (5)
as shown in Fig. Using M12 bolts,
spring washers, plain washers &
Hex Nuts .
Slide Upper Leg Assembly (1) into
Lower Leg Assembly to
achieve
height as per your requirement,
Structure can be adapted to three
different heights in pitch of 150 mm
Fix Support Angles(3) and M12 bolts,
spring washers, plain washers & Hex
Nuts.
For the sake of flexibility, do not fully
tighten the fasteners.
Other manuals for OHB
1
Table of contents
Other ABB Circuit Breaker manuals

ABB
ABB SACE Emax E1 User manual

ABB
ABB VD4 Series Installation and operating instructions

ABB
ABB ADVAC 03 Installation and operating instructions

ABB
ABB VM1/A/P Quick guide

ABB
ABB Emax X1 B/E 1150 V User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB GE Power Break II GEH6271 User manual

ABB
ABB SACE Emax Guide

ABB
ABB SACE Tmax XT User manual

ABB
ABB XT7 User manual

ABB
ABB Emax 2 Retrofill Product manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB RELION 650 SERIES Instructions for use

ABB
ABB SACE Emax 2 User manual

ABB
ABB XT7M User manual

ABB
ABB VD4 Series User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB SACE Emax 2 User manual

ABB
ABB SACE Emax 2 User manual