GE Power Break II User manual

1
Power
Break
®
II
Circuit
Breakers
Getting
Started
i
Since
this
breaker
is
available
in
a
variety
of
configurations
,
please
take
a
moment
to
compare
the
catalog
number
of
your
purchased
breaker
with
the
catalog
number
key
below
.
Installation
of
an
incorrect
breaker
could
result
in
misapplication
,
lack
of
system
coordination
,
or
reduced
system
selectivity
.
If
you
have
any
questions
,
call
the
GE
Customer
Support
Center
at
800
-
843
-
3742
.
S
H
F
W
B
2
16
H
Code
Description
Function
T
s
Power
Break
®
II
Breaker
Family
S
Standard
Hi
-
Break
Frame
Type
H
D
Draw
-
out
Front
-
connected
Connection
Type
F
08
800
A
1600
A
2000
A
Frame
Rating
16
20
B
2
up
to
2000
A
CTs
Trip
Unit
02
200
A
400
A
800
A
1000
A
1600
A
2000
A
Maximum
CT
Current
Rating
04
08
10
16
20
Standard
High
-
range
instantaneous
CTType
H
Power
Break
®
II
insulated
-
case
circuit
breaker
catalog
numbering
system
.
Example
-
a
breaker
with
catalog
number
SHB
20
B
216
H
has
the
following
features
:
•
Power
Break
®
II
(
S
)
•
Hi
-
Break
®
frame
(
H
)
•
Front
-
connected
(
F
)
•
2000
A
frame
rating
(
20
)
•
Trip
Unit
with
up
to
2000
A
CT
(
B
2
)
•
1600
A
CT
rating
(
16
)
•
High
-
range
instantaneous
CT
(
H
)
L
Courtesy of NationalSwitchgear.com

GEH
-
6270
A
WARNINGS
,
CAUTIONS
,
AND
NOTES
AS
USED
IN
THIS
PUBLICATION
WARNINGS
Warning
notices
are
used
in
this
publication
to
emphasize
that
hazardous
voltages
,
currents
,
or
other
conditions
that
could
cause
personal
injury
are
present
in
this
equipment
or
may
be
associated
with
its
use
.
Warning
notices
are
also
used
for
situations
in
which
inattention
or
lack
of
equipment
knowledge
could
cause
either
personal
injury
or
damage
to
equipment
.
CAUTIONS
Caution
notices
are
used
for
situations
in
which
equipment
might
be
damaged
if
care
is
not
taken
.
NOTES
m
Notes
call
attention
to
information
that
is
especially
significant
to
understanding
and
operating
the
equipment
.
This
document
is
based
on
information
available
at
the
time
of
its
publication
.
While
efforts
have
been
made
to
ensure
accuracy
,
the
information
contained
herein
does
not
cover
all
details
or
variations
in
hardware
and
software
,
nor
does
it
provide
for
every
possible
contingency
in
connection
with
installation
,
operation
,
and
maintenance
.
Features
may
be
described
herein
that
are
not
present
in
all
hardware
and
software
systems
.
GE
Electrical
Distribution
&
Control
assumes
no
obligation
of
notice
to
holders
of
this
document
with
respect
to
changes
subsequently
made
.
GE
Electrical
Distribution
Sc
Control
makes
no
representation
or
warranty
,
expressed
,
implied
,
or
statutory
,
with
respect
to
,
and
assumes
no
responsibility
for
the
accuracy
,
completeness
,
sufficiency
,
or
usefulness
of
the
information
contained
herein
.
No
warrantees
of
merchantability
or
fitness
for
purpose
shall
apply
.
The
following
are
trademarks
of
GE
Company
:
Power
Break
®
,
MicroVersaTrip
Plus
,
MicroVersaTrip
PM
©
Copyright
1995
GE
Company
All
Rights
Reserved
Courtesy of NationalSwitchgear.com

1
Power
Break
®
II
Circuit
Breakers
Table
of
Contents
Chapter
1
.
introduction
1
-
1
Overview
1
-
2
Receiving
the
Breaker
Storage
1
-
3
Preparation
for
Installation
Panel
Cutouts
and
Clearances
Accessory
Installation
1
-
4
Breaker
Installation
1
1
1
1
1
2
2
Chapter
2
.
Operation
2
-
1
Standard
Features
2
-
2
Operating
Instructions
Sequence
of
Operations
Operating
Instructions
for
Manually
Operated
Breaker
Operating
Instructions
for
Motor
-
Operated
Breaker
Padlock
Operation
Periodic
Operational
Checks
Wiring
Notes
2
-
3
Trip
Unit
Setup
3
3
3
4
5
6
6
6
.
7
Chapter
3
.
Accessory
Operation
3
-
1
Lugs
and
Adapters
3
-
2
Plug
-
In
Accessory
Compartment
3
-
3
Bell
Alarm
-
Alarm
Only
Operation
3
-
4
Bell
Alarm
with
Lockout
Operation
3
-
5
Shunt
Trip
Operation
3
-
6
Undervoltage
Release
Operation
3
-
7
Accessory
Configuration
at
the
Trip
Unit
Description
of
Switch
Settings
SB
Motor
Operator
Mechanism
Remote
Operation
Automatic
Operation
3
-
9
Remote
Close
Accessory
Remote
Operation
3
-
10
Key
Interlock
Mounting
Provision
Operation
3
-
11
Mechanical
Counter
8
8
8
9
9
10
10
11
11
11
11
.
12
12
.
13
13
13
13
14
14
15
n
l
i
>
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
List
of
Figures
1
.
Locations
of
front
-
panel
escutcheon
cutout
and
mounting
holes
2
.
Locations
of
screw
inserts
for
mounting
breaker
in
equipment
3
.
Front
of
breaker
,
showing
location
of
standard
features
4
.
Front
of
breaker
,
with
Trip
Unit
and
top
cover
removed
5
.
Side
view
of
breaker
,
showing
padlock
hasp
extended
6
.
Terminal
block
mounted
on
right
side
of
the
breaker
7
.
Locations
of
plug
-
in
accessory
modules
in
compartment
on
front
of
breaker
8
.
Bell
Alarm
-
Alarm
Only
module
9
.
Bell
Alarm
-
Alarm
Only
connections
on
the
right
terminal
block
10
.
Bell
Alarm
with
Lockout
module
11
.
Bell
Alarm
with
Lockout
connections
on
the
right
terminal
block
12
.
Shunt
Trip
module
13
.
Undervoltage
Release
module
14
.
Accessory
configuration
switch
on
rear
of
Trip
LInit
,
showing
factory
settings
15
.
Motor
Operator
Mechanism
16
.
Remote
Close
accessory
17
.
Key
Interlock
18
.
Side
view
of
breaker
,
showing
padlock
tab
extended
with
Key
Interlock
installed
.
19
.
Mechanical
Counter
20
.
Auxiliary
Switch
Module
with
12
switches
21
.
Auxiliary
switch
wiring
diagram
22
.
Door
Interlock
accessory
installed
on
breaker
23
.
Push
Button
Cover
2
2
3
3
.
6
6
8
9
9
9
10
10
11
12
12
13
14
14
15
15
15
16
17
e
IV
Courtesy of NationalSwitchgear.com

"
T
Power
Break
®
/
/
Circuit
Breakers
List
of
Tables
m
1
.
Weights
of
various
breaker
frame
sizes
,
with
and
without
motor
operator
.
2
.
Bolt
sizes
and
mounting
torques
for
bus
connections
3
.
Sequence
of
operations
that
may
be
performed
with
Power
Break
®
II
circuit
breakers
4
4
.
Accessory
connections
to
the
right
terminal
block
5
.
Catalog
numbers
of
direct
-
mounting
lugs
6
.
Bell
Alarm
-
Alarm
Only
catalog
numbers
7
.
Bell
Alarm
with
Lockout
catalog
numbers
8
.
Catalog
numbers
and
voltages
for
the
Shunt
Trip
9
.
Catalog
numbers
and
voltages
for
the
Undervoltage
Release
„
10
.
Accessory
configuration
switch
settings
,
including
factory
defaults
11
.
Catalog
numbers
and
operating
voltages
for
the
Motor
Operator
Mechanism
12
.
Catalog
numbers
and
operating
voltages
for
the
Remote
Close
accessory
13
.
Catalog
numbers
of
Key
Interlock
models
.
14
.
Auxiliary
Switch
Module
catalog
numbers
15
.
Auxiliary
switch
positions
on
the
terminal
board
on
the
left
side
of
the
breaker
1
1
7
8
9
10
10
11
12
13
13
14
15
16
J
9
LJ
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
1
.
Introduction
4
jl
1
-
3
Preparation
for
Installation
1
-
1
Overview
Power
Break
®
II
insulated
-
case
circuit
breakers
are
designed
to
protect
low
-
voltage
power
circuits
and
equipment
.
They
are
available
with
MicroVersa
-
Trip
®
Plus
and
PM
Trip
Units
for
fault
detection
.
Electrical
Connections
Using
an
industry
-
accepted
solvent
,
remove
any
foreign
material
from
the
line
and
load
strap
sur
-
faces
and
the
corresponding
surfaces
of
the
con
-
necting
bus
.
Ensure
that
the
mating
surfaces
are
smooth
and
free
of
burrs
and
nicks
.
Place
the
bus
connections
in
position
and
align
the
mounting
holes
.
Insert
and
fasten
the
mounting
bolts
and
washers
according
to
specifications
in
Table
2
.
1
-
2
Receiving
the
Breaker
Unpack
the
circuit
breaker
and
inspect
it
for
ship
-
ping
damage
.
Ensure
that
the
breaker
has
the
proper
current
,
voltage
,
and
interruption
ratings
for
the
application
by
comparing
the
catalog
number
with
the
table
in
the
Getting
Started
section
on
the
inside
front
page
.
The
weights
of
the
various
frame
sizes
are
listed
in
Table
1
,
for
reference
.
Bus
Connection
Breaker
Frame
Bolt
Diam
.
Torque
(
in
-
lb
)
(
1
)
1
/
2
in
.
300
800
A
Operation
Type
Frame
Rating
Weight
(
2
)
l
/
2
in
.
1600
-
2000
A
300
(
ib
.
)
Table
2
.
Bolt
sizes
and
mounting
torques
for
bus
connections
.
71
800
A
Manual
Electrical
80
Panel
Cutouts
and
Clearances
Use
the
following
information
to
prepare
the
equipment
and
assure
proper
clearances
for
instal
-
lation
and
operation
of
the
breaker
.
Figure
1
shows
the
front
-
panel
escutcheon
cutout
pattern
and
the
locations
of
the
breaker
mounting
bolts
.
The
standard
door
cutout
dimensions
require
a
trim
plate
on
the
breaker
.
The
optional
dimen
-
sions
are
for
flush
front
or
non
-
hinged
door
con
-
struction
and
the
trim
plate
may
be
omitted
.
Venti
-
lation
cutouts
are
required
for
stationary
-
mounted
1600
A
and
2000
A
frame
breakers
and
for
draw
-
out
-
mounted
2000
A
frame
breakers
.
Ventilation
cutouts
are
not
required
for
drawout
-
mounted
800
A
or
1600
A
frame
breakers
or
for
stationary
-
mounted
800
A
frame
breakers
.
Because
of
arc
chamber
venting
,
the
minimum
through
-
air
distance
from
the
top
of
the
breaker
’
s
molded
case
to
grounded
metal
is
4
50
inches
[
114
mm
]
in
an
area
5.31
inches
x
16.00
inches
[
135
mm
x
406
mm
]
,
centered
over
the
vent
screens
.
(
Refer
to
outline
drawings
10054370
,
Sheets
1
-
5
,
for
details
.
)
79
2000
A
Manual
Electrical
88
Table
1
.
Weights
of
various
breaker
frame
sizes
,
with
and
without
motor
operator
;
Storage
The
breaker
should
be
placed
in
service
immedi
-
ately
in
its
permanent
location
.
However
,
if
it
must
be
stored
for
an
indefinite
period
,
it
should
be
care
-
fully
protected
against
condensation
,
preferably
by
storage
in
a
warm
dry
room
.
Circuit
breakers
for
outdoor
equipment
should
be
stored
in
that
equip
-
ment
only
when
power
is
available
and
heaters
are
in
operation
,
to
prevent
condensation
.
The
breaker
should
be
stored
in
a
clean
location
,
free
from
corrosive
gases
or
fumes
.
In
particular
,
protect
the
breaker
from
moisture
and
cement
dust
,
as
that
combination
may
be
corrosive
.
If
the
breaker
is
stored
for
any
length
of
time
,
it
should
be
inspected
periodically
to
ensure
good
mechanical
condition
.
i
Courtesy of NationalSwitchgear.com

I
Power
Break
®
II
Circuit
Breakers
Chapter
1
.
Introduction
1
-
4
Breaker
Installation
Door
Vent
{
1600
&
2000
A
stationary
and
2000
A
drawout
only
}
[
See
GE
drawing
10054370
,
sheet
5
]
Ensure
that
all
accessory
connections
are
secure
.
Line
up
the
bolt
holes
in
the
enclosure
with
the
attachment
points
on
the
breaker
,
illustrated
in
Figure
2
,
insert
the
bolts
and
tighten
.
Use
non
-
magnetic
material
in
the
area
between
the
line
and
load
terminals
to
support
the
breaker
.
B
p
-
2.25
—
|
t
A
©
©
r
i
o
m
(
®
m
(
®
.
©
T
c
i
©
3.25
-
I
L
J
Door
Vent
(
1600
&
2000
A
stationary
and
2000
A
drawout
only
)
[
See
GE
drawing
10054370
,
sheet
5
)
Standard
Dimension
Optional
Figure
2
.
Locations
of
1
/
4
-
20
x
3
/
b
-
inch
deep
screw
inserts
for
mounting
breaker
in
equipment
10.00
(
254
]
9.83
(
249.7
]
14.00
[
356
]
13.38
[
339.9
]
1.69
(
42.9
]
1.605
(
40.8
]
A
B
C
Figure
l
Locations
of
front
-
panel
escutcheon
cutout
and
mounting
holes
.
Accessory
Installation
The
following
accessories
may
be
installed
in
the
breaker
.
Refer
to
the
instruction
sheet
supplied
with
each
accessory
for
catalog
numbers
and
installation
instructions
.
•
Lugs
and
Adapters
•
Motor
Operator
Mechanism
•
Remote
Close
•
Undervoltage
Release
•
Shunt
Trip
•
Bell
Alarm
-
Alarm
Only
•
Bell
Alarm
with
Lockout
•
Auxiliary
Switch
Module
•
Mechanical
Counter
•
Key
Interlock
Mounting
Provision
•
Push
Button
Cover
•
Door
Interlock
•
Walking
-
Beam
Interlock
2
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
2
.
Operation
2
-
1
Standard
Features
Power
Break
II
circuit
breakers
are
equipped
with
the
following
standard
features
.
The
letters
are
keyed
to
the
breaker
photographs
in
Figures
3
and
4
.
A
Indicator
:
ON
-
Red
OFF
-
Green
B
Indicator
:
CHARGED
-
Yellow
DISCHARGED
-
White
C
ON
button
D
OFF
button
E
Manual
charging
handle
F
Integral
36
-
point
terminal
block
(
12
auxiliary
switches
,
A
-
B
type
)
G
Integral
36
-
point
terminal
block
(
all
other
connections
)
H
Sealable
hinged
cover
I
Cover
mounting
screws
(
4
)
K
Trip
Unit
interchangeable
rating
plug
L
Test
set
connection
port
M
Standard
padlock
provision
N
Dust
-
resistant
ventilation
slots
Figure
4
.
Front
of
breaker
,
with
Trip
Unit
and
top
cover
removed
.
2
-
2
Operating
Instructions
Sequence
of
Operations
The
sequence
of
operations
that
may
be
performed
on
the
circuit
breaker
are
listed
in
Table
3
.
Refer
fc
>
Chapter
3
for
information
about
accessory
opera
-
tion
.
Figure
3
.
Front
of
breaker
,
showing
location
of
standard
features
.
3
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
2
.
Operation
On
/
Off
Indicator
Charge
Indicator
Main
Breaker
Contacts
Condition
of
Charging
Springs
Next
Permissible
Operating
Function
OFF
DISCHARGED
Open
Discharged
Mechanism
may
be
charged
OFF
CHARGED
Open
Charged
Contacts
may
be
closed
DISCHARGED
Closed
ON
Discharged
Mechanism
may
be
recharged
or
Contacts
may
be
opened
Closed
ON
CHARGED
Charged
Contacts
may
be
opened
Table
3
.
Sequence
of
operations
that
may
be
performed
with
Power
Break
II
circuit
breakers
.
Operating
Instructions
for
Manually
Operated
Breaker
•
Bell
Alarm
with
Lockout
not
reset
after
over
-
current
lockout
.
•
Undervoltage
Release
not
energized
.
Charging
the
Mechanism
Springs
These
conditions
must
be
corrected
before
the
Pull
the
operating
handle
down
about
90
°
(
until
it
breaker
can
be
closed
.
stops
)
.
Repeat
five
more
times
to
fully
charge
the
~
springs
.
This
urill
not
close
the
breaker
contacts
.
The
ATTENTION
:
Les
contacts
de
disjoncteur
principal
charge
indicator
will
show
CHARGED
on
a
yellow
peuvent
etre
fermes
ou
le
loquet
de
disjoncteur
est
background
.
When
the
springs
are
fully
charged
,
maintenu
en
position
declenchee
a
cause
de
toute
des
conditions
suivantes
:
the
handle
locks
in
the
stored
position
.
•
Si
le
verrou
de
cle
ou
le
cadenas
est
verrouille
en
position
OFF
.
•
Si
le
chariot
du
verrou
debrochable
est
localise
entre
les
positions
TEST
et
CONNECTED
.
•
Si
la
rearmeture
du
declencheur
(
LO
)
n
’
est
pas
realisee
apres
le
verrouillage
en
position
“
ouvert
”
provenant
du
courantde
surcharge
.
•
Si
le
minimum
de
tension
(
UVR
)
n
’
est
pas
sous
tension
.
Ces
conditions
doivent
etre
corrigees
avant
le
disjoncteur
peut
etre
ferme
.
t
NOTE
The
breaker
cannot
be
closed
unless
the
springs
are
fully
charged
and
the
handle
is
stored
fully
in
.
NOTE
La
fermeture
du
disjoncteur
ne
peut
etre
realisee
a
moins
que
les
ressorts
soient
rearmes
tout
a
fait
,
et
le
levier
est
completement
remis
a
la
position
d
’
emmagasinage
.
Closing
the
Breaker
Close
the
breaker
contacts
with
either
of
the
follow
-
ing
methods
:
•
Depress
the
ON
button
on
the
front
of
the
breaker
.
•
Energize
the
(
optional
)
Remote
Close
acces
-
sory
.
Opening
the
Breaker
Open
the
breaker
contacts
with
either
of
the
follow
-
ing
methods
:
•
Depress
the
OFF
button
on
the
front
of
the
breaker
.
•
Energize
the
(
optional
)
Shunt
Trip
accessory
or
de
-
energize
the
(
optional
)
Undervoltage
Release
accessory
.
CAUTION
:
The
main
breaker
contacts
cannot
be
closed
if
the
breaker
latch
is
held
in
the
tripped
position
by
any
of
the
following
conditions
:
•
Key
interlock
or
padlock
in
locked
OFF
condi
-
tion
.
Draw
-
out
interlock
with
carriage
between
TEST
and
CONNECTED
positions
.
t
4
Courtesy of NationalSwitchgear.com

*
r
Power
Break
®
II
Circuit
Breakers
Chapter
2
.
Operation
s
Operating
Instructions
for
Motor
-
Operated
Breaker
Charging
the
Mechanism
Springs
Charge
the
mechanism
closing
springs
with
either
of
the
following
methods
:
•
Short
terminals
17
and
35
on
the
right
termi
-
nal
block
,
with
a
push
button
or
similar
device
,
for
a
minimum
of
five
seconds
.
•
If
power
is
lost
during
the
charge
cycle
,
finish
charging
the
springs
by
cycling
the
charging
handle
until
the
indicator
shows
CHARGED
on
a
yellow
background
.
When
the
springs
are
fully
charged
,
the
handle
locks
in
the
stored
position
.
ATTENTION
:
Les
contacts
de
disjoncteur
principal
peuvent
etre
fermes
ou
le
loquet
de
disjoncteur
est
maintenu
en
position
declenchee
a
cause
de
toute
des
conditions
suivantes
:
•
Si
le
verrou
de
cle
ou
le
cadenas
est
verrouille
en
position
OFF
.
•
Si
le
chariot
du
verrou
debrochable
est
localise
entre
les
positions
TEST
et
CONNECTED
.
•
Si
la
rearmeture
du
declencheur
(
LO
)
n
'
est
pas
realisee
apres
le
verrouillage
en
position
“
ouvert
”
provenant
du
courant
de
surcharge
.
•
Si
le
minimum
de
tension
(
UVR
)
n
’
est
pas
sous
tension
.
Ces
conditions
doivent
etre
corrigees
avant
le
disjoncteur
peut
etre
ferme
.
NOTE
:
The
breaker
cannot
be
closed
unless
the
springs
are
fully
charged
and
the
handle
is
stored
Opening
the
Breaker
fully
in
.
Open
the
breaker
contacts
with
either
of
the
follow
-
ing
methods
:
•
Energize
the
(
optional
)
Shunt
Trip
accessory
or
de
-
energize
the
(
optional
)
Undervoltage
Release
accessory
.
•
Depress
the
OFF
button
on
the
front
of
the
breaker
.
NOTE
:
La
fermeture
du
disjoncteur
ne
peut
etre
realisee
a
moins
que
les
ressorts
soient
rearmes
tout
a
fait
,
et
le
levier
est
completement
remis
a
la
position
d
’
emmagasinage
.
i
Closing
the
Breaker
Close
the
breaker
contacts
with
either
of
the
follow
-
ing
methods
:
•
Energize
the
closing
solenoid
by
applying
the
Connect
terminals
17
and
35
on
the
terminal
block
rated
voltage
to
terminals
16
and
34
on
the
right
terminal
block
.
•
Depress
the
ON
button
on
the
front
of
the
the
breaker
closing
springs
whenever
the
breaker
breaker
.
Automatic
Operation
on
the
right
side
of
the
breaker
with
a
jumper
wire
.
The
Motor
Operator
will
automatically
recharge
closes
.
CAUTION
:
The
main
breaker
contacts
cannot
be
CAUTION
:
Do
not
wire
breakers
for
automatic
close
,
closed
if
the
breaker
latch
is
held
in
the
tripped
position
by
any
of
the
following
conditions
:
•
Key
Interlock
or
padlock
in
locked
OFF
condi
-
tion
.
•
Drawout
interlock
with
carriage
between
TEST
and
CONNECTED
positions
.
•
Bell
Alarm
with
Lockout
not
reset
after
over
-
current
lockout
.
•
Undervoltage
Release
not
energized
.
These
conditions
must
be
corrected
before
the
breaker
can
be
closed
.
ATTENTION
:
Ne
pas
connecter
les
disjoncteurs
pour
la
fermeture
automatique
.
5
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
2
.
Operation
Padlock
Operation
Wiring
Notes
The
padlock
prevents
the
breaker
from
closing
by
Figure
6
illustrates
the
terminal
block
installed
on
holding
the
trip
latch
in
the
tripped
position
.
To
the
right
side
of
the
breaker
.
Table
4
lists
the
device
install
the
padlock
,
use
the
following
procedure
:
1
.
Trip
the
breaker
(
press
the
OFF
button
)
.
2
.
Grasp
the
padlock
tab
(
see
Figure
3
)
and
pull
it
out
until
it
is
fully
extended
,
as
illustrated
in
Figure
5
.
Note
that
if
the
breaker
contacts
are
closed
,
the
padlock
tab
will
not
extend
.
3
.
Insert
the
padlock
;
the
breaker
will
not
close
.
connections
to
the
terminal
block
.
Each
terminal
point
will
accept
the
following
connections
:
•
Bare
stripped
wire
-
one
#
12
AWG
or
two
#
14
AWG
.
J
•
Ring
or
spade
connectors
—
two
per
terminal
.
The
terminal
screws
should
be
torqued
to
7
-
9
in
-
lbs
.
The
left
terminal
block
is
blank
unless
the
optional
NOTE
:
As
many
as
three
1
/
4
”
—
^
8
”
padlocks
may
Auxiliary
Switch
Module
accessory
is
ordered
,
be
attached
at
one
time
.
NOTE
:
Jusqu
’
a
trois
cadenas
de
1
/
4
”
-
3
/
8
”
peuvent
etre
attaches
a
la
fois
.
t
Figure
6
.
Terminal
block
mounted
on
right
side
of
the
breaker
.
Figure
5
.
Side
view
of
breaker
,
showing
padlock
hasp
extended
.
Periodic
Operational
Checks
Approximately
once
a
year
,
verify
that
the
breaker
is
operating
correctly
by
opening
and
closing
the
mechanism
.
6
Courtesy of NationalSwitchgear.com

f
Power
Break
®
//
Circuit
Breakers
Chapter
2
.
Operation
Terminal
Terminal
18
Motor
Operator
+
36
Motor
Operator
-
17
Remote
Charge
+
35
Remote
Charge
-
16
Remote
Close
+
34
Remote
Close
-
15
Bell
Alarm
only
Com
33
Charge
Indicator
14
Bell
Alarm
only
NO
32
Shunt
Trip
13
Bell
Alarm
only
NC
31
Shunt
Trip
12
Lockout
Common
30
Undervoltage
Release
11
Lockout
NO
29
Undervoltage
Release
10
Lockout
NC
28
Reserved
27
Reserved
9
Reserved
8
Reserved
26
Zone
-
Select
Input
-
7
commnet
-
25
Zone
-
Select
Input
+
6
commnet
+
24
Zone
-
Select
Output
-
5
C
Phase
Volts
23
Zone
-
Select
Output
+
4
B
Phase
Volts
22
Draw
-
Out
Switch
3
A
Phase
volts
21
Draw
-
Out
Switch
2
24
Vdc
-
20
^
Tap
1
24
Vdc
+
19
-
N
-
Common
Table
4
.
Accessory
connections
to
the
right
terminal
block
.
2
-
3
Trip
Unit
Setup
See
GEH
-
6273
for
detailed
instructions
on
setting
up
MicroVersaTrip
Plus
and
MicroVersaTrip
PM
Trip
Units
.
The
procedure
for
setting
up
the
accessory
con
-
figuration
DIP
switch
on
the
rear
of
the
Trip
LInit
is
described
in
Chapter
3
.
t
7
Courtesy of NationalSwitchgear.com

Power
Break
®
\\
Circuit
Breakers
Chapter
3
.
Accessory
Operation
Following
are
the
operation
procedures
for
each
of
the
available
breaker
accessories
.
See
the
user
guides
supplied
with
the
accessories
for
installation
and
removal
.
3
-
2
Plug
-
In
Accessory
Compartment
Several
of
the
accessories
are
installed
in
the
acces
-
sory
compartment
on
the
front
of
the
breaker
.
Figure
7
illustrates
this
compartment
and
the
locations
of
each
of
the
plug
-
in
accessory
modules
.
3
-
1
Lugs
and
Adapters
Direct
-
mounting
lugs
bolt
directly
to
the
line
or
load
strap
of
the
circuit
breaker
.
Lug
catalog
num
-
bers
and
sizes
are
listed
in
Table
5
.
Shunt
Trip
Cat
*
No
*
Wires
Wire
Sizes
Amps
Bell
Alarm
with
Lockout
Bell
Alarm
-
Alarm
Only
#
2
-
600
kcmil
CU
/
AL
1
/
0
-
250
kcmil
CU
/
AL
1
TPLUG
106
m
2
TPLUG
206
2
#
2
-
600
kcmil
CU
/
AL
600
300
-
750
kcmil
CU
/
AL
TPLUG
308
3
800
Undervoltage
Release
300
-
750
kcmil
CU
/
AL
3
THPCLUG
308
800
TPLUG
408
4
500
-
800
kcmil
CU
/
AL
1600
Figure
7
.
Locations
of
plug
-
in
accessory
modules
in
compartment
on
front
of
breaker
.
THPCLUG
408
4
500
-
800
kcmil
CU
/
AL
1600
Table
5
.
Catalog
numbers
of
direct
-
mounting
lugs
.
Bus
adapters
(
T
-
studs
)
bolt
directly
to
the
line
or
load
terminals
of
the
breaker
.
The
catalog
numbers
are
:
3
-
3
Bell
Alarm
-
Alarm
Only
The
Bell
Alarm
-
Alarm
Only
module
,
shown
in
Figure
8
,
provides
a
switch
to
remotely
indicate
that
the
circuit
breaker
has
tripped
.
It
is
reset
either
automatically
when
the
circuit
breaker
is
reclosed
or
manually
when
the
reset
button
on
the
front
of
the
Bell
Alarm
-
Alarm
Only
module
is
pressed
.
In
addition
to
activation
by
protection
trips
,
the
Bell
Alarm
-
Alarm
Only
accessory
module
can
be
set
up
to
interact
with
other
Power
Break
II
accessories
.
DIP
switches
on
the
rear
of
the
Trip
Unit
can
con
-
figure
the
Bell
Alarm
-
Alarm
Only
accessory
to
activate
when
a
Shunt
Trip
or
Undervoltage
Release
trip
occurs
.
The
catalog
numbers
for
the
Bell
Alarm
-
Alarm
Only
are
listed
in
Table
6
.
For
installation
instructions
see
GEH
-
6275
.
•
SP
08
FCA
and
SP
08
FCC
for
800
A
frames
•
SP
20
FCA
and
SP
20
FCC
for
1600
A
and
2000
A
frames
Lug
adapters
bolt
directly
to
the
line
or
load
termi
-
nals
on
the
rear
of
the
breaker
.
They
provide
proper
phase
-
to
-
phase
clearances
for
mounting
lugs
.
The
catalog
numbers
are
:
•
TPLUGA
08
for
800
A
frames
•
TPLUGA
16
for
1600
A
frames
•
SPLUGA
20
for
2000
A
frames
(
may
also
be
used
on
1600
A
frames
)
Installation
instructions
for
lugs
and
adapters
are
found
in
GEH
-
4546
.
8
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
3
.
Accessory
Operation
9
15
(
Common
)
14
(
Normally
Open
)
/
13
(
Normally
Closed
)
/
/
Figure
9
.
Bell
Alarm
-
Alarm
Only
connections
on
the
right
terminal
block
.
The
contacts
are
shown
in
the
reset
state
.
^
Bfll
Alarm
/
Alarm
Only
^
9
RatifKJ
6
A
/
7
WVAC
50
/
SOHi
5
A
/
12
SVDC
(
35
25
A
/
?
bOVni
:
SPBAA
240
f
#
3
-
4
Bell
Alarm
with
Lockout
The
Bell
Alarm
with
Lockout
module
,
shown
in
Figure
10
,
prevents
reclosing
of
the
breaker
after
a
trip
until
the
Bell
Alarm
with
Lockout
is
reset
.
It
can
only
be
reset
by
pressing
the
button
on
the
top
of
the
module
.
This
module
also
provides
a
switch
to
remotely
indicate
that
the
circuit
breaker
has
tripped
.
Figure
8
.
Bell
Alarm
-
Alarm
Only
module
.
Catalog
No
.
Contact
Rating
SPBAA
240
6
A
at
240
Vac
0.25
A
at
250
Vdc
0.50
A
at
125
Vdc
SPBAA
600
©
6
A
at
600
Vac
0.25
A
at
250
Vdc
0.50
A
at
125
Vdc
©
600
V
version
is
not
UI
,
listed
.
Table
6
.
Bell
Alarm
-
Alarm
Only
catalog
numbers
.
AM
H
.
llihfj
ffl
6
A
/
?
*
)
VAr
.
|
bO
/
SOH
/
tg
bA
/
mvDC
l
®
2
SA
/
7
SOVOC
1
/
Operation
The
Bell
Alarm
-
Alarm
Only
provides
normally
open
(
NO
)
and
normally
closed
(
NC
)
outputs
available
at
the
terminal
block
on
the
right
side
of
the
breaker
,
as
illustrated
in
Figure
9
.
The
outputs
change
state
whenever
a
breaker
trip
occurs
.
This
trip
can
be
caused
by
an
overcurrent
condition
detected
by
the
Trip
Unit
or
can
be
generated
by
the
Shunt
Trip
or
Undervoltage
Release
,
installed
and
if
the
appropriate
DIP
switches
have
been
set
on
the
back
of
the
Trip
Unit
.
(
See
Section
3
-
7
,
Accessory
Configuration
at
the
Trip
Unit
.
)
The
Bell
Alarm
-
Alarm
Only
accessory
resets
automatically
,
returning
the
outputs
to
their
nor
-
mal
configuration
,
when
the
breaker
is
reclosed
.
The
Bell
Alarm
-
Alarm
Only
can
also
be
reset
The
catalog
numbers
for
the
Bell
Alarm
with
manually
,
before
the
breaker
is
reclosed
,
by
press
-
Lockout
are
listed
in
Table
7
.
For
installation
ing
the
reset
button
on
the
front
of
the
module
.
Bell
Alarm
/
Lock
Out
Catalog
Ha
SPBA
12
AG
7
/
Figure
10
.
Bell
Alarm
with
Lockout
module
.
il
In
addition
to
activation
by
protection
trips
,
the
Bell
Alarm
with
Lockout
accessory
module
can
be
set
up
to
interact
with
other
Power
Break
II
accessories
.
DIP
switches
on
the
rear
of
the
Trip
Unit
can
con
-
figure
the
Bell
Alarm
with
Lockout
accessory
to
activate
when
a
Shunt
Trip
or
Undervoltage
Release
trip
occurs
.
instructions
see
GEH
-
6278
.
9
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
3
.
Accessory
Operation
Catalog
No
.
Contact
Rating
SPBAL
240
6
A
at
240
Vac
0.25
A
at
250
Vdc
0.50
A
at
125
Vdc
t
i
SPBAL
600
©
6
A
at
600
Vac
0.25
A
at
250
Vdc
0.50
A
at
125
Vdc
©
The
600
V
version
is
not
UL
listed
.
Table
7
.
Bell
Alarm
with
Lockout
catalog
numbers
.
31
EtfC
32
4
MOO
Peak
Wash
120
V
AC
50
/
60
HZ
125
VDC
Remove
accessory
power
‘
V
-
ig
or
removing
Norn
Current
85
mA
1.5
A
Operation
The
Bell
Alarm
with
Lockout
prevents
reclosing
of
the
breaker
after
a
trip
until
the
reset
button
on
the
front
of
the
module
is
pressed
.
This
trip
can
be
caused
by
an
overcurrent
condition
detected
by
the
Trip
Unit
or
can
be
generated
by
the
Shunt
Trip
or
Undervoltage
Release
,
if
installed
and
if
the
appro
-
priate
switches
have
been
set
on
the
back
of
the
Trip
Unit
.
(
See
Section
3
-
7
,
Accessory
Configura
-
tion
at
the
Trip
Unit
.
)
In
addition
,
the
Bell
Alarm
with
Lockout
provides
normally
open
(
NO
)
and
normally
closed
(
NC
)
alarm
outputs
available
at
the
terminal
block
on
the
right
side
of
the
breaker
,
as
illustrated
in
Figure
11
.
These
outputs
are
returned
to
their
normal
state
when
the
Bell
Alarm
with
Lockout
reset
button
is
firmly
pressed
.
Figure
12
.
Shunt
Trip
module
.
In
addition
to
providing
a
trip
signal
to
the
breaker
,
the
Shunt
Trip
accessory
module
can
be
set
up
to
interact
with
other
Power
Break
13
accessories
.
DIP
switches
on
the
rear
of
the
breaker
Trip
Unit
can
configure
the
Shunt
Trip
accessory
to
activate
a
Bell
Alarm
-
Alarm
Only
accessory
or
a
Bell
Alarm
with
Lockout
accessory
when
a
Shunt
trip
occurs
.
(
See
Section
3
-
7
,
Accessory
Configuration
at
the
Trip
Unit
.
)
The
catalog
numbers
for
the
Shunt
Trip
for
various
voltage
applications
are
listed
in
Table
8
.
For
installation
instructions
see
GEH
-
6284
.
12
(
Common
)
Catalog
Number
Voltage
Rating
®
Peak
Inrush
Current
,
A
®
Nominal
RMS
Current
,
mA
24
Vac
24
Vdc
SPST
024
1.5
140
11
(
Normally
Open
)
48
Vac
48
Vdc
SPST
048
1.5
110
10
(
Normally
Closed
)
120
Vac
125
Vdc
SPST
120
1.5
85
Figure
11
.
Bell
Alarm
with
Lockout
connections
on
the
right
terminal
block
.
The
contacts
are
shown
in
the
reset
state
.
SPST
208
208
Vac
1.5
50
240
Vac
250
Vdc
SPST
240
1.5
40
®
24
-
240
Vac
devices
are
rated
for
50
/
60
Hz
.
®
Peak
inrush
current
is
present
for
2
-
6
ms
after
activation
.
This
number
is
provided
so
that
fuses
and
supplies
can
be
chosen
appropriately
.
Table
8
.
Catalog
numbers
and
voltages
for
the
Shunt
Trip
.
3
-
5
Shunt
Trip
The
Shunt
Trip
module
,
shown
in
Figure
12
,
allows
the
breaker
to
be
tripped
electrically
from
a
remote
location
.
10
Courtesy of NationalSwitchgear.com

'
Power
Break
®
II
Circuit
Breakers
Chapter
3
.
Accessory
Operation
j
Operation
Apply
control
voltage
to
terminals
31
and
32
of
the
terminal
strip
on
the
right
side
of
the
breaker
to
trip
the
circuit
breaker
.
The
Shunt
Trip
will
cause
the
circuit
breaker
to
trip
when
the
control
voltage
is
greater
than
75
%
of
the
dc
-
rated
value
or
55
%
of
the
ac
-
rated
value
.
Catalog
Number
Voltage
Rating
®
Peak
Inrush
Current
,
A
®
Nominal
RMS
Current
,
mA
SPUV
024
DC
24
Vdc
15
140
7.5
SPUV
048
DC
70
48
Vdc
SPUV
125
DC
125
Vdc
3
30
J
SPUV
250
DC
250
Vdc
1.5
15
•
*
370
SPUV
024
AC
24
Vac
15
7.5
SPUV
048
AC
48
Vac
210
<
SPUV
120
AC
120
Vac
3
80
3
-
6
Undervoltage
Release
SPUV
208
AC
208
Vac
1.9
60
SPUV
240
AC
240
Vac
1.5
45
The
Undervoltage
Release
(
UVR
)
module
,
shown
in
Figure
13
,
trips
the
circuit
breaker
when
the
input
control
voltage
drops
to
35
-
60
%
of
its
rated
value
and
prevents
an
open
breaker
from
closing
until
the
input
control
voltage
is
greater
than
80
%
of
the
rated
value
.
®
24
-
240
Vac
devices
are
rated
for
50
/
60
Hz
.
®
Peak
inrush
current
is
present
for
2
-
6
ms
after
activation
.
This
number
is
provided
so
that
fuses
and
supplies
can
be
chosen
appropriately
.
Table
9
.
Catalog
numbers
and
voltages
for
the
Undervoltage
Release
.
Operation
Apply
control
voltage
to
terminals
29
and
30
of
the
terminal
strip
on
the
right
side
of
the
breaker
.
When
the
applied
control
voltage
is
above
80
%
of
the
UVR
’
s
rated
value
,
the
breaker
can
be
closed
.
When
the
voltage
drops
to
35
-
60
%
of
the
rated
value
,
the
UVR
will
trip
the
breaker
.
*
me
30
-
4
M
00
Undervoltage
Release
C
*
OM
|
Q
ftai
xq
Peak
Inrush
Horn
Current
SPUV
12
QAC
120
V
AC
3
A
80
mA
Uste
<
3
iftUSA
accessory
power
m
betore
mstaitmg
or
removing
.
W
3
-
7
Accessory
Configuration
at
the
Trip
Unit
The
Trip
Unit
has
a
six
-
position
DIP
switch
module
on
the
rear
of
the
unit
that
controls
the
configura
-
tion
of
the
Power
Break
II
integrated
accessories
.
In
addition
to
providing
a
trip
signal
to
the
breaker
,
These
switches
can
be
set
up
to
define
the
types
of
the
UVR
accessory
module
can
be
set
up
to
interact
signals
(
protection
trip
,
Shunt
trip
,
or
Undervoltage
with
other
Power
Break
II
accessories
.
DIP
Release
trip
)
that
activate
the
Bell
Alarm
-
Alarm
switches
on
the
rear
of
the
breaker
Trip
Unit
can
Only
and
Bell
Alarm
with
Lockout
accessories
on
configure
the
UVR
accessory
to
activate
a
Bell
the
Power
Break
II
breaker
.
Each
of
the
six
Alarm
-
Alarm
Only
accessory
or
a
Bell
Alarm
switches
enables
or
disables
a
different
path
to
acti
-
with
Lockout
accessory
when
a
UVR
trip
occurs
,
vate
these
accessories
from
the
different
types
of
(
See
Section
3
-
7
,
Accessory
Configuration
at
the
trip
signals
.
Trip
Unit
.
)
Figure
13
.
Undervoltage
Release
module
.
The
Trip
Unit
DIP
switches
are
illustrated
in
Fig
-
The
catalog
numbers
for
the
UVR
for
various
volt
-
ure
14
,
with
the
factory
settings
shown
.
Table
10
age
applications
are
listed
in
Table
9
.
For
installa
-
lists
the
switch
functions
,
tion
instructions
see
GEH
-
6285
.
ii
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
3
.
Accessory
Operation
Push
in
this
sides
to
disable
Only
also
change
state
.
The
factory
switch
setting
is
enabled
.
4
.
When
the
Shunt
Trip
accessory
causes
the
breaker
to
trip
,
the
contacts
of
the
Bell
Alarm
with
Lockout
also
change
state
.
The
factory
switch
setting
is
disabled
.
5
.
When
the
Undervoltage
Release
accessory
causes
the
breaker
to
trip
,
the
contacts
of
the
Bell
Alarm
with
Lockout
also
change
state
.
The
factory
switch
setting
is
disabled
.
6
.
When
a
protection
trip
(
long
-
time
,
short
-
time
,
instantaneous
,
or
protective
-
relay
)
occurs
,
the
contacts
of
the
Bell
Alarm
with
Lockout
also
change
state
.
The
factory
switch
setting
is
enabled
.
CD
CJl
^
/
CO
fO
Push
in
/
this
side
to
enable
Rear
of
Trip
Unit
Figure
14
.
Accessory
configuration
switch
on
rear
of
Trip
Unit
showing
factory
settings
(
solid
part
indicates
that
switch
is
pushed
in
on
that
side
)
.
Factory
Setting
Switch
Function
1
Disabled
Shunt
trip
activates
Bell
Alarm
-
Alarm
Only
3
-
8
Motor
Operator
Mechanism
2
Disabled
UVR
trip
activates
Bell
Alarm
-
Alarm
Only
The
Motor
Operator
Mechanism
,
shown
in
Figure
15
,
provides
a
means
of
remotely
or
automatically
charging
the
springs
that
close
the
breaker
.
Table
11
lists
the
catalog
numbers
for
the
available
Motor
Operator
Mechanism
models
.
For
installation
instructions
see
GEH
-
6281
.
Enabled
3
Protection
trip
activates
Bell
Alarm
-
Alarm
Only
4
Disabled
Shunt
trip
activates
Bell
Alarm
with
Lockout
5
Disabled
UVR
trip
activates
Bell
Alarm
with
Lockout
6
Enabled
Protection
trip
activates
Bell
Alarm
with
Lockout
Table
10
.
Accessory
configuration
switch
settings
,
including
factory
defaults
.
Description
of
Switch
Settings
Following
are
descriptions
of
the
effects
of
each
accessory
switch
when
it
is
enabled
:
1
.
When
a
Shunt
Trip
accessory
causes
the
breaker
to
trip
,
the
contacts
of
the
Bell
Alarm
-
Alarm
Only
also
change
state
.
The
factory
switch
setting
is
disabled
.
2
.
When
an
Undervoltage
Release
accessory
causes
the
breaker
to
trip
,
the
contacts
of
the
Bell
Alarm
-
Alarm
Only
also
change
state
.
The
factory
switch
setting
is
disabled
.
3
.
When
the
protection
trip
(
long
-
time
,
short
-
time
,
instantaneous
,
or
protective
-
relay
)
occurs
,
the
contacts
of
the
Bell
Alarm
-
Alarm
Figure
15
.
Motor
Operator
Mechanism
.
12
Courtesy of NationalSwitchgear.com

Power
Break
®
II
Circuit
Breakers
Chapter
3
.
Accessory
Operation
Catalog
No
.
Voltage
Rating
SPE
024
24
Vdc
SPE
048
48
Vdc
SPE
072
72
Vdc
SPE
120
120
Vac
SPE
125
125
Vdc
SPE
240
240
Vac
Table
11
.
Catalog
numbers
and
operating
voltages
for
the
Motor
Operator
Mechanism
.
Remote
Operation
The
circuit
breaker
closing
springs
can
be
chargeu
remotely
by
shorting
terminals
17
and
35
on
the
terminal
block
on
the
right
side
of
the
breaker
,
with
a
push
button
or
similar
device
,
for
a
mini
-
mum
of
five
seconds
.
Figure
W
.
Remote
Close
accessory
.
Catalog
No
.
Voltage
Rating
SPRCS
024
24
Vdc
SPRCS
048
48
Vdc
Automatic
Operation
Connect
terminals
17
and
35
on
the
terminal
block
on
the
right
side
of
the
breaker
with
a
jumper
wire
.
The
Motor
Operator
will
automatically
recharge
the
breaker
closing
springs
whenever
the
breaker
closes
.
SPRCS
072
72
Vdc
SPRCS
120
120
Vac
SPRCS
125
125
Vdc
SPRCS
240
240
Vac
Table
12
.
Catalog
numbers
and
operating
voltages
for
the
Remote
Close
accessory
.
CAUTION
:
Do
not
wire
breakers
for
both
automatic
charge
and
automatic
close
.
Remote
Operation
ATTENTION
:
Ne
pas
cabler
les
disjoncteurs
pour
tous
les
deux
1
armement
automatique
et
la
The
circuit
breaker
can
be
closed
remotely
,
pro
-
fermeture
automatique
.
vided
that
the
springs
are
charged
,
by
applying
the
rated
voltage
to
terminals
16
and
34
on
the
termi
-
nal
block
on
the
right
side
of
the
breaker
.
3
-
9
Remote
Close
Accessory
The
Remote
Close
accessory
is
continuously
rated
and
has
an
anti
-
pump
feature
that
prevents
a
motor
-
*
operated
breaker
from
repeatedly
closing
into
a
fault
.
Closing
control
voltage
must
be
removed
and
reapplied
for
each
breaker
closure
.
The
Remote
Close
accessory
,
shown
in
Figure
16
provides
a
means
of
remotely
closing
the
circuit
breaker
after
the
springs
have
been
charged
.
Table
12
lists
the
catalog
numbers
for
the
available
models
.
For
installation
instructions
see
GEH
-
6283
.
13
L
Courtesy of NationalSwitchgear.com
Other manuals for Power Break II
8
Table of contents
Other GE Circuit Breaker manuals

GE
GE EntelliGuard AKR30S-800A User manual

GE
GE SD200SA User manual

GE
GE POWER/VAC GEK 86132A User manual

GE
GE ReliaGear Pro-Stock THQB User manual

GE
GE AM-13.8-500-5C User manual

GE
GE Spectra Series AMC3FGB User manual

GE
GE Spectra Series AMCB6FGB User manual

GE
GE FE 160 User manual

GE
GE M-Pact Plus User manual

GE
GE EntelliGuard G User manual

GE
GE GSTG024D User manual

GE
GE MicroVersaTrip AKR-75 User manual

GE
GE PVDB-28kV User manual

GE
GE AK-1-15 Series User manual

GE
GE EntelliGuard R7 User manual

GE
GE POWER BREAK MICRO-VERSATRIP E39ME20 User manual

GE
GE AK-15 User manual

GE
GE AK-4-75 User manual

GE
GE AM-4.16-250-6 User manual

GE
GE Power Break II User manual