Elko TER-9 User manual

1 / 8
TER-9
cos φ ≥ 0.95 M M HAL.230V
KM M
AC12
250V / 1A
DC14
x
AC1
250V / 8A
AC13
x
AC2
250V / 3A
AC14
250V / 3A
AC3
250V / 2A
AC15
250V / 3A
AC5b
300W
DC5
24V / 2A
AC6a
x
DC12
24V / 8A
AC7b
250V / 1A
DC13
24V / 2A
02-21/2017 Rev.: 1
DC1
24V / 8A
DC3
24V / 3A
Un
15 16 18 25 26 28
A1 A2 T1 T1 T2 T2
15 25
16
A2
A1
°C
T1
T1
T2
T2
18 26 28
6
1
5
2
3
4
7
8
9
TER-9
ManProgAuto + t
10
11
12
13
14
15
16
17
18
19
20
21
22
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: [email protected]
www.elkoep.com
Multifunction digital thermostat
Characteristics
Description
Connection
Type of load
Mat. contacts AgNi,
contact 8A
Type of load
Mat. contacts AgNi,
contact 8A
AC5a
uncompensated
230V / 1.5A (345VA)
AC5a
compensated
x
EN
- digital thermostat with 6 functions and built-in time switch clock with day, week
and year program. You can also limit temperature functions and courses this way
in real time.
- the temperature prole can be changed using the time program.
- complex home and water heating, solar heating, etc.
- two thermostats in one, two temperature inputs, two outputs with dry contact.
- maximum universal and variable thermostat including all ordinary thermostat
functions.
- functions: two independent thermostats, dependent thermostat, dierential ther-
mostat, two level thermostat, zone-based thermostat, dead zone thermostat.
- monitoring function for short circuit or sensor disconnection.
- program setting of output functions, calibration of sensors according to reference
temperature (oset).
- the thermostat is subject to the digital clock programs.
- wide range for setting control temperature - 40 to 110°C.
- clear display of set and measured data on a backlit LCD.
- Switching modes:
- Auto – automatic switching mode:
- Programme – switching based on a programme (astro or time).
- Random – switches randomly in a 10–120 minute interval.
- Holiday – holiday mode – option of setting up a period for which the timer will
be blocked, i.e. will not switch based on the set programmes.
- Manual – manual mode – option of controlling the individual output relays
manually.
- Options of the automatic switching programme:
- ter - switches according to set thermostat function (switches based on tempera-
ture sensors and associated function).
- time program - switches or sets required temperature according to set time pro-
gram.
- 100 memory locations for time programs (common for both channels).
- Programming can be performed under voltage and in backup mode.
- The relay outputs do not work in backup mode (battery-powered).
- Choice of menu display - EN / CZ / RU / HU / ES / PL / SK (factory setting EN).
- Choice of automatic daylight savings time transition according to time zone.
- Backlit LCD display.
- Easy and quick setting with the help of 4 control buttons.
- Pluggable transparent cover on front panel.
- The time switch clock has a battery backup, which retains data in case of a power
outage (reserve backup time - up to 3 years).
- Power supply: AC 230V or 24V AC/DC (based on type of device).
- 2-module, DIN rail mounted.
Symbol
Sensor 1 Sensor 2
1. Supply voltage terminals
2. Display with back-light
3. Place for seal
4. Plug-in module for replacing backup
battery
5. Output - channel 1 (15-16-18)
6. Terminals - sensor 1
7. Terminals - sensor 2
8. Control buttons
9. Output - channel 2 (25-26-28)
10. Indicates the day in the week
11. Indication (1st channel)
12. Indication (2nd channel)
13. Display of data / settings menu / or
display of current measured temperature
14. Time display
15. Control button PRG / +
16. Reset
17. Control button MAN1 / -
18. Operating modes indication
19. 12/24 hours format / AM <− ; PM
−>
20. Indication of the switch program
21. Control button MAN2 / ESC
22. Control button OK. Switches display
date / measured temperature of channel
1, 2
CONTROL OF A DISPLAY WITH BACKLIGHT
Power on: Display is illuminated with a
backlight for 10 seconds from the last but-
ton press. The display continuously shows
the settings – date, time, day of the week,
contact state and programme. Permanent
on / o is activated by simultaneous press-
es of the MAN, ESC, OK buttons.
After activating the permanent on/o, the
display will ash briey.
Backup mode: After 2 minutes, the display
switches to the sleep mode, i.e. shows no
information. The display can be activated
by pressing any button.

2 / 8
TER-9
TC TZ
14.7
9.8
6.6
4.6
3.2
2.3
20
30
40
50
60
70
PRG
OK
+_OK
+_
Prog
OK
Auto
Prog
ter
Prog
options
Prog
language
Prog
Prog
Prog
Prog
ESPAnOL
Prog
Prog
Technical parameters
Supply
Supply terminals:
Supply voltage:
Consumption:
Supply voltage tolerance:
Backup battery type:
Measuring circuit
Measuring terminals:
Temperature range:
Hysteresis (sensitivity):
Diference:
Sensor:
Sensor failure indication:
Accuracy
Measuring accuracy:
Repeat accuracy:
Temperature dependance:
Number of function:
Output
Number of contacts:
Rated current:
Switching capacity:
Switching voltage:
Output indication:
Mechanical life:
Electrical life (AC1):
Time circuit
Real time back-up:
Accuracy:
Minimum interval:
Data stored for:
Program circuit
Number of memory places:
Program:
Data readout:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage cathegory:
Pollution degree:
Max. cable size (mm2):
Dimensions:
Weight:
Standards:
A1 - A2
AC 230 V (AC 50-60 Hz), galvanically isolated or
AC/DC 24 V, not galvanically isolated
max. 4 VA
-15 %; +10 %
CR 2032 (3V)
T1-T1 a T2-T2
-40.. +110 °C
adjustable within range 0.5...5 °C
adjustable 1 .. 50 °C
thermistor NTC 12 kΩ at 25 °C
displayed on LCD *
5 %
< 0.5 °C
< 0.1 % / °C
6
1x switching for each output (AgNi)
8 A / AC1
2000 VA / AC1, 240 W / DC
250 V AC1 / 30 V DC
symbol ON/OFF
1x107
1x105
up to 3 years
max. ±1s/ day at 23°C
1 min.
min. 10 years
100
daily , weakly, yearly
LCD display, with back light
-10.. +55 °C
-30.. +70 °C
4 kV (supply - output)
any
DIN rail EN 60715
IP40 from front panel / IP20 clips
III.
2
max. 1x 2.5, max. 2x 1.5 /
with sleeve max. 1x 2.5
90 x 35.6 x 64 mm
(230V) 127 g, (24V) 120 g
EN 61812-1; EN 61010-1;
EN 60730-2-9; EN 60730-1; EN 60730-2-7
* ERROR - sensor short circuit
NO SENSOR - interruption sensor
Temperature sensor TC, TZ
Temperature (°C) NTC sensor (kΩ)
Tolerance of sensor NTC 12 kΩ is ± 5% at 25 °C.
Resistance value of sensors based on temperature
Mode precendence
mode precedence
display output mode
ON / OFF
manual control
ON / OFF holiday mode
ON / OFF time program Prog
ter thermostat
mode with the highest
priority
ter and Time Program can work at the same time on a single channel.
Language settings
language
Language
selection
options
PRG entrance into programming menu
+_
browsing in menu
setting of values
+_quick shifting during setting of values
OK
entrance into required menu
conrmation
switch. between display
ESC
one level up
a step back
ESC back to the starting menu
Control description
Device diers short and long button press. In the manual marked as:
- short button press (<1s)
- long button press (>1s)
After 30s of inactivity (from the last press of any button) will device automatically returns
into starting menu.
In the start screen, press OK to toggle between displaying the date or measured
temperature.

+_
Auto
Prog
Prog
Prog
Prog
Prog
Prog
+_
+_
+_
+_
OK OK OK OK OKOK OK
OK OK OK OK OK OK
OK OK OK
OK OK OK
OK OK OK
PRG
+_
Prog Prog
Prog Prog
Prog Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
OK OK
OK
+_
+_
+_
+_
+_
+_
+_
+_
+_
+_
+_
+_
Prog
Prog
Prog
Auto
PRG OK OK
OK OK
OK
OK OKOK
OK
OK OK
+_
+_
ESC
ESC
ESC
ESC
ESC
ESC
Prog
Prog Prog
OK
OK
OK
+_
Prog
Prog
on
OK OK
OK
+_
Prog
Prog
on
Prog
Prog Prog
+_
+_
ESC
ESC
Prog
Prog
OK OK
Prog
°C
Prog
°C
Prog
°C
Prog
°C
3 / 8
Menu overview
setting the display
of the time format
setting the display
of the date format
setting the display
of the week day
setting the switch
from the summer
to the winter time
setting the datesetting the
current time
add a
program
edit the program delete a program
setting and
adjusting the
time program
time date su-wi week day date form time form
add edit delete
setting the
time and date
manual modesetting the
holiday mode
setting the auto
switching mode
setting the
language
operating hours
for individual
channels
setting time correction
by ± 12.6 s / day
switch
modes
device
options
holiday manual
language
operating ho
time correct
AUTO
time/date
time prog
modes
options
end
selection of
thermostat functions
temperature
settings
hysterezis
setting
temperature
dierence settings
delay settings upon
switching on/o
measured
temperature change
setting
temperature units
thermostat
settings
function temperatur hysteresi differenc delay offset units
ter
16--sep-- 10
TER display and settings
selection of
thermostat
functions
temperature
settings
hysterezis
setting
channel choice
temperature settings
channel choice
oset setting in
a range of ±20
channel choice
channel choice
hysteresis setting in
range of 0.5 - 5 °C (F)
function selection
temperature
dierence
settings
delay settings
upon switching
on/o
measured
temperature
change
TER
function function
temperatur temperatur
hysteresi hysteresi
differenc differenc
channel
channel
channel
channel
set
channel
channel
channel
channel
delay delay
offset offset
ON - switching on,
OFF - switching o
dierence setting in a
range of 1-50 °C (F)
delay setting 0-60
seconds
If the function TER is active, then symbol„Auto“ is displayed on the screen.
If the entered switching delay is shown on the display„Auto + t“.
16--SEP-- 10
selection of unit
setting
temperature
units
set
set
units units
end
- long press (>1s)
- short press (<1s)

4 / 8
T1
Ts1
dy1 dy2 dy1 dy2
15-18
H1
H1
25-28
T2
Ts2
dy1 dy2 dy1 dy2
H2
H2
H2
T1
H1
T2 Ts2
Ts1
15-18
15-18
25-28
dy1 dy2 dy1 dy2
dy1 dy2 dy1 dy2 dy1
dy1 dy2 dy1 dy2
H2
H2
H1
H1
T
15-18
25-28
T1
Ts
H1
H2
D
dy2
dy1
dy1dy2
dy1 dy2 dy1 dy2
dy1
H1
H1
H2
H2
15-18
25-28
T1
T2
Ts
dy1 dy2
H1
H2
D
dy1 dy2
dy1 dy2
dy1 dy2 dy1 dy2
dy1 dy2
H2
H2
H1
H1
T
T1
Ts
15-18
25-28
T2
D
H
1
H2
dy1 dy2 dy1
dy1 dy2
T
H2
H2
H1
H1
25-28
15-18
Ts1
Ts2
D
D-H1
D
D-H2 D
dy1
dy1 dy2
dy1
dy2
1. 2 independent single-stage thermostat
Heater function
Heater function
2. Dependent functions of 2 thermostats
Thermostat functions
3. Dierential thermostat
Legend:
Ts1 - real (measured) temperature 1
Ts2 - real (measured) temperature 2
T1 - adjusted temperature T1
T2 - adjusted temperature T2
H1 - adjusted hysteresis for T1
H2 - adjusted hysteresis for T2
dy1 - set switching delay of the output
dy2 - set delay on output breaking
15-18 output contact (for T1)
25-28 output contact (for T2)
Legend:
Ts1 - real (measured) temperature 1
Ts2 - real (measured) temperature 2
T1 - adjusted temperature T1
T2 - adjusted temperature T2
H1 - adjusted hysteresis for T1
H2 - adjusted hysteresis for T2
dy1- set switching delay of the output
dy2 - set delay on output breaking
25-28 output contact (for T2)
15-18 output contact (intersection T1 and T2)
Output contact switched until adjusted temperature is reached.
Hysteresis eliminates frequent switching. Heating/cooling func-
tion adjusted in the menu.
Output 15-18 is closed, if temperature of both thermostats is bel-
low an adjusted level. When any thermostat reaches adjusted lev-
el, the contact 15-18 open. Serial inner connection of thermostats
(logic function AND).
4. 2-stage thermostat
5. Thermostat with “WINDOW”
Legend:
Ts - real (measured) temperature T1
D - adjusted dierence
T1 - adjusted temperature T1
T=T1-D
H1 - adjusted hysteresis for T1
H2 - adjusted hysteresis for T
dy1- set switching delay of the output
dy2 - set delay on output breaking
15-18 output contact
25-28 output contact
Legend:
Ts - real (measured) temperature
T1 - adjusted temperature
T=T1-D
H1 - adjusted hysteresis for T1
H2 - adjusted hysteresis for T
dy1- set switching delay of the output
dy2 - set delay on output breaking
15-18 output contact
25-28 output contact
Typical example of use for two-stage thermostat is e.g in boiler-
room, where there are two biolers from which one is main and the
other one is auxiliary. The main boiler is managed according to set
temperature and auxiliary boiler is switched in case temperature
falls under set dierence. Thus it helps to the main boiler in case
outside temperature dramatically falls. In the range of set dier-
ence (D) output 15-18 functions as normal thermostat to input 1
(type 1). In case temperature falls under set dierence, output 2
switches.
Output is closed (heating) only if temperature is within adjusted
range.If temperature is out of range, the contact opens. T is set as
T1-D. The function is used for protection of gutters against freez-
ing.
Legend:
Ts1 - real (measured) temperature T1
Ts2 - real (measured) temperature T2
D - adjusted dierence
dy1- set switching delay of the output
dy2 - set delay on output breaking
15-18 output contact (for T1)
25-28 output contact (for T2)
Switching of output corresponds with input, which has lower
temperature when diference is exceeded dierencial thermo-
stat is used for keeping two identical temperature e.g. in heating
systems (boiler and reservoir), solar systems (collector, reservoir
exchanger), water heating (water heater, water distribution)etc.
6. Thermostat with dead zone
Legend:
Ts - real (measured) temperature
T1 - adjusted temperature
T=T1-D
H1 - adjusted hysteresis for T1
H2 - adjusted hysteresis for T
dy1- set switching delay of the output
dy2 - set delay on output breaking
15-18 output contact (heating)
25-28 output contact (cooling)
In case of thermostat with a „dead zone“, it is possible to set tem-
perature T1 and a dierence (respectively a width of dead zone D).
If temperature is higher than T1, output contact of cooling switch-
es ON; if the temperature gets bellow T1, the contact switches
OFF. If the temperature gets bellow temperature T, the contact
of heating switches ON and it switches OFF when temperature T
is exceeded. This function can be used for example for automatic
air warming and cooling in ventilation so the sit is always within
the range T1 and T.

5 / 8
OK OK
OK
OK
+_
+_
+_
+_
Prog
+_
Prog
ProgProg Prog
OKOK
+_+_+_
Prog Prog
OK
+_
Prog
OK
ESC
Prog Prog
OK
ESC
Prog Prog
ESC
Prog
Prog
Prog
Prog
OK
+_
+_
+_
+_
Prog
OK
OK
+_
+_
ESC
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
OK
Prog
ESC
Prog
Prog
Prog
Prog
Prog
Prog
Prog
OK
+_
OK
Prog
Prog
OK
ESC
ESC
Auto
PRG
Prog
ter
Time and date setting
setting the hours
setting
the time
setting
the date
setting the
switch between
the summer /
winter time
setting the monthsetting the year setting the day
setting the minutes
setting the switch between the summer
and winter time depending on area
time/date time hour minute time
date year month day date
su-wi
su-wi eur
su-wi usa
su-wi rus
no su-wi
su-wi
setting the
week day
date
format
time
format
week day
date form
16 sep 10
16/sep/10
16--sep--10
week day
date form
time form
time form
12h
24h
end
- long press (>1s)
- short press (<1s)
After entering the date is normally calculated and numbered by day of the week: Monday = rst day of the week.
Numeral showing the day of the week, may not correspond to the calendar day of the week. It can be set in the menu „Display settings of the week“. Set the number from the set to
the current date.
Note: After the date is changed, the numbering of days back to the standard numbering ie Monday = rst day of the week.
16--sep-- 10

6 / 8
Prog
Prog
OK OK
+_
OK
Prog ProgProg
+_
OK
Prog
OK
+_
Prog
Prog
Prog
OK
Prog
+_
OK
Prog
OK
+_
OK
+_
+_
OK
OK
OK
+_
Prog Prog
OK
+_
OK OK
Prog
OK +_
ESC
ESC
+_
Prog Prog
OK
+_
OK OK
Prog
OK
+_
ESC
+_
+_
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
on
Prog
Prog
Prog
Prog
Prog
Prog
Prog
Prog
on
Prog
on
Prog
Prog
°C
Prog
OK
ProgProg Prog
OKOK
+_+_+_
OK OK
Prog
+_
Prog Prog
OK
+_
OK
+_
Prog
on
Prog
Prog
°C
Prog
on
Prog
Prog
°C
Prog
ESC
+_
Prog
Prog
OK
OK
Prog
OK
+_
Prog
OK
ProgProg Prog
OKOK
+_+_+_
OK OK
Prog
+_
Prog Prog
OK
+_
OK
ESC
+_
Prog
on
Prog
Prog
°C
*
+_
Auto
PRG
Prog
ter
add a
program
channel choice
Time program
adjusting
the channel
program
choice *
daily
program
yearly
program
adjusting
the daily
program
edit
program
time prog add prog
channel
channel
day prog
year prog
edit prog
channel
channel
day prog
setting the
minutes
setting the
hour
setting the program
activity on a week day
setting the
month
setting the
year
setting the
day
setting the
minutes
setting the
hours
adjusting the
setting of
hours
adjusting the
setting of
minutes
adjusting the setting of program
activity on a week day
hour
hour
hour
daymonthyear
minute
minute
minute
add
add
add
setting for temperature toggle
level or constant ON/OFF
setting for temperature
toggle level or constant
ON/OFF
setting for temperature toggle
level or constant ON/OFF
choosing the
program *
adjusting the
yearly program
delete the
program
delete delete
end
year prog
prog
adjusting
the setting
of the month
adjusting
the setting
of the year
adjusting
the setting
of the day
adjusting
the setting
of minutes
adjusting
the setting
of hours
year month day hour minute add
- long press (>1s)
- short press (<1s)
setting for temperature
toggle level or constant
ON/OFF
1. ON - permanently ON
1. OFF - always o
1. OR - controlled by twilight switch
By shortly pressing OK , you can toggle between the program number and the display of its settings. Use +_to toggle preset programs. By holding OK you can proceed with the required step -
CHANGE / DELETE. If you do not want to proceed, press ESC to go to the main settings without any change.
If the program memory is full, you will see full on the display.
If the programs memory is empty and you want to change or erase a program, the display will read empty.
16--sep-- 10

Prog Prog Prog
Prog
Prog
Prog
Prog
ESPAnOL
Prog
Prog
ProgProg Prog
ProgProg ProgProg Prog Prog
7 / 8
OK
+_
+_
Prog
Prog
ESC
Prog
Prog
Prog
OK
+_
Prog
+_
Prog
Prog
OK
+_
OK
OKOK
+_+_+_
OK OK
OK
ESC
OK
Prog
ESC
+_
ESC
+_
Prog
OKOK
+_+_+_
OK
ESC
OK
+_
+_
OK
OK
OK
ESC
ESC
Prog
Prog
Prog
Prog
Prog
Prog
Prog
OK OK
Prog
Prog
Prog
+_
Prog
Prog
ESC
+_
OK
ESC
Prog
+_
OK OK
+_
ESC
OK
+_
Auto
PRG
Prog
ter
Prog
OK OK OK
+_
Prog
auto
Prog
auto
Prog
Prog
Prog
on
+_
Auto
PRG
Prog
ter
+_
automatic
switch
mode
holiday
mode
choosing the channel
choosing the channel
setting the start of the holiday mode
manual
mode
choosing the switching
program
switching on the
manual mode
modes
channel
holiday on year
holiday
inactive
manualmanual
channel
channel
end
month day
channel
prog
random
Setting the switching modes
- long press (>1s)
- short press (<1s)
setting the end of the holiday mode
year month day holiday
What you see on the display:
- when a random mode is activated - Random - the symbol is lit .
- vacation mode HOLIDAY:
- the illuminated symbol indicates the vacation mode.
- the ashing symbol indicates the vacation mode.
- the symbol is not illuminated if the vacation mode is not set or has.
- when the manual mode is activated, the symbol is lit and the manually controlled channel is ashing.
Settings options
Time correction:
The shift unit is 0.1s per day.
The numeric value refers to seconds per 10 days.
Time correction is factory-set and individual for each product so that the real-time clock would run with minimum deviation. The time correction value can be arbitrarily adjusted, but after product
RESET, the value returns to factory settings.
operating
hours
channel settings total number of hours
of switching when the
device is connected to
the selected channel
time correction by
±12.6 s/day
time
correction
operating
time corr
end
time corr
time corr
time corr
channel
channel clear
operating
language
choice
options language language
operating
show
16--sep-- 10
16--sep-- 10

Prog Prog ProgProg ProgProg Prog ProgProg
°C
Prog
°C
Prog
Prog
ter
Auto
8 / 8
Auto
TER-9 TER-9
Auto
TER-9
Prog
OK
OK
PRG +
Auto
ESC
OK
OK
OK
OK OK
OK OKOK OK OK OK
OK
Prog
+_+_
+_
+_
+_
+_
OK
OK
OK
OK
Prog
+_
+_
+_
+_
+_
+_
ProgProg
°C
Prog
°C
Prog
ESC OK
OK OK OK
Prog
Prog Prog
Prog
ProgProg Prog
OKOK
+_+_+_
OK
Prog
+_
Prog Prog
OK
+_
OK
ProgProg
+_
Prog
on
Prog
°C
CR2032
+
PRG
Auto
Prog
ter
Performed by shortly pressing the hidden RESET button with a blunt-pointed object (e.g. a pencil
or screw-driver with a diameter of at most 2 mm).
The type of device and software version will be displayed for 1 second, then the device will enter
default mode. This means that the language is set to EN, all data is zeroed (thermostat function,
time/date, user programs, device options function).
Reset
press button OK to complete
the deleting of all set programs
in starting menu (time is shown
on display) - press simultaneously
button PRG and OK and display
announces a notice all
Deleting of all programs
all
16--sep-- 10
An example of TER-9 programming
Battery replacement
You can change the battery without disassembling the device.
CAUTION
- only change the battery when the device is disconnected from power supply !!!
- the date and time must be reset after changing the battery !!!
- remove the plug-in module with the battery
- replace the original battery
- enter a new battery so that its upper edge (+) lines up with the plug-in module
- slide the plug-in module in the device and pay attention to polarity (+ up) – for roughly 1 s,
the display will show the name and the software version
- you can connect the device to power supply
Setting the TER-9 in the function: two dependent thermostats with temperature setting T1 = 10°C a T2 20 °C with hysteresis setting T1 = 2 °C a T2 = 1°C.
With automatic controlled temperature change on 18.11.2010 at 6:52 p.m. to the temperature T1= 15 °C.
function function temperatur temperatur temperatur hysteresi
hysteresi hysteresi
set
channel channelchannel
channel channel
time prog add
add
prog year prog
year month day hour minute
day prog
- long press (>1s)
- short press (<1s)
16--sep-- 10
16--sep-- 10
Warning
Device is constructed for connection in 1-phase main alternating current voltage AC 230 V or
24 V AC/DC (based on type of device) and must be installed according to norms valid in the
state of application. Connection according to the details in this direction. Installation, con-
nection, setting and servicing should be installed by qualied electrician sta only, who has
learnt these instruction and functions of the device. This device contains protection against
overvoltage peaks and disturbancies in supply. For correct function of the protection of this
device there must be suitable protections of higher degree (A, B, C) installed in front of them.
According to standards elimination of disturbancies must be ensured. Before installation the
main switch must be in position “OFF” and the device should be de-energized. Don´t install
the device to sources of excessive electro-magnetic interference. By correct installation en-
sure ideal air circulation so in case of permanent operation and higher ambient temperature
the maximal operating temperature of the device is not exceeded. For installation and setting
use screw-driver cca 2 mm. The device is fully-electronic - installation should be carried out
according to this fact. Non-problematic function depends also on the way of transportation,
storing and handling. In case of any signs of destruction, deformation, non-function or missing
part, don´t install and claim at your seller it is possible to dismount the device after its lifetime,
recycle, or store in protective dump.
Other manuals for TER-9
3
Table of contents
Other Elko Thermostat manuals