EVCOS.p.A.|EV3B71/EV3B81|Instructionsheetver.1.0|Code1043B71E103|Page1of2|PT05/22
EV3B71/EV3B81 Controllers for refrigerated units,
with compressor protection against mains voltage fluctuations
E ENGLISH
- Controllers for normal temperature units
- Power supply 115... 230 VAC
- Cabinet probe (PTC/NTC)
- Door switch/multi-purpose input
- Compressor relay rated 16 res. A @ 250 VAC (EV3B71) or 30 res. A @ 250 VAC
(EV3B81)
- Compressor protection against mains voltage fluctuations
- Cooling or heating operation
1 MEASUREMENTS AND INSTALLATION
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided.
INSTALLATION PRECAUTIONS
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in)
- Ensure that the working conditions are within the limits stated in the TECHNICAL
SPECIFICATIONS section
- Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations
or shocks
- In compliance with safety regulations, the device must be installed properly to ensure
adequate protection from contact with electrical parts. All protective parts must be
fixed in such a way as to need the aid of a tool to remove them
2 ELECTRICAL CONNECTION
N.B.
- Use cables of an adequate section for the current running through them
- To reduce any electromagnetic interference connect the power cables as far away
as possible from the signal cables
PRECAUTIONS FOR ELECTRICAL CONNECTION
- If using an electrical or pneumatic screwdriver, adjust the tightening torque
- If the device has been moved from a cold to a warm place, the humidity may have
caused condensation to form inside. Wait about an hour before switching on the power
- Make sure that the supply voltage, electrical frequency and power are within the set
limits. See the section TECHNICAL SPECIFICATIONS
- Disconnect the power supply before doing any type of maintenance
- Do not use the device as safety device
- For repairs and for further information, contact the EVCO sales network
3 FIRST-TIME
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA-
TION.
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal
test will be run.
The test normally takes a few seconds, when it is finished the display will switch off.
3. Configure the device as shown in the section Setting configuration parameters.
Recommended configuration parameters for first-time use.
PAR. DEF. PARAMETER MIN... MAX.
SP 0.0 setpoint r1... r2
P0 1 probe type 0 = PTC 1 = NTC
P2 0 temperature unit of measurement 0 = °C 1 = °F
Then check that the remaining settings are appropriate; see the section CONFIGURA-
TION PARAMETERS.
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with-
out powering up the device.
6. Power up the device.
4 USER INTERFACE AND MAIN FUNCTIONS
4.1 Switching the device on/off
1. If POF = 1, touch the ON/STAND-BY key for 4 s.
If the device is switched on, the display will show the P5 value ("cabinet temperature" default);
if the display shows an alarm code, see the section ALARMS.
LED ON OFF FLASHING
compressor on
compressor off
- compressor protection active
- setpoint setting active
defrost active
-
- defrost delay active
- dripping active
reserved
-
-
HACCP
reserved - -
energy saving active
-
-
reserved
-
-
°C/°F
view temperature
-
-
AUX reserved - -
device off
device on
device on/off active
If 30 s have elapsed without the keys being pressed, the display will show the “Loc” label and
the keypad will lock automatically.
4.2 Unlock keypad
Touch a key for 1 s: the display will show the label “UnL”.
4.3 Set the setpoint
Check that the keypad is not locked.
1. Touch the SET key.
2. Touch the UP or DOWN key within 15 s to set the value within
the limits r1 and r2 (default “-40... 50”)
3. Touch the SET key (or do not operate for 15 s).
4.4 Activate manual defrost (if r5 = 0, default)
Check that the keypad is not locked and that overcooling is not active.
1. Touch the UP key for 2 s.
If P4 = 1 (default), defrost is activated provided that the evaporator temperature is lower than
the d2 threshold.
4.5 Cabinet light on/off (if u0 = 3, default or if u1 = 3)
1. Touch the ON/STAND-BY key.
4.6 Button-operated load on/off (if u0 = 1)
Check that the keypad is not locked.
1. Touch the ON/STAND-BY key (for 2 s if u1 = 3).
5 ADDITIONAL FUNCTIONS
5.1 View/delete compressor functioning hours
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH view compressor functioning hours (hundreds)
rCH delete compressor functioning hours
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (when label “rCH” is se-
lected).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.2 View the temperature detected by the probes
Check that the keypad is not locked.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature
Pb2 auxiliary temperature (if P4 = 1 or 2)
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
5.3 View the mains voltage
Assicurarsi che la tastiera non sia bloccata.
1. Touch the DOWN key for 4 s.
2. Touch the UP or DOWN key within 15 s to select “UOL”.
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4. Touch the SET key (or do not operate for 15 s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15 s to set the value.
8. Touch the SET key (or do not operate for 15 s).
9. Touch the SET key for 4 s (or do not operate for 60 s) to exit the
procedure.
6.2 Restore the factory settings (default) and store customized settings as default
N.B.
- Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS
- the storing of customized settings overwrites the default
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15 s to set the value.
VAL. DESCRIPTION
149 value to restore the factory settings (default)
161 value to store customized settings as default
4.
Touch the SET key (or do not operate for 15 s): the display will
show the label “dEF” (when value “149” is set) or the label
“MAP” (when value “161” is set).
5. Touch the SET key.
6. Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or do not operate for 15 s): the display will
show for 4 s “- - -“ flashing, then the device will exit the proce-
dure.
8. Interrupt the power supply to the device.
9. Touch the SET key 2 s before action 6. to exit the procedure be-
forehand.
7 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2 CA1 0.0 cabinet probe offset -25... 25 °C/°F
3 CA2 0.0 auxiliary probe offset -25... 25 °C/°F
4 P0 1 probe type 0 = PTC 1 = NTC
5 P1 1 enable °C decimal point 0 = no 1 = yes
6
P2
0
temperature unit of measure-
ment 0 = °C 1 = °F
7
P4
1
configurable input function
0 = door switch/multi-pur-
pose input
1 = evaporator probe
2 = condenser probe
8
P5
0
value displayed
0 = cabinet temperature
1 = setpoint
2 = auxiliary temperature
9 P8 5 display refresh time 0... 250 s : 10
N. PAR. DEF. REGULATION MIN... MAX.
10
r0 2.0 setpoint differential 1... 15 °C/°F
11
r1 -40 minimum setpoint -99 °C/°F... r2
12
r2 50.0
maximum setpoint r1... 199 °C/°F
13
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
14
r5
0
cooling or heating operation
0 = cooling
1 = heating
15
r12
0
position of the r0 differential
0 = asymmetric
1 = symmetric
N. PAR. DEF. COMPRESSOR MIN... MAX.
16
C0
0
compressor on delay after pow-
er-on 0... 199 min
17
C2
3
compressor off minimum time
0... 199 min
0 = protection against mains
voltage fluctuations dis-
abled
18
C3 0 compressor on minimum time 0... 199 s
19
C4
0
compressor off time during cabi-
net probe alarm 0... 240 min
20
C5
10
compressor on time during cabi-
net probe alarm 0... 240 min
21
C6
80.0
threshold for high condensation
warning 0... 199 °C/°F
differential = 2 °C/4 °F
22
C7
90.0
threshold for high condensation
alarm 0... 199 °C/°F
23
C8 1 high condensation alarm delay 0... 15 min
24
C14
190
mains voltage threshold below
which the compressor is not
switched on
0... 300 V
the device attempts to switch
on every 30 s
25
C15
180
mains voltage threshold below
which the compressor is switched
off
0... 300 V
if satisfied C17 time
26
C16
260
mains voltage threshold above
which the compressor is not
switched on or switched off
0... 300 V
if satisfied C17 time
the device attempts to switch
on every 30 s
27
C17
5
consecutive duration of the per-
manence of the mains voltage
outside the thresholds C15 and
C16 due to the compressor being
switched off
0... 60 s
28
C18
5
consecutive number of failed
compressor starts due to the
mains voltage outside the
thresholds C14 and C16 such as
to cause the forced start-up of
the compressor
0... oo
0 = protection against mains
voltage fluctuations dis-
abled
oo= the device never makes
the forced start-up of
the compressor
the interruption of the power
supply resets the count
N. PAR. DEF. DEFROST (if r5 = 0) MIN... MAX.
29
d0
8
automatic defrost interval
0... 99 h
0 = only manual
if d8 = 3, maximum interval
30
d2 2.0 threshold for defrost end -99... 99 °C/°F
31
d3
30
defrost duration
0... 99 min
se P4 = 1, maximum duration
32
d4 0 enable defrost at power-on 0 = no 1 = yes
33
d5 0 defrost dealy after power-on 0... 199 min
34
d6
2
value displayed during defrost
0 = cabinet temperature
1 = display locked
2 = dEF label
35
d7 2 dripping time 0... 15 min
36
d8
0
defrost interval counting mode
0 = device on hours
1 = compressor on hours
2 = hours evaporator tem-
perature < d9
3 = adaptive
37
d9
0.0
evaporation threshold for auto-
matic defrost interval counting -99... 99 °C/°F
38
d11 0 enable defrost timeout alarm 0 = no 1 = yes
39
d15
0
compressor on consecutive time
for hot gas defrost 0... 99 min
40
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
EVCOS.p.A.|EV3B71/EV3B81|Instructionsheetver.1.0|Code1043B71E103|Page2of2|PT05/22
41
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
42
d20
180
compressor on consecutive time
for defrost 0... 500 min
0 = disabled
43
d22
0.0
evaporation threshold for adap-
tive defrost interval counting
(relative to optimal evaporation
temperature)
-10... 10 °C/°F
optimal evaporation tempera-
ture + d22
N. PAR. DEF. ALARMS MIN... MAX.
44
A1
10.0
threshold for low temperature
alarm (relative to setpoint) 0... 199 °C/°F
0 = disabled
45
A4
10.0
threshold for high temperature
alarm (relative to setpoint) 0... 199 °C/°F
0 = disabled
46
A6
12
high temperature alarm delay af-
ter power-on 0... 99 min x 10
47
A7
15
high/low temperature alarms de-
lay 0... 199 min
48
A8
15
high temperature alarm delay af-
ter defrost 0... 240 min
49
A9
15
high temperature alarm delay af-
ter door closing 0... 240 min
50
A11
2.0
high/low temperature alarms re-
set differential 1... 15 °C/°F
N. PAR. DEF. DIGITAL INPUTS MIN... MAX.
51
i0
1
door switch/multi-purpose input
function
0 = disabled
1 = compressor off
2 = reserved
3 = energy saving
4 = iA alarm (only display)
5 = iA alarm (compressor
off)
52
i1
0
door switch/multi-purpose input
activation 0 = with contact closed
1 = with contact open
53
i2
30
open door alarm delay
-1... 120 min
-1 = disabled
if i0 = 4, multi-purpose input
alarm delay
if i0 = 5, compressor on de-
lay after alarm reset
54
i3
15
regulation inhibition maximum
time with door open -1... 120 min
-1 = until the closing
55
i10
0
door closed consecutive time for
energy saving
0... 999 min
after regulation temperature
< SP
0 = disabled
56
i13
180
number of door openings for de-
frost 0... 240
0 = disabled
57
i14
32
door open consecutive time for
defrost 0... 240 min
0 = disabled
N. PAR. DEF. ENERGY SAVING (if r5 = 0) MIN... MAX.
58
HE2 0 energy saving maximum duration
0... 999 min
59
HE3
0
consecutive time without operat-
ing on keys for low consumption 0... 240 min
0 = disabled
N. PAR. DEF. SAFETIES MIN... MAX.
60
POF 0 enable ON/STAND-BY key 0 = no 1 = yes
61
PAS -19 password -99... 999
8 ALARMS
COD. DESCRIPTION RESET REMEDIES
Pr1 cabinet probe alarm automatic - check P0
Pr2 auxiliary probe alarm automatic - check probe integrity
- check electrical connection
COn
forced compressor start
alarm manual
- touch a key
- check C18
LU
compressor alarm not on or
off due to low mains voltage
manual, au-
tomatic after
30 s
- touch a key
- check C14 and C15
HU
compressor alarm not on or
off due to high mains volt-
age
manual, au-
tomatic after
30 s
- touch a key
- check C16
AL low temperature alarm automatic check A1 and A7
AH high temperature alarm automatic check A4 and A7
id open door alarm automatic check i0 e i1
COH high condensation warning automatic check C6
CSd
high condensation alarm
manual
- switch the device off and on
- check C7
iA multi-purpose input alarm automatic check i0 and i1
dFd
defrost timeout alarm
manual
- touch a key
- check d2, d3 and d11
9 TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container Black, self-extinguishing
Category of heat and fire resistance D
Measurements
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with removable screw terminal
blocks
Mounting methods for the control device
To be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the cover-
ing IP65 (front)
Connection method
Fixed screw terminal blocks for wires up to
2,5 mm² Removable screw terminal blocks for wires up
to 2,5 mm²; by request
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft) Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0 to 55 °C (from 32 to 131 °F)
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from
10 to 90%
Pollution status of the control device 2
Conformity
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH (EC) Regulation
1907/2006
EMC 2014/30/UE LVD 2014/35/UE
Power supply
115... 230 VAC (+10 % -15%), 50/60 Hz
(±3 Hz), max. 4 VA (EV3B71) or 4.9 VA
(EV3B81) insulated
Earthing methods for the control device None
Rated impulse-withstand voltage
2.5 KV
Over-voltage category
II
Software class and structure
A
Analogue inputs 1 for PTC or NTC probes (cabinet probe)
PTC probes Sensor type
KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field
From -50 to 150 °C (from -58 to 302 °F)
Resolution
0.1 °C (1 °F)
NTC probes Sensor type
ß3435 (10 K@ 25 °C, 77 °F)
Measurement field
From -40 to 105 °C (from -40 to 221 °F)
Resolution
0.1 °C (1 °F)
Other inputs
Input configurable for analogue input (auxil-
iary probe) or digital input (door
switch/multi-purpose, dry contact)
Dry contact Contact type 5 VDC, 1.5 mA
Power supply None
Protection None
Digital outputs 1 electro-mechanical relay
Relay K1 SPST, 16 A res. @ 250 VAC (EV3B71)
SPST, 30 A res. @ 250 VAC (EV3B81)
Type 1 or Type 2 Actions Type 1
Additional features of Type 1 or Type 2 ac-
tions
C
Displays
3 digits custom display, with function icons
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of EVCO and thus pro-
tected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full
or partial reproduction and disclosure of the content other than with the express approval of EVCO. The
customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the de-
vice. EVCO accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the equip-
ment.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
telefono 0437 8422 | fax 0437 83648
email [email protected] | web www.evco.it

This manual suits for next models

1

Other Evco Controllers manuals

Evco EV3802 User manual

Evco

Evco EV3802 User manual

Evco EVK904 User manual

Evco

Evco EVK904 User manual

Evco EVJ 700 Instructions for use

Evco

Evco EVJ 700 Instructions for use

Evco EVFTFT618 User guide

Evco

Evco EVFTFT618 User guide

Evco EVXS815 User guide

Evco

Evco EVXS815 User guide

Evco Vcolor 539 Series User guide

Evco

Evco Vcolor 539 Series User guide

Evco EV3C23 User manual

Evco

Evco EV3C23 User manual

Evco c-pro 3 nano CHIL Instructions for use

Evco

Evco c-pro 3 nano CHIL Instructions for use

Evco Vcolor 869 User guide

Evco

Evco Vcolor 869 User guide

Evco EV3 HP User guide

Evco

Evco EV3 HP User guide

Evco RICS 4.30 User manual

Evco

Evco RICS 4.30 User manual

Evco Vcolor 818 User guide

Evco

Evco Vcolor 818 User guide

Evco EVJ 200 User manual

Evco

Evco EVJ 200 User manual

Evco Vcolor 318 M User manual

Evco

Evco Vcolor 318 M User manual

Evco EV3422 User manual

Evco

Evco EV3422 User manual

Evco EV3802 User manual

Evco

Evco EV3802 User manual

Evco Vcolor 338 User guide

Evco

Evco Vcolor 338 User guide

Evco FK 200p User manual

Evco

Evco FK 200p User manual

Evco EV3 HRV Instructions for use

Evco

Evco EV3 HRV Instructions for use

Evco EVRS225 User manual

Evco

Evco EVRS225 User manual

Evco EV3B23 User manual

Evco

Evco EV3B23 User manual

Evco EV9376 User manual

Evco

Evco EV9376 User manual

Evco EVK614 User manual

Evco

Evco EVK614 User manual

Evco Vcolor 279 Instructions for use

Evco

Evco Vcolor 279 Instructions for use

Popular Controllers manuals by other brands

Siemens OpenAir GDE131.1U installation instructions

Siemens

Siemens OpenAir GDE131.1U installation instructions

Avonic AV-CON300 quick start guide

Avonic

Avonic AV-CON300 quick start guide

Computherm WPR-100GE operating instructions

Computherm

Computherm WPR-100GE operating instructions

Emerson E2 quick start guide

Emerson

Emerson E2 quick start guide

Danfoss VLT HVAC operating instructions

Danfoss

Danfoss VLT HVAC operating instructions

GLP Easy-One instruction manual

GLP

GLP Easy-One instruction manual

Cielo Breez Eco user manual

Cielo

Cielo Breez Eco user manual

Lennox @DNOVA pCO1 user manual

Lennox

Lennox @DNOVA pCO1 user manual

CHROMATEQ CLUB-E 1024 quick start guide

CHROMATEQ

CHROMATEQ CLUB-E 1024 quick start guide

IAI acon First step guide

IAI

IAI acon First step guide

SCC MPPT 3KW user manual

SCC

SCC MPPT 3KW user manual

Renishaw UCC MMI installation guide

Renishaw

Renishaw UCC MMI installation guide

Pioneer “Serato DJ” DDJ-ERGO Setup guide

Pioneer

Pioneer “Serato DJ” DDJ-ERGO Setup guide

Weishaupt W-FM 100 Installation and operating instruction

Weishaupt

Weishaupt W-FM 100 Installation and operating instruction

Resol ER3 manual

Resol

Resol ER3 manual

inVENTer Easy Connect e16 manual

inVENTer

inVENTer Easy Connect e16 manual

Crestron SP-SC Operation guide

Crestron

Crestron SP-SC Operation guide

OWI AMPMOVC Specifications

OWI

OWI AMPMOVC Specifications

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.