1 About this document
This document describes the use of the above-mentioned product. Certain aspects
of use connected to a hydraulic unit or handwheel control are described in other
documents and must be observed èChap. 1.1.
All available documents for the product èwww.festo.com/pk
1.1 Applicable documents
Document Table of contents
DFPD-HD-...-HW operating instructions Mounting, commissioning and operation of the
hydraulic unit
DFPD-HD-...-MW operating instructions Mounting, commissioning and operation of the
handwheel control
Fig. 1
2 Safety
 Take into consideration the legal regulations for the respective destination.
 Observe product labelling.
 Before carrying out mounting, dismantling, installation and maintenance work,
switch off the compressed air supply and vent the drive. Secure compressed air
supply against accidental restarting.
Return to Festo
Hazardous substances can endanger the health and safety of personnel and cause
damage to the environment. To prevent hazards, the product should only be
returned upon explicit request by Festo.
 Consult your regional Festo contact.
 Complete the declaration of contamination and attach it to the outside of the
packaging.
 Comply with all legal requirements for handling hazardous substances and
transporting dangerous goods.
3 Use for intended purpose
The DFPD-HD quarter turn actuator is intended to activate process valves, such as
ball valves and butterfly shut-off valves with a rotation angle from 0° (valve closed)
to 90°. The quarter turn actuator is suitable for controlling media-flow process
valves in fluid engineering systems.
 The product may only be used in its original status without unauthorized
modifications.
 Only use the product if it is in perfect technical condition.
 Observe the specifications on the product labelling.
Note
The operating torque of the drive must not be higher than the maximum per
missible torque listed in ISO 5211, with reference to the size of the mounting
flange and of the coupling.
Operating medium
 Only use compressed air in accordance with the specifications
èTechnicaldata.
 Only use unlubricated compressed air under normal conditions. Once the
product has been used with lubricated compressed air, it must continue to
beoperated with compressed air only.
4 Further information
– Accessories èwww.festo.com/catalogue
– Documents and literature èwww.festo.com/sp
5 Service
 Contact the regional Festo contact if you have technical questions
èwww.festo.com.
6 Product overview
The product label can be found on the gear unit.
6.1 Function
The DFPD-HD-...-RD is a double-acting quarter turn
actuator. The piston is moved by pressurizing and
exhausting the pneumatic cylinder.
The linear motion of the piston is transformed via a Scotch yoke system into
aswivel motion of the transmission shaft. The connected process valve records
the moment of reaction of the quarter turn actuator.
Fig. 2
6.2 Layout
2
34
78
5
6
1
6
9aJ aA
7
18 mounting threads
according to ISO 5211
2Parallel key groove
3Pneumatic cylinder
44 mounting threads – e.g.,
forsensor box
5Transmission shaft (internal) –
delivery “Valve open”
6Adjustable stop for end-position
adjustment
7Transport lug
8Gear units
9Mechanical position indication
aJ Supply port (4)
aA Supply port (2)
Fig. 3
7 Transport and storage
Warning
Danger of crushing!
The product without accessories weighs up to about 1500 kg, depending on the
product version.
Body parts can be crushed if the product falls.
 Use appropriate load handling equipment.
 Use the 3 transport lugs to life the quarter turn actuator (Fig. 3, 7).
 Loosen the quarter turn actuator before transporting the process valve.
Note
For variants with a hydraulic unit (DFPD-HD-...-HW): environmental damage due
to escaping oil.
 Store the product horizontally and avoid inclines.
 Observe environmental and storage conditions èTechnical data.
 To prevent contamination, close any pneumatic connections.
 Protect the coupling parts with grease or protective oil.
 To prevent damage to the coupling flange, store the quarter turn actuator on an
even wooden pallet.
 Store the product in a cool, dry, UV-protected and corrosion-protected
environment.
 In case of long-term storage: regularly check the function of the quarter turn
actuator.
 When shipping used products: comply with all legal requirements for handling
hazardous substances and transporting dangerous goods.
For return to Festo èChap. 2.
8 Mounting and installation
Note
Installation should only be conducted by qualified specialized personnel.
Note
Quarter turn actuators of the series DFPD-HD are intended for installation in
parallel with the line axis.
 If another mounting position is necessary, consult your regional Festo contact
èwww.festo.com.
Note
Quarter turn actuators with a hydraulic manual override are designed for a
horizontal mounting position only. In this position, the pump and reservoir as
mounted towards the top of the hydraulic cylinder.
8.1 Mounting
1. Clean the coupling flange.
2. Adjust the valve position according to the quarter turn actuator settings.
3. Lubricate the valve stem.
4. Place the quarter turn actuator on the switching shaft of the process valve.
5. Fasten the quarter turn actuator to the connecting flange of the process valve
with 8 threaded pins.
6. Tighten the nuts of the threaded pin crosswise
Tightening torque èFig. 4
Flange type F25 F30 F35
Tightening torques [Nm] 160 320 1100
Fig. 4
8.2 Pneumatic installation
 Observe the operating instructions of the process valve.
 Test the correct function of the pneumatic control.
Port Effect
2Air supply; always actuated
4Return stroke
Fig. 5
9 Commissioning
Note
Commissioning should only be carried out by qualified personnel.
Prerequisites
– The drive is fully mounted and connected.
1. Check operating conditions and limit values èTechnical data.
2. Switch on the compressed air supply.
3. Check the quarter turn actuator for leakage.
4. First check the direction of rotation of the quarter turn actuator and reaction of
the process valve at a low travel speed.
9.1 Adjusting the end position – “Valve closed” position
The “Valve closed” position is adjusted using the adjusting screw on the end flange
of the pneumatic cylinder.
1
2
3
4
5
6
Fig. 6
1. Put the quarter turn actuator in the “Valve closed” position 1.
2. Switch off the compressed air supply.
3. Remove the cover of the stop bolt 2 and sealing disc 3.
4. Loosen the stop nut 5together with the sealing disc 6.
5. To reduce the rotation angle, screw in the stop adjusting screw 4.
To increase the rotation angle, unscrew the stop adjusting screw 4.
6. Tighten the stop nut 5. Make sure that the sealing disc 6 is centred on the
stop nut and lies in the recess of the flange.
7. Switch on the compressed air supply.
8. To check the adjustment, run through a complete cycle.
9. Put the cover of the stop bolt 2and sealing disc 3into place again.
9.2 Adjusting the end position – “Valve open” position
The “Valve open” position is adjusted using the adjusting screw on the end flange
of the gear unit.
5
4
3
2
1
6
Fig. 7
1. Put the quarter turn actuator in the “Valve open” position 1.
2. Switch off the compressed air supply.
3. Remove the cover of the stop bolt 2 and sealing disc 3.
4. Loosen the stop nut 5together with the sealing disc 6.
5. To reduce the rotation angle, screw in the stop adjusting screw 4.
To increase the rotation angle, unscrew the stop adjusting screw 4.
6. Tighten the stop nut 5. Make sure that the sealing disc 6 is centred on the
stop nut and lies in the recess of the flange.
7. Switch on the compressed air supply.
8. To check the adjustment, run through a complete cycle.
9. Put the cover of the stop bolt 2and sealing disc 3into place again.
10 Operation
 Comply with operating conditions.
 Observe the permitted limit values.
Note
Use lubricated compressed air for continuous operation under extreme
conditions. The oil must be chemically inert and must not carbonise. After the
initial use of lubricated compressed air, it is required in continued operation.
11 Fault clearance
 In case of malfunctions, consult your regional Festo contact.
12 Service
When used as intended, the product is maintenance-free.
Festo recommends the following periodic inspections:
Interval Inspection
Annually Correct function of the quarter turn actuator by
repeatedly opening and closing the valve
(rotation angle = 90°)
Every six months Visual inspection (during operation)
Quarterly Correct function of the quarter turn actuator during
operation
Fig. 8
13 Dismantling
Note
Disassembly only by qualified specialized personnel.
Warning
Danger of crushing!
The product without accessories weighs up to about 1500 kg, depending on the
product version.
Body parts can be crushed if the product falls.
 Use appropriate load handling equipment.
 Use the 3 transport lugs to life the quarter turn actuator (Fig. 3, 7).
 Loosen the quarter turn actuator before dismantling the process valve.
Warning
Risk of injury due to uncontrolled movements.
 Depressurise the pipeline before dismantling the quarter turn actuator.
1. Disconnect the quarter turn actuator from the compressed air supply.
2. Loosen the pneumatic connections.
3. Loosen the mounting screws of the quarter turn actuator.
4. Lift the quarter turn actuator off the process valve.
14 Disposal
 Observe the local regulations for environmentally friendly disposal.
 Dispose of the product in an environmentally friendly manner. When doing this,
also take residual media into account (potential recycling of hazardous waste).
15 Technical data
DFPD
Operating medium Compressed air in accordance with
ISO8573-1:2010 [7:4:4] 1)
Note on the operating medium Lubricated operation possible
(required in further operation)
Ambient temperature [°C] –20…+80
Rotation angle [°] 0…90
Mounting position Parallel to line axis
(DFPD-HD-...-HW horizontal only)
Pneumatic port G½, G1
Standard connection to the process valve ISO 5211
CE marking (see declaration of conformity
èwww.festo.com/sp)
As per EU Explosion Protection Directive
(ATEX)
To EC Machinery Directive
Operating conditions
Operating pressure [bar] 3…8.5
Nominal operating pressure [bar] 5.0
End position adjustment range 0° [°] ± 5
End position adjustment range 90° [°] ± 5
Degree of protection IP66M, IP67M
Materials
Housing Steel
Cap Steel
Pneumatic cylinder Steel (nickel-plated)
Piston rod Steel (chrome-plated)
Piston Steel
Guide rod Steel
Stop adjusting screw Steel
Seal NBR, polyurethane
Ceiling paintjob Polyurethane
1) Note: Pressure dew point at least 10 °C below the outside temperature.
Fig. 9

Other manuals for DFPD-Series

5

This manual suits for next models

1

Other Festo Controllers manuals

Festo CMMP-AS User manual

Festo

Festo CMMP-AS User manual

Festo CPX-FEC Parts list manual

Festo

Festo CPX-FEC Parts list manual

Festo s CMMD-AS-C8-3A Guide

Festo

Festo s CMMD-AS-C8-3A Guide

Festo VPPM C1 Series User manual

Festo

Festo VPPM C1 Series User manual

Festo CECX-X-C1 Series User manual

Festo

Festo CECX-X-C1 Series User manual

Festo CMXR-C1 Instruction Manual

Festo

Festo CMXR-C1 Instruction Manual

Festo MS2-LFR Parts list manual

Festo

Festo MS2-LFR Parts list manual

Festo CMXH User manual

Festo

Festo CMXH User manual

Festo CMMP-AS Series Reference guide

Festo

Festo CMMP-AS Series Reference guide

Festo EGSP Series User manual

Festo

Festo EGSP Series User manual

Festo DFPI-ND2P Series Setup guide

Festo

Festo DFPI-ND2P Series Setup guide

Festo DFPD-HD-Series User manual

Festo

Festo DFPD-HD-Series User manual

Festo SPC200 Series User manual

Festo

Festo SPC200 Series User manual

Festo CPX-CMAX-C1-1 Guide

Festo

Festo CPX-CMAX-C1-1 Guide

Festo SPC200 Series User manual

Festo

Festo SPC200 Series User manual

Festo CMMS-ST-C8-7 Reference guide

Festo

Festo CMMS-ST-C8-7 Reference guide

Festo DFPD-x-RS Series User manual

Festo

Festo DFPD-x-RS Series User manual

Festo SPC200 Series User manual

Festo

Festo SPC200 Series User manual

Festo VEAB User manual

Festo

Festo VEAB User manual

Festo MPP-3-1/8 User manual

Festo

Festo MPP-3-1/8 User manual

Festo VPPI S1D Series User manual

Festo

Festo VPPI S1D Series User manual

Festo CECC-X-M1 series Operating and installation instructions

Festo

Festo CECC-X-M1 series Operating and installation instructions

Festo SFC-DC-VC-3-E-H0-CO Reference guide

Festo

Festo SFC-DC-VC-3-E-H0-CO Reference guide

Festo CPX-CMAX Operating and installation instructions

Festo

Festo CPX-CMAX Operating and installation instructions

Popular Controllers manuals by other brands

Mitsubishi Electric MELSEC-A Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC-A Series user manual

Brightlink BL-VW22-4K60-GUI user manual

Brightlink

Brightlink BL-VW22-4K60-GUI user manual

Mitsubishi Electric AJ65DBTB1-32T1 user manual

Mitsubishi Electric

Mitsubishi Electric AJ65DBTB1-32T1 user manual

EverFocus EFC304 user manual

EverFocus

EverFocus EFC304 user manual

Munters TRIO User and installation manual

Munters

Munters TRIO User and installation manual

Datakom DKG-108 user manual

Datakom

Datakom DKG-108 user manual

Siemens SIDOOR AT40 System manual

Siemens

Siemens SIDOOR AT40 System manual

ComAp InteliNano NT Plus reference guide

ComAp

ComAp InteliNano NT Plus reference guide

JUMO DICON touch datasheet

JUMO

JUMO DICON touch datasheet

Aficio AP1015 operating instructions

Aficio

Aficio AP1015 operating instructions

SMAR LC700 user guide

SMAR

SMAR LC700 user guide

Sens SuperTorque 8Z Installation & operation manual

Sens

Sens SuperTorque 8Z Installation & operation manual

Nevco 321 Operator instructions

Nevco

Nevco 321 Operator instructions

Sunricher SR-2830A quick start guide

Sunricher

Sunricher SR-2830A quick start guide

Val Controls I 24-BF Series Hardware manual

Val Controls

Val Controls I 24-BF Series Hardware manual

PIETRO FIORENTINI REFLUX 819 Technical manual

PIETRO FIORENTINI

PIETRO FIORENTINI REFLUX 819 Technical manual

JUMO DICON touch operating manual

JUMO

JUMO DICON touch operating manual

VNS G904 user guide

VNS

VNS G904 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.