E2S BE DCS110-L1D Series User manual

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 1 of 6
INSTRUCTION MANUAL (ATE
X
/ IECE
x
)
BExDCS110-L1D
Flame
p
roof Combined Sounder /
LED
Beaco
n
1) Introduction
The BExDCS110-L1D is a flameproof combined sounder /
LED beacon which is certified to meet the requirements of the
ATEX directive 94/9/EC and the IECEx Scheme. The
combined unit produces both loud audio warning signals and
visual warning signals that can be used in hazardous areas
where potentially flammable atmospheres may be present.
Thirty-two different first stage audio alarm sounds can be
selected by internal switches, and each one can be externally
changed to a second or third stage alarm sound (see tone
table on Page 5). The sounder produces output levels in the
110dB(A) range. The beacon section has nine different
selectable flash patterns including a steady ON state and can
also be remotely switched to a second and third flash pattern
(see flash pattern table on page 5). The unit can be used in
Zone 1 and Zone 2 areas with gases in groups IIA and IIB
and with Temperature Classifications of T1, T2, T3 and T4
and can also be used in Zone 21 and Zone 22 areas for
combustible dusts and has an IP rating of IP 67 and a surface
temperature rating of T115ºC (T100ºC at +55ºC).
2) Marking
All units have a rating label, which carries the following
important information:-
Unit Type No. BExDCS110-L1D
Input Voltage: DC Units 12V or 24V or 48V
AC Units 230V or 115V
Codes: Ex d IIB T4 for Ta –50°C to +70ºC
Ex tD A21 IP6X T115°C based on max Ta of +70°C
Certificate No. KEMA 01ATEX2223X
IECEx KEM 10.0025X
“Warnings”
DO NOT OPEN WHEN AN EXPLOSIVE
GAS ATMOSPHERE IS PRESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND
CABLE GLANDS (Rated 110ºC) AT
AMB. TEMPERATURES OVER 40ºC
Year of Construction /
Serial No. i.e. 10 / 1DCS52000001
3) Type Approval Standards
The units have an EC Type examination certificate issued by
KEMA and have been approved to the following standards:-
EN60079-0:2006 IEC60079-0:2004 (Ed4) General Requirements
EN60079-1:2007 IEC60079-1:2007 (Ed6) Flameproof Enclosure ‘d’
EN61241-0:2006 IEC61241-0:2004 (Ed1) Dust General
Requirements
EN61241-1:2004 IEC60079-1:2004 (Ed1) Dust Enclosures tD
4) Installation Requirements
The unit must be installed in accordance with the latest
issues of the relevant parts of the EN60079 specifications or
the equivalent IEC specifications – Selection, Installation and
maintenance of electrical apparatus for use in potentially
explosive atmospheres (other than mining applications or
explosive processing and manufacture):-
EN60079-14:2008 Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4) Areas (other than mines)
EN60079-10:2003 Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
The installation of the unit must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
4) Zones, Gas Group, Category and Temperature
Classification
The BExDCS110-L1D unit has been certified Ex d IIB T4 for
Ta –50°C to +70ºC for gas and Ex tD A21 IP6X T115ºC
based on max. Ta of +70ºC for dust. This means that the
units can be installed in locations with the following
conditions:-
Area Classification:
Zone 1 Explosive gas air mixture likely to occur in
normal operation.
Zone 2 Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA Propane
Group IIB Ethylene
Temperature Classification:
T1 400oC
T2 300oC
T3 200oC
T4 135oC
Ambient Temperature Range:
-50°C to +70°C
0518
II 2G
Epsilon x:
Equipment Group
and Category:
CE Marking:
Notified Body No.

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 2 of 6
Area Classification Dust:
Zone 21 Explosive dust air mixture likely to occur in
normal operation.
Zone 22 Explosive dust air mixture not likely to occur,
and if it does, it will only exist for a short time.
IP Rating: IP67 T100ºC Ta < +55ºC
T115ºC Ta < +70ºC
Equipment Category: 2G/D
Ambient Temperature Range: -50°C to +70°C
5) Location and Mounting
The location of the unit should be made with due regard to
the area over which both the sounder and beacon warning
signal must be audible and visible. The unit should only be
fixed to services that can carry the weight of the unit.
The unit should be securely bolted to a suitable surface using
the 7mm diameter boltholes in the stainless steel U shaped
mounting bracket (see figure 1). The angle can then be
adjusted in the direction such that its warning signals can be
both heard and seen. This can be achieved by loosening the
two large bracket screws in the side of the unit, which allow
adjustment in steps of 18°. On completion of the installation
the two large bracket adjustment screws on the side of the
unit must be fully tightened to ensure that the unit cannot
move in service.
6) Access to the Flameproof Enclosure
In order to connect the electrical supply cables to the unit it is
necessary to remove the beacon section to gain access to
the flameproof chamber. To achieve this remove the four M6
hexagon socket head screws (see figure 2) and withdraw the
beacon section taking extreme care not to damage the
flameproof joints in the process.
Note the four M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on these
units. It is therefore important that these screws and their
spring washers are kept in a safe place during installation.
On completion of the cable wiring installation the flameproof
joints should be inspected to ensure that they are clean and
that they have not been damaged during installation. Also
check that the earth bonding wire between the two casting
sections is secure and the ‘O’ ring seal is in place. When
replacing the beacon section casting, ensure that it is square
with the sounder section chamber casting before inserting.
Carefully push the beacon section in place allowing time for
the air to be expelled. Only after the beacon section casting is
fully in place should the four M6 Stainless Steel A4-80 cover
bolts and their spring washer be inserted and tightened
down. If the beacon section jams while it is being inserted,
carefully remove it and try again. Never use the cover bolts to
force the beacon section casting into position.
In case of repair, contact the manufacturer for information on
the dimensions of the flameproof joints.
7) Power Supply Selection
It is important that a suitable power supply is used to run the
unit. The power supply selected must have the necessary
capacity to provide the input current to all of the units
connected to the system. The sounder and LED beacon
sections can both be wired to the same power supply or to
different power supplies
The following table shows the input current taken by the
sounder section and beacon section of the various units:-
Unit Type Input Sounder Max.
Voltage Current I/P Volts
BExDCS110-L1D 24V DC 265mA 30V
BExDCS110-L1D 12V DC 195mA 15V
BExDCS110-L1D 48V DC 130mA 50V
BExDCS110-L1D 230V AC 56mA 253V
BExDCS110-L1D 115V AC 110mA 126V
Unit Type Input LED Beacon Max.
Voltage Current I/P Volts
BExDCS110-L1D 24V DC 400mA 30V
BExDCS110-L1D 12V DC 760mA 15V
BExDCS110-L1D 48V DC 130mA 50V
BExDCS110-L1D 230V AC 65mA 253V
BExDCS110-L1D 115V AC 135mA 126V
The above table also shows the maximum voltages at which
the units can be operated.
Sounder Section
The input current to the sounder section will vary according to
the voltage input level and the frequency of the tone selected.
The current levels shown above are for the 440Hz
Continuous tone @ nominal input voltage. The 24V and 48V
DC units and the 230V AC, 115V AC units have a switching
S/S Mounting
Bracket
Sounder
Section
Flashdome
Guard
Plastic Acoustic Horn
(Anti-static Plastic)
Fig 1
Beacon
Section
4 off Cover Screws External Earth
Terminal
Fig 2

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 3 of 6
voltage regulator circuit and therefore the input current level
will decrease slightly as the input voltage in increased and
will increase slightly as the input voltage is reduced. The 12V
units do not have a voltage regulator and therefore their input
current will increase when the input voltage is increased.
LED Beacon Section
The input current to the beacon section will vary according to
the voltage input level. The current levels shown above are
for nominal input voltages of 12V, 24V and 48V DC the units
have a converter circuit and therefore the input current level
will decrease slightly as the input voltage in increased and
will increase slightly as the input voltage is reduced.
8) Cable Selection
When selecting the cable size consideration must be given to
the input current that each unit draws (see table above), the
number of units on the line and the length of the cable runs.
The cable size selected must have the necessary capacity to
provide the input current to all of the units connected to the
line.
SAFETY WARNING: If the unit is used at high ambient
temperatures, i.e. over +40ºC, then the cable entry
temperature may exceed +70ºC and therefore suitable heat
resisting cables must be used, with a rated service
temperature of at least 110ºC.
9) Earthing
Both AC and DC units must be connected to a good quality
earth. The units are provided with internal and external
earthing terminals, which are both, located on the beacon
section of the unit (see figures 2 and 3).
N L
When using the external earth terminal a cable crimp lug
must be used. The cable lug should be located between the
two M5 stainless steel flat washers. The M5 stainless steel
spring washer must be fixed between the outer flat washer
and the M5 stainless steel nut to ensure that the cable lug is
secured against loosening and twisting.
The internal earth bonding wire ensures that a good quality
earth is maintained between the sounder section casting and
the beacon section casting.
10) Cable Glands
The BExDCS110-L1D unit has dual cable gland entries which
have an M20 x 1.5 entry thread as standard. Only cable
glands approved for Ex ‘d’ applications can be used, which
must be suitable for the type of cable being used and also
meet the requirements of the Ex ‘d’ flameproof installation
standard EN60079-14:2008 / IEC60079-14.
SAFETY WARNING: If the unit is used at high ambient
temperatures, i.e. over +40ºC, then the cable entry
temperature may exceed +70ºC and therefore suitable heat
resisting cable glands must be used, with a rated service
temperature of at least 110ºC.
When only one cable entry is used the other one must be
closed with an Ex ‘d’ flameproof blanking plug, which must be
suitably approved for the installation requirements.
For combustible dust applications, the cable entry device and
blanking elements shall be in type of explosion protection
increased safety "e" or flameproof enclosure "d" and shall
have an IP 6X rating according to EN60529:1992.
11) Cable Connections
The combined sounder LED beacon unit BExDCS110-L1D
has separate printed circuit boards in the sounder and LED
beacon sections. The terminals for the sounder are on the
printed circuit board in the sounder section and the terminals
for the beacon are on the printed circuit board in the beacon
section (see figures 4&5 and 6&7). See section 8 of this
manual for access to the enclosure and the wiring diagrams
at the end of this manual.
The sounder and LED beacon sections can be wired to the
same input supply so that they operate simultaneously or
they can be wired to separate input supplies so they can be
operated independently (see diagrams on page 6 of this
manual). If the sounder and beacon sections are connected
to the same input supply, the incoming cables should be
connected to the input terminals on the LED beacon board
and the two connecting wires, that are supplied with the unit,
should be used to link the supply from the interconnecting
terminals on the beacon board down to the supply terminals
on the sounder board.
SOUNDER SECTION CONECTIONS
On the AC units a two-way terminal block is provided for the
live and neutral mains supply wires and a three way terminal
block is provided for linking the second and third stages, (see
figure 7). On the DC units a four way terminal block is
provided for +ve and –ve supply input and second and third
stage modes of operation, (see figure 6).
A single wire with a cross sectional area of up to 4mm² can
be connected to each terminal way or if an input and output
wire is required two 2.5mm² wires can be connected to each
terminal way. When connecting wires to the terminals great
care should be taken to dress the wire so that when the
beacon section is inserted into the chamber the wires do not
exert excess pressure on the terminal blocks. This is
particularly important when using cables with large cross
sectional areas such as 2.5mm² and above. If the sounder is
wired to the same power supply as the beacon always use
the flexible interconnecting wires provided.
Internal Bonding
Wire Terminal
Internal Earth Terminal
2 off M20
Cable Entries Figure 3

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 4 of 6
LED BEACON SECTION CONNECTIONS
The cable supply connections are made into the terminal
blocks on the electronic pcb assembly located in the
flameproof LED beacon section enclosure, see section 8 of
this manual for access to the flameproof enclosure. The AC
unit has two live terminals and two neutral terminals for the
input and output supply wiring and the DC unit has two +ve
terminals and two -ve terminals for the input and output
supply wiring. Both units have S2 and S3 terminals to
remotely change the flash pattern, see section 16 of this
manual.
Wires having a cross sectional area of up to 4mm² can be
connected to each terminal way. When connecting wires to
the terminals great care should be taken to dress the wires so
that wires do not exert excess pressure on the terminal
blocks. This is particularly important when using cables with
large cross sectional areas such as 2.5mm² and above.
N L
+ + - - S2 S3
+ -
12) Tone Selection and 2nd and 3rd Stage Alarms
The BExCS110-L1D sounder section has 32 different tones
that can be selected for the first stage alarm. The sounders
can then be switched to sound second and third stage alarm
tones. The tones are selected by operation of a DIP switch on
the sounder pcb for both DC and AC units. The tone table on
page five shows the switch positions for the 32 tones and
which tones are available for the second and third stages. To
operate the sounder on stage one simply connect the supply
voltage to the normal supply terminals (+ve and –ve for DC
units, L and N for AC units).
The operation of the second and third stages is different for
DC and AC units.
DC Units Second and Third Stage Tone Selection
The BExCS110-L1D DC sounder section has the facility to
use either +ve or –ve switching to change the tone to the
second and third stages. For –ve switching connect the two
headers on the pcb to the left-hand (marked –ve) and centre
pins. For +ve switching connect the headers to the right hand
(marked +ve) and the centre pins. To change to the second
stage tone, connect either a -ve or +ve supply line to terminal
S2, depending on which switching mode is being used while
maintaining the dc supply to the +ve and –ve terminals.
Similarly for the third stage tone, connect a -ve or +ve supply
line to terminal S3. The supply to the S3 terminal will
automatically override a supply to the S2 terminal.
AC Units Second and Third Stage Tone Selection
To select the second and third stage tones on the
BExDCS110-L1D AC sounder section, the Common (C)
terminal on the three way terminal block on the pcb is
connected to the S2 terminal for the second stage tone and
the S3 terminal for the third stage tone.
Volume Control
The BExDCS110-L1D sounder section, with the exception of
12V DC units, has a volume control to adjust the output level.
To set the required output level, adjust the potentiometer on
Figure 7
Figure 6
BExDCS110-L1D DC Sounder Section
BExDCS110-L1D AC Sounder Section
Volume Control
DIP Switch
DIP Switch
Volume Control
DC Input
Terminals
Stage Headers
Stage Terminals
AC Input
Terminals
S2
S3
-
+
S2
S3
C
N
L
Figure 4
AC Input
Terminals
Interconnecting
Terminals to
sounder pcb
(simultaneous
mode of
ope
r
a
ti
o
n
)
BExDCS110-L1D AC LED Beacon Section
Flash Pattern
Pin Headers
DC Input
Terminals
Figure 5
Flip / Flop
Pin Header
BExDCS110-L1D DC Beacon Section
Interconnecting
Terminals to
sounder pcb
(simultaneous
mode of
ope
r
a
ti
o
n
)
2nd and 3r
d
Stage
Terminals

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 5 of 6
the pcb. For maximum output level the potentiometer should
be set to the fully clockwise position.
13) Flash Pattern Selection and 2nd & 3rd Stages
The BExDCS110-L1D LED beacons have 9 different flash
patterns including one ON state that can be selected for the
first stage. They can then be remotely switched to second
and third stage flash patterns. The flash patterns are selected
by pin headers on the pcb for both DC and AC units. The
table on page five shows the pin header positions for the nine
flash patterns and which patterns are available for the second
and third stages. To operate the led beacon on stage one
simply connect the supply voltage to the normal supply
terminals (+ve and –ve for DC units, L and N for AC units).
The operation of the second and third stages is different for
DC and AC units.
DC Units Second and Third Stage Selection
To change to the second stage flash pattern, simply connect
a -ve supply line to terminal S2, while maintaining the dc
supply to the +ve and –ve terminals. Similarly for the third
stage flash pattern, connect a -ve supply line to terminal S3.
The supply line to the S3 terminal will automatically override
a supply to the S2 terminal.
AC Units Second and Third Stage Selection
To select the second and third stage flash patterns on the
BExDCS110-L1D AC beacons the Common (C) terminal on
the three way terminal block on the pcb is connected to the
S2 terminal for the second stage tone and the S3 terminal for
the third stage tone.
Flash Pattern Table
Stage 1 LED Stage 2 Stage 3
Pattern Flash Pattern Pattern Pattern
1 ON 9 8
2 Rotating 3 LED on Fast 7 1
3 Rotating 6 LED on Fast 8 1
4 Rotating 3 LED on Slow 9 1
5 Rotating 6 LED on Slow 6 1
6 Double strike strobe 1 Hz 9 1
7 Single strike strobe 2 Hz 3 1
8 Double strike strobe 2 Hz 3 1
9 Alternate side flash 1:1 2 Hz 3 1
PIN HEADER POSITIONS
Pattern No. 1 Pattern No. 2 Pattern No. 3
Pattern No. 4 Pattern No. 5 Pattern No. 6
Pattern No. 7 Pattern No. 8 Pattern No. 9
Pattern Selection
Pin Headers
PCB Edge
14) Line Monitoring (DC Units)
On BExDCS110-L1D DC units, dc reverse line monitoring
can be used if required. All DC units have a blocking diode
fitted in their supply input lines on both the sounder section
and the LED beacon section. An end of line monitoring diode
or an end of line monitoring resistor can be connected across
the +ve and –ve terminals. If an end of line resistor is used it
must have a minimum resistance value of 3k3 ohms and a
minimum wattage of 0.5 watts or a minimum resistance value
of 500 ohms and a min. wattage of 2 watts. If the sounder
and beacon sections are wired to separate power supplies,
then an end of line monitoring component can be used in
each section.
TONE SELECTION TABLE
Tone Selection DIP Switch
Settings
Stage Selection
Stage 1 Frequency Description 1 2 3 4 5
Stage 2 Stage 3
1 Continuous 1000Hz
Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11
2 Alternating 800/1000Hz at 0.25s
intervals 1 0 0 0 0 Tone 17 Tone 5
3 Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated 0 1 0 0 0 Tone 2 Tone 5
4 Sweeping 800/1000 at 1Hz 1 1 0 0 0 Tone 6 Tone 5
5 Continuous at 2400Hz 0 0 1 0 0 Tone 3 Tone 27
6 Sweeping 2400/2900Hz at 7Hz 1 0 1 0 0 Tone 7 Tone 5
7 Sweeping 2400/2900Hz at 1Hz 0 1 1 0 0 Tone 10 Tone 5
8 Siren 500/1200/500Hz at 0.3Hz 1 1 1 0 0 Tone 2 Tone 5
9 Sawtooth 1200/500Hz at 1Hz 0 0 0 1 0 Tone 15 Tone 2
10 Alternating 2400/2900Hz at 2Hz 1 0 0 1 0 Tone 7 Tone 5
11 Intermittent 1000Hz at 0.5Hz
General alarm 0 1 0 1 0 Tone 31 Tone 1
12 Alternating 800/1000Hz at 0.875Hz 1 1 0 1 0 Tone 4 Tone 5
13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 Tone 15 Tone 5
14 Intermittent 800Hz 0.25s on 1s off 1 0 1 1 0 Tone 4 Tone 5
15 Continuous at 800Hz 0 1 1 1 0 Tone 2 Tone 5
16 Intermittent 660Hz 150mS on,
150mS off 1 1 1 1 0 Tone 18 Tone 5
17 Alternating 544Hz
(100mS)/440Hz(400mS) 0 0 0 0 1 Tone 2 Tone 27
18 Intermittent 660Hz 1.8s on, 1.8s off 1 0 0 0 1 Tone 2 Tone 5
19 1400Hz to 1600Hz sweep up over
1s - 1600Hz to 1400Hz sweep down
over 0.5s
0 1 0 0 1 Tone 2 Tone 5
20 Continuous 660Hz 1 1 0 0 1 Tone 2 Tone 5
21 Alternating 554/440Hz at 1Hz 0 0 1 0 1 Tone 2 Tone 5
22 Intermittent 554Hz at 0.875Hz 1 0 1 0 1 Tone 2 Tone 5
23 800Hz pulsing at 2Hz 0 1 1 0 1 Tone 6 Tone 5
24 Sweeping 800/1000Hz at 50Hz 1 1 1 0 1 Tone 29 Tone 5
25 Sweeping 2400/2900Hz at 50Hz 0 0 0 1 1 Tone 29 Tone 5
26 Simulated bell sound 1 0 0 1 1 Tone 2 Tone 1
27 Continuous 554Hz 0 1 0 1 1 Tone 26 Tone 5
28 Continuous 440Hz 1 1 0 1 1 Tone 2 Tone 5
29 Sweeping 800/1000Hz at 7Hz 0 0 1 1 1 Tone 7 Tone 5
30 420Hz repeating 0.625s on, 0.625s
off Australian alert signal 1 0 1 1 1 Tone 32 Tone 5
31 1200/500Hz at 1 Hz
Prepare to abandon platform 0 1 1 1 1 Tone 11 Tone 1
32 Sweeping 500/1200Hz 3.75s on,
0.25s off 15Hz 1 1 1 1 1 Tone 26 Tone 1

_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. IS 2469-P Issue C 23-04-10 Sheet 6 of 6
Beacon
PCB Sounder
PCB
+ - S2 S3 + - S2 S3
S3
S2
-
+
Unit No. 1 Unit No. 2 Unit No. 3
+ - S2 S3
Sounder
PCB + - S2 S3
Sounder
PCB
Beacon
PCB Beacon
PCB
+
-
S2
S3
LED Beacon
Connections
Sounder
Connections
+ - S2 S3+ - S2 S3
Beacon
PCB Sounder
PCB
+ - S2 S3
S3
S2
-
+
Unit No. 1 Unit No. 2 Unit No. 3
+
-+ - S2 S3
Sounder
PCB + - S2 S3
Sounder
PCB
+
-
+ -
Beacon
PCB +
-
Beacon
PCB
S2
S3
+ - S2 S3 + - S2 S3
Sounder 2nd
& 3rd Stages
Beacon 2nd
& 3rd Stages
Beacon
PCB Sounder
PCB
L N C S2 S3
S3
S2
Unit No. 1 Unit No. 2 Unit No. 3
Sounder
PCB Sounder
PCB
Beacon
PCB Beacon
PCB
L
L N C S2 S3 L N C S2 S3
C
L
N
N
S2
S3
C
L N C S2 S3 L N C S2 S3 L N C S2 S3
Beacon
Connections
Sounder
Connections
Beacon
PCB Sounder
PCB
L N C S2 S3
S3
S2
Unit No. 1 Unit No. 2 Unit No. 3
L
N
Sounder
PCB Sounder
PCB
Beacon
PCB Beacon
PCB
L N C S2 S3
N
L
L N C S2 S3
N
L
N
L
C
L N C S2 S3 L N C S2 S3 L N C S2 S3
S3
S2
C
Sounder 2nd
& 3rd Stages
Beacon 2nd
& 3rd Stages
BExDCS110-L1D DC Combined Sounder Unit
LED Beacon and Sounder Wired for Inde
p
endent O
p
eration
BExDCS110-L1D DC Combined Sounder Unit
LED Beacon and Sounder Wired for Simultaneous O
p
eration
NOTE
Either the L or the N wire may be made
common to both the sounder and the
beacon to reduce the number of cores in
the cable.
NOTE
Either the +ve or the -ve wire may be made
common to both the sounder and the
beacon to reduce the number of cores in
the cable.
BExDCS110-L1D AC Combined Sounder Unit
LED Beacon and Sounder Wired for Inde
p
endent O
p
eration
BExDCS110-L1D AC Combined Sounder Unit
LED Beacon and Sounder Wired for Simultaneous O
p
eration

EC DECLARATION OF CONFORMITY
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH, UK
Telephone: +44 (0)20 8743 8880 European Safety Systems Ltd
Facsimile: +44 (0)20 8740 4200 Company Registration No. 2763350
E-mail: sales@e2s.com Registered Office: Impress House
www.e2s.com Mansell Road, London, UK, W3 7QH, UK
Equipment Type: BExCS110-05D, BExDCS110-05D,
BExCL15-05D, BExDCL15-05D,
BExCA110-05D, BExDCA110-05D,
BExCTS110-05D, BExDCTS110-05D,
BExCTV110-05D, BExDCTV110-05D
BExCS110L1D, BExDCS110L1D
Directive 94/9/EC: Electrical and Mechanical equipment for use in explosive atmospheres (ATEX)
Notified Body for EC type Examination:
KEMA Quality B.V.
Notified Body No.: 0344
Utrechtseweg 310, 6812 AR Arnhem, The Netherlands
EC
-
type Examination Certificate:
KEMA 01ATEX2223X
Notified Body for Quality Assurance Notification:
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Quality Assur
ance Notification
:
SIRA 05 ATEX M342
Provisions fulfilled by the equipment:
ll2 G Ex d llB T4
ll 2 D Ex tD A21 IPGX T100 °C or T115 °C
Standards applied:
EN 60079-0:2006
EN 60079-1:2007
EN 61241-0:2006
EN61241-1:2004
Directive 2004/108/EC: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007
EN 61000-6-4:2007
The standards EN 60079-0: 2006, EN 61241-0:2006 and EN 61241-1:2004 are no longer harmonized. The requirements
of these standards have been checked against the harmonized standards EN 60079-0:2009 and EN 60079-31:2009 and
there were no major technical changes affecting the latest technical knowledge for the products listed above.
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is
placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed
directives.
Martin Streetz Date and Place of Issue: London, 04/07/2012
Quality Assurance Manager Document No: DC-005-Issue_C
Table of contents
Other E2S Marine Equipment manuals
Popular Marine Equipment manuals by other brands

Furuno
Furuno FE-700 Operator's guide

Marine Rescue Technologies
Marine Rescue Technologies Sea Marshall AU9 user manual

Philips
Philips Beolink 1000 quick start guide

JRC
JRC Alphatron Marine Mode Switch 3 Pos Operation manual

Furuno
Furuno FMD3100 Operator's manual

Kohler
Kohler GM89754-KP2 installation instructions

INIM Electronics
INIM Electronics enea ESB1050 instruction manual

NexSens
NexSens CB-450 Data Buoy quick start guide

Furuno
Furuno FCV-291 Specifications

Alamarin Jet
Alamarin Jet AJ 340 Operation and maintenance manual

GUIDANCE MARINE
GUIDANCE MARINE Artemis Mk6 Operator's guide

Nittan
Nittan EV-ABS instruction manual