manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Circuit Breaker
  8. •
  9. GE Power Break II User manual

GE Power Break II User manual

Other manuals for Power Break II

8

This manual suits for next models

6

Other GE Circuit Breaker manuals

GE Power Break II User manual

GE

GE Power Break II User manual

GE AK-2-15 User manual

GE

GE AK-2-15 User manual

GE Spectra Series AMC3FGB User manual

GE

GE Spectra Series AMC3FGB User manual

GE SecoVac Series User manual

GE

GE SecoVac Series User manual

GE M-PACT User manual

GE

GE M-PACT User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE AKR-3-50 User manual

GE

GE AKR-3-50 User manual

GE AM-2.4/4.16-100/150- 3 User manual

GE

GE AM-2.4/4.16-100/150- 3 User manual

GE PowerVac User manual

GE

GE PowerVac User manual

GE AK-1-15 Series Owner's manual

GE

GE AK-1-15 Series Owner's manual

GE GL 310 F1/4031 P/VR User manual

GE

GE GL 310 F1/4031 P/VR User manual

GE MicroVersaTrip AKR-75 User manual

GE

GE MicroVersaTrip AKR-75 User manual

GE ReliaGear Pro-Stock Spectra RMS User manual

GE

GE ReliaGear Pro-Stock Spectra RMS User manual

GE SD200SA User manual

GE

GE SD200SA User manual

GE EntelliGuard L User manual

GE

GE EntelliGuard L User manual

GE A Series Pro-Stock THQB User manual

GE

GE A Series Pro-Stock THQB User manual

GE GE-200A User manual

GE

GE GE-200A User manual

GE GL 310 F3/4031 P/VR User manual

GE

GE GL 310 F3/4031 P/VR User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE AM-13.8-500-5A User manual

GE

GE AM-13.8-500-5A User manual

GE AKR-5-100 User manual

GE

GE AKR-5-100 User manual

GE MicroVersaTrip Plus Series User manual

GE

GE MicroVersaTrip Plus Series User manual

GE MicroVersaTripPlus AK-50 User manual

GE

GE MicroVersaTripPlus AK-50 User manual

GE AM-13.8-500-5C User manual

GE

GE AM-13.8-500-5C User manual

Popular Circuit Breaker manuals by other brands

Siemens 3VT9524-4TG30 quick start guide

Siemens

Siemens 3VT9524-4TG30 quick start guide

Acrel ASCB1 Series Installation and operation manual

Acrel

Acrel ASCB1 Series Installation and operation manual

ABB SACE Emax 2 E2.2 manual

ABB

ABB SACE Emax 2 E2.2 manual

Eaton NOVA LBS 15 Installation and operation instructions

Eaton

Eaton NOVA LBS 15 Installation and operation instructions

ABB SACE Emax E1 quick start guide

ABB

ABB SACE Emax E1 quick start guide

Siemens SIRIUS 3RV1742 Original operating instructions

Siemens

Siemens SIRIUS 3RV1742 Original operating instructions

WEG FHU ACW125 installation instructions

WEG

WEG FHU ACW125 installation instructions

TERASAKI NHP TemBreak PRO P160 Series installation instructions

TERASAKI

TERASAKI NHP TemBreak PRO P160 Series installation instructions

Siemens Sentron 3VA9157-0PK1 Series operating instructions

Siemens

Siemens Sentron 3VA9157-0PK1 Series operating instructions

hager TS 303 User instruction

hager

hager TS 303 User instruction

ETI EFI-4B Instructions for mounting

ETI

ETI EFI-4B Instructions for mounting

Gladiator GCB150 Installation instruction

Gladiator

Gladiator GCB150 Installation instruction

nader NDM3EU-225 operating instructions

nader

nader NDM3EU-225 operating instructions

Eaton 50DHP-VR Instruction handbook

Eaton

Eaton 50DHP-VR Instruction handbook

ABB SACE Emax 2 E6.2 Instruction handbook

ABB

ABB SACE Emax 2 E6.2 Instruction handbook

Gewiss 90 RCD Installation

Gewiss

Gewiss 90 RCD Installation

OEZ LFN Instructions for use

OEZ

OEZ LFN Instructions for use

Eaton Power Defense PDG2 Instruction leaflet

Eaton

Eaton Power Defense PDG2 Instruction leaflet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

•
•

'
·•
—
Figure 1. Shunt Trip.
Catalog Voltage Peak Inrush
Number Rating (1) Current, A (2)
Nominal RMS
Current, mA
SPST012 12 Vdc
3.0 200
SPST024 24 Vac 1.5 140
24 Vdc
SPST048 1.5 110
48
48
Vac
Vdc
SPST120 1.5 85
125
120 Vac
Vdc
SPST208 208 Vac 1.5 50
SPST240 1.5 40
250
240 Vac
Vdc
24-240 Vac devices are rated for 50/60 Hz.
Peak inrush current is present for 2-6 ms after activation.
This number is provided so that fuses and supplies can be chosen
appropriately.
Catalog Voltage Peak Inrush
Number Rating (1) Current, A (2)
Nominal RMS
Current, mA
SPSTL012 12 Vdc
19 300
SPSTL024 15 300
24
24
Vac
Vdc
SPSTL048 7.5 200
48
48
Vac
Vdc
SPSTL120 3.0 80
120
125
Vac
Vdc
SPSTL208 208 Vac
1.9 60
SPSTL240 1 .5 45
250
240 Vac
Vdc
1
GEH6284 INSTRUCTIONS
Power Break® II Circuit Breaker Accessories
Shunt Trip and Shunt Trip with Lockout
The catalog numbers for various voltage applications are
listed in Table 1 for the Shunt Trip and in Table 2 for the Shunt
Trip with Lockout.
—
Table 1. Catalog numbers and voltages for the Shunt Trip.
—
Figure 2. Shunt Trip with Lockout.
Introduction
The Shunt Trip and Shunt Trip with Lockout accessories,
shown in Figures 1 and 2, can be installed in 800-4000
ampere frame Power Break®II circuit breakers. These
accessories allow the breaker to be tripped electrically from a
remote location.
In addition to providing a trip signal to the breaker, the
Shunt Trip accessories can be set up to interact with other
Power Break II accessories, when used with a MicroVersaTrip
PlusTM or MicroVersaTrip PM™ Trip Unit. DIP switches on
the rear of the breaker Trip Unit can configure the Shunt Trip
accessories to activate a Bell Alarm-Alarm Only accessory or
a Bell Alarm with Lockout accessory when a shunt trip
occurs. The Accessory Configuration section below
describes how this can be done. If the breaker is equipped
with a Power+™ Trip Unit, it is configured so that only
protection trips will activate a Bell AlarmAlarm Only or Bell
Alarm with Lockout.
—
Table 2 Catalog numbers and voltages for the Shunt Trip with Lockout.
Operation
Apply control voltage to terminals 31 and 32 of the terminal
strip on the right side of the breaker to trip the circuit
breaker. The Shunt Trip will cause the circuit breaker to trip
when the control voltage is greater than 75% of the rated de
voltage or 55% of the rated ac voltage. Control power to the
Shunt Trip must be removed before the breaker can be
closed. Control power to the Shunt Trip with Lockout must
be removed for a minimum of 0.25 second before the breaker
can be closed.
(1)
(2)
Installation
WARNING:
Before installing any accessories, turn the breaker
off, disconnect it from all voltage sources, and discharge the
charging springs.
AVERTISSEMENT:
Avant d'installer tout accessoire, mettre le
disjoncteur en position OFF, le deconnecter de toute tension
d'alimentation, et decharger les ressorts d'armement.
WARNING:
For Shunt Trip operation using Entelliguard Trip
Units: If a shunt trip device is used, the breaker can be
closed normally after trip, even if the shunt trip is
continuously energized. For the "Shunt Trip w/Lockout"
device, power must be removed from the "Shunt Trip w/
lockout" device in order to close the breaker.
AVERTISSEMENT:
Pour l'operation du déclencheur shunt
du déclencheur Entelliguard: Si un déclencheur shunt est
utilisé, le disjoncteur peut être fermé d'une fa çon normale
suite au déclenchement même si le déclencheur shunt est
énergisé continuellement. Pour un déclencheur shunt muni
d'un verrouillage (lockout), l'alimentation doit être enlevée
du déclencheur shunt avant de proceder à la fermeture du
disjoncteur

The Shunt Trip accessory is installed in the accessory
compartment through the front of the circuit breaker in the
position shown in Figure 3.
Shunt Trip or
Shunt Trip with Lockout
Bell Alarm Bell Alarm-
with Alarm Only
Lockout
Undervoltage Release
Use the following procedure to install the Shunt Trip accessory
into the Shunt Trip slot of the accessory compartment:
Open the hinged door over the accessory
compartment and Trip Unit.
To remove an existing accessory, loosen the accessory
locking screw and pull the module out with the Rating
Plug Removal Tool (catalog number TRTOOL).
Insert the Shunt Trip accessory into the proper slot, as
illustrated in Figure 4. The Shunt Trip accessory is
keyed for the correct slot in the accessory
compartment. If the accessory cannot be fully seated
in the compartment, check that the compartment
position is correct.
CAUTION: Over tightening the locking screw may damage
or distort the case of the accessory.
ATTENTION: Le serrage excessif de la vis de verrouillage
peut d éformer le bo îtier d'accessoire.
8.
9.
If the breaker is equipped with a MicroVersaTrip Plus
or MicroVersaTrip PM Trip Unit, the Shunt Trip
accessory can be configured to activate installed Bell
Alarm-Alarm Only or Bell Alarm with Lockout
accessories when a shunt trip occurs, with the
procedure described in the Accessory Configuration
section.
Connect the control wiring for either Shunt Trip to
terminals 31 and 32 at the terminal block on the right
side of the breaker.
Test to ensure proper operation, according to the
procedures below.
Reconnect power to the circuit breaker and any other
accessories.
Close and lock or seal the door over the accessory
compartment and Trip Unit to prevent unauthorized
changes to Trip Unit settings and to keep contaminants
out of empty accessory slots.
Accessory Configuration
This section only applies if Bell Alarm-Alarm Only or Bell Alarm
with Lockout accessories are installed in the breaker, along
with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit. If
the breaker is equipped with a Power+ Trip Unit, the factory
default settings, listed in Table 3, can not be changed.
The Shunt Trip accessory can be configured to activate the
Bell Alarm-Alarm Only or Bell Alarm with Lockout accessories if
a shunt trip occurs. The configuration can be changed by
removing the Trip Unit from the breaker, setting the DIP
switches on the rear of the Trip Unit, and reinstalling the Trip
Unit. Figure 5 illustrates the Trip Unit rear DIP switches and
their functions. Table 3 lists the switch functions and the
factory settings for each.
—
Figure 5 Accessory switch on the rear of the MicroVersaTrip Plus™ or Micro Versa Trip PM™ Trip Unit,
showing the factory settings (solid part indicates that the switch is pushed in on that side)
2
—
Figure 3. Accessories compartment on the front of the circuit breaker, with the Shunt Trip slot
indicated
—
Figure 4. Inserting a Shunt Trip into the accessory compartment.
Tighten the locking screw on the front of the
accessory until it is snug (9 in-lb).
4.
1.
2.
3.
5.
6.
7.
Factory
Switch Setting Function
1 Disabled Shunt trip activates Bell Alarm- Alarm Only
2 Disabled UVR trip activates Bell Alarm-Alarm Only
3 Enabled Protection trip activates Bell Alarm Alarm
Only
4 Disabled Shunt trip activates Bell Alarm with
Lockout
5 Disabled UVR trip activates Bell Alarm withLockout
6 Enabled Protection trip activates Bell Alarm with
Lockout
When a Shunt Trip accessory causes the breaker to
trip, the contacts of the Bell Alarm-Alarm Only also
change state. (The factory switch setting is disabled. )
When an Under voltage Release accessory causes the
breaker to trip, the contacts of the Bell Alarm-Alarm
Only also change state. (The factory switch setting is
disabled.)
When a protection trip (long-time, short-time,
instantaneous, ground-fault, or protective-relay)
occurs, the contacts of the Bell Alarm-Alarm Only also
change state. (The factory switch setting is enabled.)
When a Shunt Trip accessory causes the breaker to
trip, the contacts of the Bell Alarm with Lockout also
change state. (The factory switch setting is disabled.)
When an Under voltage Release accessory causes the
breaker to trip, the contacts of the Bell Alarm with
Lockout also change state. (The factory switch setting
is disabled. )
When a protection trip (long-time, short-time,
instantaneous, ground-fault, or protective-relay)
occurs, the contacts of the Bell Alarm with Lockout also
change state. (The factory switch setting i s enabled.)
Procedure for Changing Switch Settings
Change the accessory switch settings with the following
procedure:
WARNING:
Before beginning this procedure, turn the
breaker off, disconnect it from all voltage sources, and
discharge the closing springs.
AVERTISSEMENT:
Avant de commencer cette procédure,
mettre le disjoncteur en position OFF, le déconnecter de
toute tension d'alimentation, et désarmer les ressorts de
fermeture.
2.
3.
4.
5.
Loosen the four #10-32 screws at the corner of the
breaker cover.
Remove the cover from the breaker face.
Pull the Trip Unit locking lever to the right, then hold
the Trip Unit near the battery cover and lift it straight
out of the breaker.
Refer to Figure 5 and Table 3 to determine the switches
to be changed. Push in the appropriate "Enable" or
"Disable" side of the switch.
Confirm all switch settings before reinstalling the Trip
Unit in the breaker.
Pull the Trip Unit locking lever to the right. While
holding the lever, carefully align the connector on the
rear of the Trip Unit with the connector in the breaker.
Press down on the Trip Unit, while holding it near the
battery cover. When the Trip Unit is fully seated, slide
the locking lever back to the left.
Reinstall the breaker top cover and tighten the four
#10-32 screws to 32 in-lb.
Replace the trim plate and tighten the four #8-32
screws to 20 in-lb.
Verify that the switch settings are correct by inducing
breaker trips from the Shunt Trip and Undervoltage
Release (if present) and checking the responses of the
Bell Alarm-Alarm Only and Bell Alarm with Lockout
accessories.
ƈƓơƢƄƠƝƑƓƒƣƠƓ
Test the Shunt Trip for proper operation with the following
procedure.
Turn off the power to the Shunt Trip.
Close the breaker contacts.
Apply at least 55% of the rated ac voltage or at
least 75% of the rated de voltage to the Shunt
Trip; the breaker should trip immediately.
If a Bell Alarm-Alarm Only or Bell Alarm with Lockout is
present, ensure that it activates (or does not activate)
as selected by the MicroVersaTrip Plus or
MicroVersaTrip PM Trip Unit.
If a Shunt Trip with Lockout has been installed, continue
with the following steps:
After the breaker has tripped and with the power still
applied to the Shunt Trip with Lockout, attempt
to close the breaker. The breaker should not close
nor attempt to close.
If a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit
is installed, check that the Trip Unit display is
active (powered).
Remove power from the Shunt Trip with Lockout.
Attempt to close the breaker; it should close as
normal.
3
—
Table 3. Accessory switch settings, including factory defaults.
Description of Switch Settings
Following are descriptions of the effects of each accessory
switch when it is enabled.
1.
2.
3.
4.
5.
6.
5.
6.
7.
8.
1.
2.
.
4.
6.
7.
8.
9.
10.
Loosen the four #8-32 screws on the breaker trim-
plate assembly and remove the trim plate.
1.
Symptom
1.
2.
3.
4.
5.
The Shunt Trip will not
insert completely into
the breaker.
The breaker will not trip
when control power is
applied to the Shunt Trip.
The breaker closes
manually when the Shunt
Trip with Lockout is
energized.
The breaker will not close
manually when the Shunt
Trip or Shunt Trip with
Lockout control power is
removed.
The breaker fails to close
after power is removed
from the Shunt Tri p with
Lockout.
Possible Cause
The accessory is
inserted incorrectly.
The Shunt Trip is not energized.
The installed Shunt Trip has an
incorrect voltage rating.
The Shunt Trip connection is
poor.
The breaker is not closed.
The Shunt Trip with Lockout
solenoid is not energized.
The Shunt Trip with Lockout control
power connection is poor.
The Shunt Trip or Shunt Trip with
Lockout control power is actually
still applied.
The breaker is already closed.
The Shunt Trip with Lockout
plunger is not retracted.
Control power was not removed
for a minimum or 0.25 second.
Corrective Action
Ensure that the accessory is inserted in the correct slot, as in
Figure 3, and that the label is upright.
Check that Shunt Trip control power is applied at greater than
75% of the rated de voltage or 55% of the rated ac voltage.
Check that the accessory is completely inserted; reinsert if
necessary.
If a 12 Vdc Shunt Trip is installed, check that the polarity of the
control power matches that shown on the label of the
Shunt Trip accessory.
Check for the proper voltage rating on the Shunt Trip.
Check that the Shunt Trip accessory is completely inserted.
Check that the Trip Unit is seated correctly. If the Trip Unit
was removed to set the switches, check that it has been
correctly installed; remove and reinstall, if necessary.
Note that an otherwise unpowered Trip Unit is powered up
by an energized Shunt Trip.
Verify that the breaker is closed.
Check that the Shunt Trip with Lockout control power is
applied at greater than 75% of the rated de voltage or 55% of
the rated ac voltage. Check that the accessory is completely
inserted; re-insert if necessary.
Note that an otherwise unpowered Trip Unit is powered by an
energized Shunt Trip accessory.
Check that the Shunt Trip with Lockout accessory is completely
inserted.
Check that control power to the Shunt Trip or Shunt Trip with
Lockout has been removed.
Check that the breaker is not closed; if so, open it and try
again.
Remove the Shunt Trip with Lockout accessory. If the lockout
plunger protrudes out of the accessory, replace the accessory.
If the plunger does not protrude, reinsert the accessory,
ensuring proper alignment of the accessory in the pocket.
Wait at least 0.25 seconds before closing the breaker after
removing control power from the Shunt Trip with Lockout.






Symptom
4
1SQC930029M0201, GEH6284 December 2019
—
ABB Inc.
305 Gregson Drive
Cary, NC 27511.
electrification.us.abb.com
—
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB Inc. does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.
We reserve all rights in this document and
in the subject matter and illustrations
contained therein. Any reproduction or
utilization of its contents – in whole or in
parts – is forbidden without prior written
consent of ABB Inc.
Copyright© 2019 ABB
All rights reserved
—
GE is a trademark of GE. Manufactured
by ABB Inc. under license from GE.
Trouble-Shooting
The following guide is provided for troubleshooting and isolating common problems. It does not cover every possible
situation. Contact the Customer Support Center at 800-843-3742 if any problem is not resolved by these procedures.