E2S D1xS2FDC024-A User manual

INSTRUCTION MANUAL
D1xS2
Alarm Horn Sounder
Class I, Zone 1, 2, 21 & 22
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 1 of 8
D1xS2F
D1xS2H
1) Product Table
Unit Type Code
Nominal
Input Voltage
Nominal
Current P2
Nominal
Current P3
Voltage Range
Sound
Pressure Level
dB(A)
Max*
P2/P3
Nom.†
P2/P3
D1xS2FDC024-A
12Vdc
289mA
356mA
11.5-54Vdc
120/123
115/118
24Vdc
324mA
740mA
48Vdc
195mA
391mA
D1xS2FAC230-A
115Vac
125mA
282mA
100-240Vac 50/60Hz
230Vac
78mA
167mA
D1xS2HDC024-A
12Vdc
289mA
356mA
11.5-54Vdc
124/127
119/122
24Vdc
324mA
740mA
48Vdc
195mA
391mA
D1xS2HAC230-A
115Vac
125mA
282mA
100-240Vac 50/60Hz
230Vac
78mA
167mA
*Max = Tone 4
Nom. = Tone 44
The table shows the input current taken by the various sounders.
The current levels shown above are for the 440Hz Continuous tone @ nominal input voltage.
Nominal current at nominal voltage.
Table 1: Electrical Ratings.
2) Warnings
CAUTION
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS
ATMOSPHERES:
DISCONNECT FROM SUPPLY BEFORE OPENING.
KEEP TIGHTLY CLOSED WHEN IN OPERATION.
WARNING
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES
FROM ENCLOSURE.
EQUIPMENT MUST NOTBE INSTALLED WITH THE HORN FACING
UPWARDS OF HORIZONTAL
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS
PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING HAZARD - CLEAN
ONLY WITH A DAMP CLOTH
ATEX/IECEx & UKEx INSTALLATIONS: IF TEMPERATURE
EXCEEDS 70°C AT ENTRY OR 80°C AT BRANCHING POINT USE
SUITABLE RATED CABLE AND GLANDS
ATTENTION
ATMOSPHÈRES DANGEREUSES :
COUPER L 'ALIMENTATION AVANT OUVERTURE.
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT.
AVERTISSEMENT
CONDUITS DOIVENT ETRE SCELLES EN MOINS DE 18 POUCES.
ÉQUIPEMENT NE DOIT PAS ETRE INSTALLE AVEC LE KLAXON
TOURNEE VERS LE HAUT DE HORIZONTAL.
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
ATEX/IECEx & UKEx INSTALLATIONS : SI LA TEMPÉRATURE
DÉPASSE 70 °C À L'ENTRÉE OU 80 °C AU POINT DE
BRANCHEMENT, UTILISER UN CÂBLE ET DES JOINTS
D'ÉTANCHÉITÉ APPROPRIÉS

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 2 of 8
3) Marking & Rating Information
The D1xS2 Alarm Horns comply with the following standards for
hazardous locations:
3.1 Class/Division Ratings for US & Canada
Standards
Class I UL 1203 & CSA C22.2 No 30-M1986
Class Division Ratings for US (NEC)
Model No:
Rating
D1xS2-DC024-A /
D1xS2-AC230-A
Class Division Ratings for Canada (CEC)
Model No:
Rating
D1xS2-DC024-A
D1xS2-AC230-A
Class Zone Ratings for US (NEC)
Model No:
Rating
D1xS2-DC024-A /
D1xS2-AC230-A
Class Zone Ratings for Canada (CEC)
Model No:
Rating
D1xS2-DC024-A
D1xS2-AC230-A
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
3.2 ATEX / IECEx & UKEx Ratings
Standards
Model No:
Rating
D1xS2-DC024-A
Ex db IIC T5 Gb Ta 55°C to +75°C
Ex db IIC T6 Gb Ta 55°C to +60°C
Ex tb IIIC T95°C Db Ta 55°C to +75°C
D1xS2-AC230-A
Ex db IIC T5 Gb Ta 55°C to +75°C
Ex db IIC T6 Gb Ta 55°C to +60°C
Ex tb IIIC T93°C Db Ta 55°C to +75°C
See Product table for electrical ratings of each unit model
Certificate No.
DEMKO 19ATEX2141X
IECEx ULD 19.0008X
UKEx UL UL21UKEX2132X
Epsilon x
Equipment Group
and Category:
II 2G
II 2D
CE Marking and
Notified Body No.
2813
UKCA Marking and
Notified Body No.
0518
4) Zones, Gas Group, Category and
Temperature Classification
The units can be installed in locations with the following conditions:
Area Classification Gas
Zone 1
Explosive gas air mixture likely to occur in normal
operation.
Zone 2
Explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist for
a short time.
Gas Groupings
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1
450oC
T2
300oC
T3
200oC
T4
135oC
T5
100ºC
T6
85ºC (D1xS2 up to 60°C ambient)
Area Classification Dust
Zone 21
Explosive dust air mixture likely to occur in normal
operation.
Zone 22
Explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only exist for
a short time.
Dust Groupings
Group IIIA
Combustible Dusts
Group IIIB
Non-Conductive Dusts
Group IIIC
Conductive Dusts
Equipment Category
2G, 2D
Equipment Protection Level
Gb, Gc, Db, Dc
Maximum Surface Temperature for Dust Applications
95°C (D1xS2-DC024-A)
93°C (D1xS2-AC230-A)
Ambient Temperature Range
-55°C to +75°C (-67°F to +167°F)
IP Rating
IP66 to EN60529
4 / 4X / 3R / 13 to UL50E / NEMA250

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 3 of 8
5) Specific Conditions of Installation
ATEx/IECEx & UKEx Installations:
The cable entries have two M20 x 1.5 6H entry thread and a
glands, only suitably rated ATEx/IECEx or UKEx certified cable
glands must be used. They must be suitable for the type of
cable being used and also meet the requirements of the
current installation standards EN 60079-14 / IEC60079-14.
If the installation is made using conduit, openings must have a
sealing fitting connected as close as practical to the wall of the
enclosure, but in no case more than the size of the conduit or
50mm, whichever is the lesser.
Any unused cable entries must be closed with suitably rated
and UKEx certified blanking plugs.
NEC / CEC Installations:
The cable entries have two M20 x 1.5 6H entry thread and a
glands, only suitably rated and UKEx certified cable glands
must be used. They must be suitable for the type of cable
being used and also meet the requirements of the current
installation standards for NEC & CEC.
If the installation is made using conduit, openings must have a
Any unused cable entries must be closed with suitably rated
and certified blanking plugs.
All Installations:
The plastic horn is not anti-static and the metallic enclosure has a
non-conductive coating. These may generate an ignition-capable
level of electrostatic charges under certain extreme conditions. The
user should ensure that the equipment is not installed in a location
where it may be subjected to external conditions that might cause a
build-up of electrostatic charges on non-conducting surfaces.
6) Specific Conditions for Safe Use
Flameproof threaded joints and cemented joints are not permitted to
be repaired.
7) Product Mounting and Access
7.1 Mounting
Fig 1: Mounting Locations
7.2 Installation procedure
a. Secure the D1x unit to a flat surface via the three 7mm
fixing holes in the mounting bracket.
b. Remove the explosionproof cover of the alarm horn by
unscrewing it, taking care not to damage the
explosionproof threads in the process (Refer to section
7.4).
c. Fit an M20/NPT suitably rated cable gland or conduit entry
into the hole in the enclosure and connect the field wiring
to the appropriate alarm horn terminals as shown in D190-
06-005 (AC) or D190-06-001. (DC). The power supply
terminals are duplicated so that units may be connected
in parallel. An end of line monitoring resistor may be fitted
to DC units only (see section 10). If the second and third
M20/NPT entries are not used, suitably rated stopping
plugs must always be fitted.
d. Replace the explosionproof cover of the loudspeaker,
taking care not to damage the explosionproof threads.
Tighten fully.
7.3 Hornless Variants
Minimum Ratings of Cables & Cable Glands
Max Ambient Temp (°C)
55
60
65
70
75
D1xS2-DC024-A Min. Rating (°C)
70
75
80
85
90
D1xS2-AC230-A Min. Rating (°C)
70
75
80
85
Table 2: Min. Ratings of Cables & Cable Glands.
D1xS2F
D1xS2H

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 4 of 8
7.4 Access to the Explosionproof Enclosure
Fig 2: Accessing the enclosure
On completion of the installation the flameproof threaded joint should
be inspected to ensure that they are clean and that they have not
been damaged during installation.
Ensure the O-ring seal is in place and undamaged.
When fitting the flameproof cover ensure the thread is engaged
correctly. Fully tighten the cover all the way, ensure no gap is visible
between the cover and base of the sounder enclosure.
8) Installation Requirements
8.1 Safe Installation Requirements
Warning High voltage may be
present, risk of electric shock.
DO NOT open when energised,
disconnect power before opening.
The sounder must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards.
8.2 Cable Selection and Connections
Electrical connections are to be made into the terminal blocks on the
PCBA, using solid wire 0.5-4mm2 / AWG 20-12 or stranded wire,
sizes 0.5-2.5mm2 / AWG 24-14. Wire insulation needs to be stripped
8mm. Wires may be fitted securely with crimped ferrules. Terminal
screws need to be tightened down with a tightening torque of 0.45
Nm / 3.5 Lb-in.
When selectingthe cablesize, consideration must be givento the input
current that each unit draws (see table 1), the number of sounders on
the line and the length of the cable runs. The cable size selected must
have the necessary capacity to provide the input current to all the
sounders connected to the line.
AC: 1.0 - 2.5mm2/ AWG18 - AWG12
DC: 0.2 - 2.5mm2/ AWG24 - AWG12
Fig 3: Wire Preparation.
When connecting wires to the terminals great care should be taken to
dress the wires so that when the cover is inserted into the chamber
the wires do not exert excess pressure on the terminal blocks. This is
particularly important when using cables with large cross-sectional
areas such as 2.5mm².
8.3 Earthing
Internal earthing connections should be made to the Internal Earth
terminal in the base of the housing using a ring crimp terminal to
secure the earth conductor under the earth clamp. The earth
conductor should be at least equal in size and rating to the incoming
power conductors but at least a mini mum of 0.82mm2 / 18AWG in
size.
8.4 Cable Glands, Blanking Elements & Adapters
Ingress Protection
Adapters
The D1x sounder range can be supplied with the following types of
adapters:
M20 to M25
It is important to note that stopping plugs cannot be fitted onto
adapters, only directly onto the M20 entries.
Internal Earth
Marked with G
External Earth
8mm

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 5 of 8
9) Settings
Following illustrations show the settings available for D1xS2 Alarm
Horn Sounders. See schematic diagram D190-06-001 for details.
9.1 Configuration
See Table 1 for product power supply and Sound Pressure Levels
(SPL).
Configuration for DC Units
Fig 5: DC PCBA.
Configuration for AC Units
Fig 6: AC PCBA .
9.2 Stage Switching Polarity (DC Units)
Switching from positive switching (default) to negative switching - DC
Only.
NOTE: Max supply is 33V DC if higher DC voltage is required, use
Negative switching.
Fig 7: Stage Switching Polarity.
(default)
(default)

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 6 of 8
9.3 Tone Selection
The D1x Alarm Horn Sounders have 64 different tones that can be
selected independently for the first and second stage alarms. The
tones are selected by operation of the tone setting DIP switch 1 & DIP
switch 2 (see fig 8) on the PCB, for stage 1 and stage 2 respectively.
Default = Switch 2
S2 - Tone 1
0 0 0 0 0 0
Default = Switch 1
S1 Tone 44
1 1 0 1 0 1
(ON = 1, OFF = 0)
Figure 8: DIP switch configuration
The sounder can also be switched to sound the third and fourth stage
alarm tones.
The tone table (D221-95-001-IS) shows the switch positions for the 64
tones on first and second stages and which tones are available for the
third and fourth stages dependent on the Stage 1 DIP switch setting.
Following table (Table 3) is a summary of DC: D190-06-001; AC:
D190-06-005 wiring options.
Config.
Voltage
Configuration Description
Features
Product
Option
Identifier
1a
DC
Single Stage Configuration
•Line monitoring
•Positive Switching
1
1b
DC
Two Stage Configuration
•Common Negative
•Positive Switching
1
1c
DC
Three/Four Stage Configuration
•Common Negative
•Positive Switching
1
2
DC
Three/Four Stages. Voltage Free 2nd, 3rd &
4th Stage Activation Configuration
•Common Positive
•Customer Set H1 & H2 to Negative
Switching
1
3
DC
Two Stage Configuration
•Independent Stage Input
•Reverse Polarity Stage Monitoring
1
4
DC
Two Stage Configuration
•Line Stage Monitoring (Use suitable
monitoring relays/ modules)
•Not to be used in reverse polarity
monitoring
Y
5
DC
Two/Three Stage Voltage Free Activation
Configuration
K
6
DC
Three/Four Stage Configuration
•Independent Stage Input
•Line Stage Monitoring (Use suitable
monitoring relays/ modules)
•Positive Switching (Default)
V
1a
AC
Single Stage Configuration
1
1b
AC
Three/Four Stage Configuration
1
2
AC
Two/Three Stage Voltage Free Activation
Configuration
K
Table 3: Summary of Wiring Options. See Document D190-06-001 for DC Schematic Diagrams; D190-06-005 for AC Schematic
Diagrams.

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 7 of 8
10) End of Line Monitoring (DC Units)
10.1 Standard DC End Of Line Monitoring
All DC units have a blocking diode fitted in their supply input lines. An
end of line monitoring diode or an end of line monitoring resistor can
be connected across the +ve and ve terminals in the flameproof
chamber. If an end of line resistor is used it must have a minimum
resistance value of 3k3 ohms and a minimum wattage of 0.5W or a
minimum resistance value of 500 ohms and aminimum wattage of 2W.
The resistor must be connected directly across the +ve and -ve
terminals as shown in the following drawing. The resistor leads should
be kept as short as possible. See D190-06-001 for details.
Figure 9: End of Line Resistor placement.
10.2 Custom DC Multi-Stage End Of Line Monitoring
An optional 12-way terminal module is available to enable up to four
alarm stages to be activated from three DC voltage output channels.
The three alarm stage activation inputs can be independently
monitored.
Refer to Schematic D190-06-001, Config. 6.
when ordering.
Spare part code for field installation: SP78-0001
11) Maintenance, Overhaul and Repair
Maintenance, repair and overhaul of the equipment should only be
carried out by suitably qualified personnel in accordance with the
current relevant standards:
For ATEx/IECEx or UKEx:
EN60079-19/IEC60079-19
Explosive atmospheres Equipment repair, overhaul and
reclamation
EN 60079-17/IEC60079-17
Explosive atmospheres Electrical installations inspection
and maintenance
Units must not be opened while an explosive atmosphere is present.
If opening the unit during maintenance operations, a clean
environment must be maintained and any dust layer removed prior to
opening the unit.
Potential electrostatic charging hazard Clean only with a damp
cloth.
Figure 10: End of Line Resistor placement
Optional 12-Way Terminal Module.

European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
www.e2s.com
Tel: +44 (0)208 743 8880
Document No. D190-00-101-IS
Issue 2
17-03-2022
Sheet 8 of 8
· All models are approved for use as Audible Signal Appliance for use as General Signaling: UL464A & CSA C22.2 No 205-17
· Type 4 / 4X / 3R / 13, IP66
· -55°C to +85°C / -67°C to +176°F
General Signaling Canada:
D1xS2-AC230-A: -55°C to +40°C / -67°F to +104°F
D1xS2-DC024-A, D1xS2-DC024-S: -55°C to +85°C / -67°F to +185°F
· To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
· EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device legs
meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible control panel
specification for EOL device values and ratings
Model
Nominal
Voltage
Voltage Range
P1
Nominal
Operating
Current#
P2
Nominal
Operating
Current#
P3
Nominal
Operating
Current#
P1 Max
Operating
RMS*
P2 Max
Operating
RMS*
P3 Max
Operating
RMS*
D1xS2-DC024-A
12V dc
11.5 - 54V dc
-
289mA
359mA
-
324mA
740mA
24V dc
-
324mA
740mA
48V dc
-
195mA
391mA
D1xS2-AC230-A
115V ac
100- 240V ac
50/60Hz
-
125mA
282mA
-
138mA
325mA
230V ac
-
78mA
167mA
*Max Operating current for worst-case input voltage; Nominal current at nominal voltage and Tone 12
Table 4: UL General Signaling Electrical ratings

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com Page 1 of 1 D221-95-001-IS_Issue_A - 09/03/2021
1000Hz PFEER Toxic Gas
1200/500Hz @ 1Hz DIN /PFEER P.T.A.P.
1000Hz @ 0.5Hz(1s on, 1soff) PFEER Gen. Alarm
1.4KHz-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s NF C 48-265
544Hz(100mS)/440Hz (400mS) NF S 32-001
1500/500Hz - (0.5s on , 0.5s off) x3 + 1s gap AS4428
500-1500Hz Sweeping 2 sec on 1 sec off AS4428
500/1200Hz @ 0.26Hz (3.3son, 0.5s off) Netherlands -
NEN 2575
1000Hz (1s on, 1s off)x7 + (7s on, 1s off) IMO Code 1a
1000Hz (1s on, 1s off)x7 + (7s on, 1s off) IMO Code 1a
420Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal
Pattern
1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal
Pattern
422/775Hz - (0.85 on, 0.5 off) x3 + 1s gap NFPA -
Temporal Coded
1000/2000Hz @ 1Hz Singapore
300Hz Continuous
440Hz Continuous
470Hz Continuous
500Hz Continuous IMO code 2 (Low)
554Hz Continuous
660Hz Continuous
800Hz IMO code 2 (High)
1200Hz Continuous
2000Hz Continuous
2400Hz Continuous
440Hz @0.83Hz (50
cycles/minute) Intermittent
470Hz @0.9Hz - 1.1s Intermittent
470Hz @5Hz - (5
cycles/second) Intermittent
544Hz @ 1.14Hz - 0.875s Intermittent
655Hz @ 0.875Hz Intermittent
660Hz @0.28Hz - 1.8sec
on, 1.8sec off Intermittent
660Hz @3.34Hz - 150mS
on, 150mS off Intermittent
745Hz @ 1Hz Intermittent
800Hz - 0.25sec on, 1 sec off Intermittent
800Hz @ 2Hz IMO code 3.a
(High) Intermittent
1000Hz @ 1Hz Intermittent
2400Hz @ 1Hz Intermittent
2900Hz @ 5Hz Intermittent
363/518Hz @ 1Hz Alternating
450/500Hz @ 2Hz Alternating
554/440Hz @ 1Hz Alternating
554/440Hz @ 0.625Hz Alternating
561/760Hz @0.83Hz (50
cycles/minute) Alternating
800/1000Hz @ 0.875Hz Alternating
2400/2900Hz @ 2Hz Alternating
500/1200Hz @ 0.3Hz Sweeping
560/1055Hz @ 0.18Hz Sweeping
560/1055Hz @ 3.3Hz Sweeping
660/1200Hz @ 1Hz Sweeping
800/1000Hz @ 1Hz Sweeping
800/1000Hz @ 7Hz Sweeping
800/1000Hz @ 50Hz Sweeping
2400/2900Hz @ 7Hz Sweeping
2400/2900Hz @ 1Hz Sweeping
2400/2900Hz @ 50Hz Sweeping
2500/3000Hz @ 2Hz Sweeping
2500/3000Hz @ 7.7Hz Sweeping
800Hz Motor Siren
1200Hz Motor Siren
2400Hz Motor Siren
Stage 1
Set DIP
SW 1
Tone No.
Tone Description Tone Visual
Stage 1 & 2
DIP SW 1/2
Settings
1 2 3 4 5 6
Stage 3
Set DIP
SW 1
(S3)
Stage 4
Set DIP
SW 1
(S2 + S3)
0 0 0 0 0 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
46
47
48
49
50
52
53
54
55
56
57
58
59
60
61
62
63
42
1 0 0 0 0 0
0 1 0 0 0 0
1 1 0 0 0 0
0 0 1 0 0 0
1 0 1 0 0 0
0 1 1 0 0 0
1 1 1 0 0 0
0 0 0 1 0 0
1 0 0 1 0 0
0 1 0 1 0 0
1 1 0 1 0 0
0 0 1 1 0 0
1 0 1 1 0 0
0 1 1 1 0 0
1 1 1 1 0 0
0 0 0 0 1 0
1 0 0 0 1 0
0 1 0 0 1 0
1 1 0 0 1 0
0 0 1 0 1 0
1 0 1 0 1 0
0 1 1 0 1 0
1 1 1 0 1 0
1 1 0 1 1 0
0 0 1 1 1 0
0 1 1 1 1 0
0 0 0 0 0 1
0 1 0 0 0 1
1 1 0 0 0 1
0 0 1 0 0 1
1 0 1 0 0 1
0 1 1 0 0 1
1 1 1 0 0 1
0 0 0 1 0 1
0 1 0 1 0 1
1 0 1 1 0 1
0 1 1 1 0 1
1 1 1 1 0 1
0 0 0 0 1 1
1 0 0 0 1 1
0 1 0 0 1 1
1 1 0 0 1 1
0 0 1 0 1 1
1 0 1 0 1 1
0 1 1 0 1 1
1 1 1 0 1 1
0 0 0 1 1 1
1 0 0 1 1 1
0 1 0 1 1 1
1 1 0 1 1 1
0 0 1 1 1 1
1 0 1 1 1 1
0 1 1 1 1 1
0 0 0 1 1 0
1 0 0 1 1 0
0 1 0 1 1 0
1 1 1 1 1 0
1 0 0 0 0 1
1 0 0 1 0 1
1 0 1 1 1 0
1000Hz
1200Hz
500Hz 1s
1000Hz 1s
1s
1600Hz
1400Hz 1s
0.5s
544Hz 0.1s
0.4s
440Hz
0.5s
1500Hz
500Hz 0.5s 0.5s 0.5s 0.5s 1s
2s 1s
3s 0.5s
1500Hz
500Hz
1200Hz
500Hz
1000Hz
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
1s
7s
7s
420Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1s
1000Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1s
1200Hz
500Hz 0.85 0.5s 0.85 0.5s 0.85
2000Hz
1000Hz
1s
f(Hz)
a(s)
b(s)
(f=440, a=0.6, b=0.6)
(f=470, a=0.55, b=0.55)
(f=470, a=0.1, b=0.1)
(f=470, a=0.43, b=0.44)
(f=655, a=0.57, b=0.57)
(f=660, a=1.8, b=1.8)
(f=660, a=0.15, b=0.15)
(f=745, a=0.5, b=0.5)
(f=800, a=0.25, b=1)
(f=800, a=0.25, b=0.25)
(f=1000, a=0.5, b=0.5)
(f=2400, a=0.5, b=0.5)
(f=2900, a=0.1, b=0.1)
f1(Hz)
a(s)
f(Hz)
f1(Hz)
a(s) a(s)
f(Hz)
(f=363, f1=518, a=0.1)
(f=450, f1=500, a=0.25)
(f=440, f1=554, a=0.5)
(f=440, f1=554, a=0.8)
(f=561, f1=760, a=0.6)
0 0 1 1 0 1
1 1 0 1 0 1
43
44
45
780/600Hz @ 0.96Hz Alternating
800/1000Hz @ 2Hz Alternating
970/800Hz @ 2Hz Alternating
64 Simulated Bell 1 1 1 1 1 1
f1(Hz)
a(s) a(s)
f(Hz)
(f=800, f1=1000, a=0.57)
(f=2400, f1=2900, a=0.25)
f1(Hz)
a(s) a(s)
f(Hz)
(f=800, f1=1000, a=0.25)
f1(Hz) a(s) a(s)
f(Hz)
(f=600, f1=780, a=0.52)
f1(Hz) a(s) a(s)
f(Hz)
(f=800, f1=970, a=0.25)
(f=500, f1=1200, a=3.34)
(f=560, f1=1055, a=5.47)
(f=560, f1=1055, a=0.3)
f1(Hz)
a(s)
f(Hz)
51 600/1250Hz @ 0.125Hz Sweeping (f=600, f1=1250, a=8)
f(Hz)
a(s)
(f=800, a=1.6)
(f=1200, a=2)
(f=2400, a=1.7)
1450Hz 0.25s
0.69ms
(f=660, f1=1200, a=1)
(f=800, f1=1000, a=1)
(f=800, f1=1000, a=0.14)
(f=800, f1=1000, a=0.02)
(f=2400, f1=2900, a=0.14)
(f=2400, f1=2900, a=1)
(f=2400, f1=2900, a=0.02)
(f=2500, f1=3000, a=0.5)
(f=2500, f1=3000, a=0.13)
(f=300)
(f=440)
(f=470)
(f=500)
(f=554)
(f=660)
(f=800)
(f=1200)
(f=2000)
(f=2400)
f(Hz)
0.5s
2
3
2
24
19
44
44
24
34
34
1
1
1
3
44
44
44
24
24
24
24
24
24
24
24
24
24
8
8
24
8
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
8
8
24
8
21
24
24
24
24
24
24
24
24
24
3
20
44
44
44
1
1
1
1
35
1
1
8
8
8
35
8
8
8
8
8
8
8
8
8
19
19
19
19
19
19
19
19
19
19
19
19
19
19
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
1
1
8
8
8
35
35
35
35
35
f1(Hz)
a(s)
f(Hz)

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D190-00-001-IS-UL Issue B 27/10/2021
FIRE INSTRUCTION & SERVICE MANUAL
D1xS Sounder UL464 / CAN/ULC-S525 Fire
Models: D1xS1-DC024-A. D1xS2-DC024-A,
D1xS1-DC024-S. D1xS2-DC024-S,
• -55°C to +85°C / -67°F to +185°F
• Units can be mounted using at least 2 of the 3-off ø7mm holes in the mounting bracket.
• D1xS1RDC024-A & D1xS1RDC024-S are approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 &
CAN/ULC-S525) and produce a minimum sound pressure level of US: 81.62dB(A); CA: 84.8dB(A) at 10 feet, (figures @ worst case
11.5Vdc).
• D1xS1RDC024-A & D1xS1RDC024-S produce a minimum sound pressure level of US: 83.4dB(A); CA: 86.4dB(A) at 10 feet (@24Vdc)
• D1xS1FDC024-A & D1xS1FDC024-S are approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 &
CAN/ULC-S525) and produce a minimum sound pressure level of: US: 92.06dB(A); CA: 98.2dB(A) at 10 feet, (figures @ worst case
11.5Vdc).
• D1xS1FDC024-A & D1xS1FDC024-S produce a minimum sound pressure level of: US: 94.62dB(A); CA: 100.9dB(A) at 10 feet
(@24Vdc)
• D1xS2FDC024-A & D1xS1FDC024-S are approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 &
CAN/ULC-S525) and produce a minimum sound pressure level of P1: US: 93.56dB(A) / P2: US: 94.9dB(A); CA: 101.6dB(A) / P3: US:
95.51dB(A); CA: 101.8dB(A) at 10 feet, (figures @ worst case 11.5Vdc).
• D1xS2FDC024-A & D1xS2FDC024-S produce a minimum sound pressure level of P1: US: 95.64dB(A) / P2: US: 98.42dB(A); CA:
105.2dB(A) / P3: US: 102.7dB(A); CA: 109.4dB(A) at 10 feet (@24Vdc)
• D1xS2HDC024-A & D1xS2HDC024-S are approved for use as an audible signal appliance for fire alarm use – Public Mode (UL464 &
CAN/ULC-S525) and produce a minimum sound pressure level of P2: US: 95.51dB(A); CA: 103.8dB(A) / P3: US: 96.24dB(A); CA:
105dB(A) at 10 feet, (figures @ worst case 11.5Vdc).
• D1xS2HDC024-A & D1xS2HDC024-S produce a minimum sound pressure level of P2: US: 100.2dB(A); CA: 108.5dB(A) / P3: US:
103.5dB(A); CA: 111.6dB(A) at 10 feet (@24Vdc)
• For Fire Alarm applications, the Sounder Volume must be at the highest setting, (see volume control section). For fire alarm use, Tone
12 as shown below must be selected:
• Connection Terminals: Pluggable
AC: 1.0 - 2.5mm2 / AWG18 - AWG12
DC: 0.2 - 2.5mm2 / AWG24 - AWG12
• Terminal Tightening torque 0.4Nm
• To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
• Units can be located indoor or outdoor wet use, wall or ceiling mounted and there are no limitations on orientation
• Factory finishes are not intended to be modified
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70, and the National Fire Alarm
Signaling Code, NFPA 72 or CSA 22.1 Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit
exclusivement être réalisée par du personnel qualifié, conformément au code national d'électricité américain, NFPA 70, et le code national d’alarrme
incendie et de signalisation NFPA 72 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux installations électriques,
Section 32
Attention: Disconnect from power source before installation or service to prevent electric shock / Débranchez-le de la source d'alimentation avant l'instal-
lation ou l'entretien pour éviter tout choc électrique.
Attention: Do not paint / Ne pas Peinturer
1000Hz(0.5s on, 0.5s off)x3 + 1s gap ISO 8201 Temporal
Pattern
Stage 1
Set DIP
SW 1
Tone No.
Tone Description Tone Visual
Stage 1 & 2
DIP SW 1/2
Settings
1 2 3 4 5 6
Stage 3
Set DIP
SW 1
(S3)
Stage 4
Set DIP
SW 1
(S2 + S3)
12 1 1 0 1 0 0
1000Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1s 1 8
Surge Current Ratings for use in fire alarm systems
Model Nominal Voltage Voltage Range Initial Peak Initial RMS
D1xS1-DC024-A
24V dc
11.5 - 54V dc P1: 1312mA P1: 159mA
D1xS1-DC024-SP1: 1312mA P1: 159mA 20 - 28V dc
D1xS2-DC024-A P2: 1005mA / P3: 1267mA P2: 286mA / P3: 553mA11.5 - 54V dc
D1xS2-DC024-S 20 - 28V dc P2: 1005mA / P3: 1267mA P2: 286mA / P3: 553mA

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D190-00-001-IS-UL Issue B 27/10/2021
FIRE INSTRUCTION & SERVICE MANUAL
D1xS Sounder UL464 / CAN/ULC-S525 Fire
Models: D1xS1-DC024-A. D1xS2-DC024-A,
D1xS1-DC024-S. D1xS2-DC024-S,
D1xS1FDC024-A & D1xS1FDC024-S Sounder Directional
Characteristics for Canadian Fire CAN/ULC-S525
OSPL Horizontal Axis Vertical Axis
-3dB(A) +39° / -41° +38° / -41°
-6dB(A) +45° / -47° +64° / -69°
D1xS2FDC024-A & D1xS2FDC024-S Sounder Directional
Characteristics for Canadian Fire CAN/ULC-S525 (P3)
OSPL Horizontal Axis Vertical Axis
-3dB(A) +46° / -48° +46° / -47°
-6dB(A) +52° / -54° +52° / -53°
D1xS1RDC024-A & D1xS1RDC024-S Sounder Directional
Characteristics for Canadian Fire CAN/ULC-S525
OSPL Horizontal Axis Vertical Axis
-3dB(A) +42° / -41° +42° / -41°
-6dB(A) +48° / -48° +48° / -49°
D1xS2HDC024-A & D1xS2HDC024-S Sounder Directional
Characteristics for Canadian Fire CAN/ULC-S525 (P3)
OSPL Horizontal Axis Vertical Axis
-3dB(A) +16° / -21° +15° / -21°
-6dB(A) +40° / -44° +40° / -44°
+
+
-
-
S2 S1
P1 (D1xS1)
P2 (D1xS2)
P3 (D1xS2)

warning signals
2S
D1x
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-001
R.S.RAIT
B.ISARD
R.N.POTTS OF
NTS 1 3
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
RECOMMENDED MINIMUM VALUES:
R1
Stage 1 +ve IN
Stage 1 +ve OUT
Common -ve IN
Common -ve OUT
Stage 2 +ve
Stage 1 +ve IN
Stage 1 +ve OUT
Common -ve IN
Common -ve OUT
Stage 2 +ve
Stage 3 +ve
R1
+
-
-
+
R1
+
-
-
+
S2
R1
+
-
-
+
S2
S3
Stage 1 +ve IN
Stage 1 +ve OUT
Stage 1 -ve IN
Stage 1 -ve OUT
Single Stage Configuration Config.: 1a
Line Monitoring
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Two Stage Configuration Config.: 1b
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve & Common -ve
Three/Four Stage Configuration Config.: 1c
Common Negative
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Common -ve
Stage 2: Apply Power to Stage 2 +ve &Common -ve
Stage 3: Apply Power to Stage 3 +ve &Common -ve
Stage 4: Apply Power to Stage 2 +ve, Stage 3 +ve & Common -ve
19/01/2022
19/01/2022
19/01/2022
D1xS1 / D1xS2 / GNExS1 / GNExS2 / STExS1 /
STExS2 DC SOUNDER WIRING DIAGRAMS
INTRODUCTIONINTRODUCTION
1RSR - 19/01/2022

warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-001
R.S.RAIT
B.ISARD
R.N.POTTS NTS
SWITCHES FOR STAGE OPERATION
CUSTOMER SUPPLIED
Stage 2 -ve
Common +ve IN
Common +ve OUT
Stage 1 -ve OUT
Stage 3 -ve
Stage 1 -ve IN
H2
H1
Stage 1 +ve
Stage 1 -ve
Stage 2 -ve
Stage 2 +ve
OF
2 3
R1
+
-
-
+
S2
S3
R1
+
-
-
+
S2
R2
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
RECOMMENDED MINIMUM VALUES:
R1
Set H1 & H2 to -ve switching
Three/Four Stages. Voltage Free 2nd, 3rd & 4th Stage Activation Configuration Config.: 2
Common Positive
Customer Set H1 & H2 to Negative Switching (See Below)
Stage 1: Apply Power to Common +ve & Stage 1 -ve
Stage 2: Apply Power to Common +ve & Stage 1 -ve & connect Stage 2 -ve to Stage 1 -ve
Stage 3: Apply Power to Common +ve & Stage 1 -ve & connect Stage 3 -ve to Stage 1 -ve
Stage 4: Apply Power to Common +ve & Stage 1 -ve
& connect Stage 2 -ve & Stage 3 -ve to Stage 1 -ve
Two Stage Configuration Config.: 3
Independent Stage Input
Reverse Polarity Stage Monitoring
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Stage 2: Apply Power to Stage 1 +ve & Stage 1 -ve & connect Stage 2 -ve to Stage 1 -ve
H2
H1
Set H1 & H2 to -ve switching
Cut Link W1
INTRODUCTIONINTRODUCTION
1RSR - 19/01/2022
19/01/2022
19/01/2022
19/01/2022
D1x
D1xS1 / D1xS2 / GNExS1 / GNExS2 / STExS1 /
STExS2 DC SOUNDER WIRING DIAGRAMS

Stage 1 -ve
+ve IN
+ve OUT
-ve OUT
Stage 2 -ve
-ve IN/COMMON
warning signals
2S
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-001
R.S.RAIT
B.ISARD
R.N.POTTS NTS
Stage 1 +ve
Stage 1 -ve
Stage 2 +ve
Stage 2 -ve
OF
3 3
R1
+
-
-
+
R1
+
-
-
+
S2
R2
Two Stage Configuration Config.: 4
Line Stage Monitoring (Use suitable monitoring relays/modules)
Not to be used for reverse polarity monitoring
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Stage 2: Apply Power to Stage 2 +ve & Stage 2 -ve
Two/Three Stage Voltage Free Activation Configuration Config.: 5
Customer Set H1 & H2 to Negative Switching (See Below)
Power: +ve & -ve
Stage 1: Connect Stage 1 -ve to Common -ve
Stage 2: Cconnect Stage 2 -ve to Common -ve
Stage 3: Connect both Stage 1 -ve & Stage 2 -ve to Common -ve
CUSTOM
CONFIGURATION
PRODUCT
OPTION 'Y'
Cut Link W1
H2
H1
Set H1 & H2 to -ve switching
CUSTOM
CONFIGURATION
PRODUCT
OPTION 'K'
SWITCHES FOR STAGE OPERATION
CUSTOMER SUPPLIED
OPTIONAL LINE MONITORING RESISTOR, CUSTOMER SUPPLIED,
14V MAX SYSTEM = 120Ω MIN, 2W MIN OR 1KΩ MIN, 0.5W MIN
28V MAX SYSTEM = 470Ω MIN, 2W MIN OR 2.4KΩ MIN, 0.5W MIN
RECOMMENDED MINIMUM VALUES:
R1
Stage 1 +ve IN
Stage 1 +ve OUT
Three/Four Stage Configuration Config.: 6
Independent Stage Input
Line Stage Monitoring (use suitable monitoring relays/modules)
Set to positive switching (default)
Stage 1: Apply Power to Stage 1 +ve & Stage 1 -ve
Stage 2: Apply Power to Stage 2 +ve & Stage 2 -ve
Stage 3: Apply Power to Stage 3 +ve & Stage 3 -ve
Stage 4: Apply Power to Stage 2 +ve & Stage 2 -ve
& Apply Power to Stage 3 +ve & Stage 3 -ve
Stage 1 -ve IN
Stage 1 -ve OUT
Stage 2 +ve IN
Stage 2 +ve OUT
Stage 2 -ve IN
Stage 2 -ve OUT
Stage 3 +ve IN
Stage 3 +ve OUT
Stage 3 -ve IN
Stage 3 -ve OUT
R1R2R3
(CONFIGURATION SHOWS OPTIONAL
ADDITIONAL TERMINAL PCBA -
PRODUCT OPTION 'V')
19/01/2022
19/01/2022
19/01/2022
D1x
D1xS1 / D1xS2 / GNExS1 / GNExS2 / STExS1 /
STExS2 DC SOUNDER WIRING DIAGRAMS
INTRODUCTIONINTRODUCTION
1RSR - 19/01/2022

warning signals
2S
D1x
EUROPEAN SAFETY SYSTEMS LTD
IMPRESS HOUSE
MANSELL ROAD
ACTON
LONDON W3 7QH
WWW.E2S.COM
C
THIS DRAWING AND ANY INFORMATION OR DESCRIPTIVE
MATTER THEREIN IS COMMUNICATED IN CONFIDENCE AND
IS THE COPYRIGHT PROPERTY OF EUROPEAN SAFETY
SYSTEMS LTD. NEITHER THE WHOLE OR ANY EXTRACT MAY
BE DISCLOSED, LOANED, COPIED OR USED FOR
MANUFACTURING OR TENDERING PURPOSES WITHOUT THEIR
WRITTEN CONSENT.
EUROPEAN SAFETY SYSTEMS LTD.
AS PER LATEST DATE OF ISSUE SHOWN ABOVE
DRAWING TO BS8888:2000
GEOMETRIC TOLERANCES TO ISO1101:1983
LINEAR DIMENSIONAL TOLS
ANGULAR DIMENSIONAL TOLS
STANDARDS
MOD No. REASON - INITIAL - DATEISSUE
DATE
APPROVED
CHECKED DATE
DATE
DRAWN WEIGHT (Kg)
SURFACE FINISH
MATERIAL
ALTERNATIVE MATERIAL SHEETSCALE
TITLE
A3
IF IN DOUBT, ASK -
DO NOT SCALE
ALL DIMENSIONS IN MM
DRAWING NUMBER
A
B
C
D
E
F
G
109
G
F
E
78
6
5
D
C
134
2
A
B
D190-06-005
R.S.RAIT
B.ISARD
R.N.POTTS OF
NTS 1
SWITCHES FOR STAGE OPERATION
CUSTOMER SUPPLIED
1
Earth Earth
Stage 2
Stage 3
Common
Live IN
Live OUT
Neutral IN
Neutral OUT
Earth
Stage 1
Stage 2
Common
N
N
L
L
E
N
N
L
L
E
C
N
N
L
L
E
C
S2
S3
Live IN
Live OUT
Neutral IN
Neutral OUT
Stage 1 Live IN
Stage 1 Live OUT
Stage 1 Neutral IN
Stage 1 Neutral OUT
Single Stage Configuration Config.: 1a
Stage 1: Apply Power to Stage 1 Live & Stage 1 Neutral
Two Stage Voltage Free Activation Configuration Config.: 2
Power: Live & Neutral
Stage 1: Connect Stage 1 to Common
Stage 2: Connect Stage 2 to Common
Stage 3: Connect both Stage 1 & Stage 2 to Common
Three/Four Stage Configuration Config.: 1b
Stage 1: Apply Power to Live & Neutral
Stage 2: Apply Power to Live & Neutral
& connect Stage 2 to Common
Stage 3: Apply Power to Live & Neutral
& connect Stage 3 to Common
Stage 4: Apply Power to Live & Neutral
& connect both Stage 2 & Stage 3 to Common
INTRODUCTION
1RSR - 19/01/2022
19/01/2022
19/01/2022
19/01/2022
D1xS1 / D1xS2 / GNExS1 / GNExS2 / STExS1 /
STExS2 AC SOUNDER WIRING DIAGRAMS
CUSTOM
CONFIGURATION
PRODUCT
OPTION 'K'

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐067_Issue_H(D1x).docx‐Page1of2‐QAF_252_Issue_5
EUDeclarationofConformity
Manufacturer: EuropeanSafetySystemsLtd.
ImpressHouse,MansellRoad,Acton
London,W37QH
UnitedKingdom
AuthorisedRepresentative:E2SWarnsignaltechnikUG
Charlottenstrasse45‐51
72764Reutlingen
Germany
EquipmentType: D1xS1,D1xS2
D1xL1,D1xL2
D1xC1X05,D1xC1X10,D1xC2X05,D1xC2X10
D1xB2XH1,D1xB2XH2
Directive2014/34/EU:EquipmentandProtectiveSystemsforuseinPotentiallyExplosiveAtmospheres(ATEX)‐D1xS1,D1xS2,D1xL1,D1xL2,D1xC1X05,D1xC1X10,
D1xC2X05andD1xC2X10only
NotifiedBodyforEUtypeExamination(ModuleB):ULInternationalDemkoA/S
Borupvang5A
2750Ballerup
Denmark
EU‐typeExaminationCertificate(ModuleB):DEMKO19ATEX2141X
NotifiedBodyforQualityAssuranceNotification/ConformitytoEU‐type
basedon
qualityassuranceoftheproductionprocess(ModuleD):
SiraCertificationService
NotifiedBodyNo.:2813
Unit6,HawardenIndustrialPark,Hawarden,Deeside,CH53US,UK
QualityAssuranceNotification(ModuleD):SIRA05ATEXM342
Provisionsfulfilledbytheequipment:II2GExdbIICT6…T3GB
II2DExtbIIICT82C…145CDb
Standardsapplied:EN60079‐0:2018
EN60079‐1:2014
EN60079‐31:2014
Directive2014/30/EU:ElectromagneticCompatibilityDirective(EMC)
Standardsapplied:EN61000‐6‐1:2007
EN61000‐6‐2:2005
EN61000‐6‐3:2007/A1:2011/AC:2012
EN61000‐6‐4:2007/A1:2011
Directive2014/35/EU:LowVoltageDirective(LVD)
Standardsapplied:EN60947‐1:2007+A2:2014
Directive2011/65/EU:Restrictionoftheuseofcertainhazardoussubstancesinelectricalandelectronicequipment(RoHS)
Theproductandallthecomponentscontainedwithinitareinaccordancewiththerestrictionoftheuseofhazardoussubstancesinelectricalandelectronic
equipment,includingamendmentbyDirective2015/863/EU.
Regulation(EC)1907/2006:Registration,Evaluation,AuthorisationandRestrictionofChemicals(REACH)
Theproductandallthecomponentscontainedwithinitarefreefromsubstancesofveryhighconcern.
OtherStandardsandRegulations
EN60529:1992+A2:2013‐Degreesofprotectionprovidedbyenclosures(IPcode)–enclosureratedIP66

E2STelephone:+44(0)2087438880Fax:+44(0)2087404200Email:[email protected]www.e2s.comDC‐067_Issue_H(D1x).docx‐Page2of2‐QAF_252_Issue_5
MartinStreetzDocumentNo.:DC‐067_Issue_H
QualityAssuranceManagerDateandPlaceofIssue:London,10/02/2022
EUDeclarationofConformity
OnbehalfofEuropeanSafetySystemsLtd.,Ideclarethat,onthedatetheequipmentaccompaniedbythisdeclarationisplacedonthemarket,theequipment
conformswithalltechnicalandregulatoryrequirementsoftheabovelisteddirectives,regulationsandstandards.
ThisDeclarationisissuedunderthesoleresponsibilityofthemanufacturer.

E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-097_Issue_A (D1x UKCA).docx - Page 1 of 2 -
QAF_252_Issue_5
UKCA Declaration of Conformity
Manufacturer: European Safety Systems Ltd.
Impress House, Mansell Road, Acton
London, W3 7QH
United Kingdom
Equipment Type: D1xS1, D1xS2
D1xL1, D1xL2
D1xC1X05, D1xC1X10, D1xC2X05, D1xC2X10
Directive UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres
(UKCA)
Notified Body for
UK
type Examination
(Module B)
:
UL International (UK) Ltd
Notified Body No.: 0843
Unit 1-3 Horizon Kingsland Business Park, Wade Road,
Basingstoke, Hampshire RG24 8AH UK
UK
-
type Examination Certificate (Module B):
UL21UKEX2132X
Notified Body for Quality Assurance Notification
/
Conformity to EU
-
type
based on
quality assurance of the production process (Module D):
Sira Certification Service
Notified Body No.: 0518
Rake Lane, Eccleston, Chester CH4 9JN, UK
Quality Assurance Notification
(Module D)
:
CSAE 22UKQAN0046
Provisions fulfilled by the
equipment:
II 2G Ex db IIC T6…T
3
GB
II 2D Ex tb IIIC T82 C…145 C Db
Standards applied:
EN 60079
-
0:2018
EN 60079-1:2014
EN60079-31:2014
Directive 2014/30/EU: Electromagnetic Compatibility Directive (EMC)
Standards applied:
EN
61000
-
6
-
1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007 / A1:2011 / AC: 2012
EN 61000-6-4:2007 / A1: 2011
Directive 2014/35/EU: Low Voltage Directive (LVD)
Standards applied:
EN
60947
-
1:2007
+
A2:2014
Directive 2011/65/EU: Restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)
The product and all the components contained within it are in accordance with the restriction of the use of hazardous substances in electrical and electronic
equipment, including amendment by Directive 2015/863/EU.
Regulation (EC) 1907/2006: Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH)
The product and all the components contained within it are free from substances of very high concern.
Other Standards and Regulations
EN 60529:1992+A2:2013 - Degrees of protection provided by enclosures (IP code) – enclosure rated IP66

E2S Telephone: +44 (0)20 8743 8880 Fax: +44 (0)20 8740 4200 Email: [email protected] www.e2s.com DC-097_Issue_A (D1x UKCA).docx - Page 2 of 2 -
QAF_252_Issue_5
Martin Streetz Document No.: DC-097_Issue_A
Quality Assurance Manager Date and Place of Issue: London, 24/02/2022
EU Declaration of Conformity
On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment
conforms with all technical and regulatory requirements of the above listed directives, regulations and standards.
This Declaration is issued under the sole responsibility of the manufacturer.

Page left Intentionally blank
This manual suits for next models
3
Table of contents
Other E2S Marine Equipment manuals

E2S
E2S Sontel BExTS110DAC115 User manual

E2S
E2S BExCS110-05D-PDC012 User manual

E2S
E2S AlertAlarm A105N User manual

E2S
E2S GNExS2 User manual

E2S
E2S A105NSONTEL User manual

E2S
E2S IS-pA1 User manual

E2S
E2S BExDTS110D User manual

E2S
E2S GNExS1RDC024-S User manual

E2S
E2S A112N User manual

E2S
E2S D1xC1 Series User manual

E2S
E2S Appello A121APPX User manual

E2S
E2S D2xS2F Series User manual

E2S
E2S BE*H120D User manual

E2S
E2S Minialarm IS-mA1 User manual

E2S
E2S D1xS1RDC024-S User manual

E2S
E2S SONF1DC024 X Y Series User manual

E2S
E2S E2xS2FDC024 User manual

E2S
E2S MA1 Series User manual

E2S
E2S E2XS112UL User manual

E2S
E2S BExCS110-05D User manual