GE EntelliGuard AKR30S-800A User manual

DEH41549 R05
EntelliGuard * R Retrofill
Circuit Breakers 800-5000A
Installation Manual for R3 & R6 ype Retrofill Circuit Breakers replacing
Drawout Letter Code B, D & F Legacy AKR Circuit Breakers used in
AKD-8 & Substructures.
General Electric AKD-8 Low Voltage Switchgear is a free-standing
assembly of metal-enclosed power circuit breakers. It may also be
part of a single-ended or double-ended load center unit substation.
his manual applies to EntelliGuard R breakers to be used in AKD-8
Switchgear & substructures found in OEM Equipment and GE
Switchboards using legacy AKR circuit breakers of the following types:
800-2000A, AKR-#D-30/50/ 50 circuit breakers in all Equipment types.
3200, 4000 & 5000A, AKR-#D-75/100/125 for AKD-8 switchgear,
AKR-#B-75/100/125 types in OEM equipment and AKR-#F-75/100/125
types in GE switchboards.
(# is shown in place of a number which designates the trip unit type.)

1
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Table of Contents
Preface ...................................................................................................................................................................... 4
Hazards ............................................................................................................................................................................................................................. 4
Danger ............................................................................................................................................................................................................................ 4
Warning ......................................................................................................................................................................................................................... 5
Caution ........................................................................................................................................................................................................................... 5
Notice or Note ............................................................................................................................................................................................................. 6
Warranty ........................................................................................................................................................................................................................... 6
rademarks and Patents ........................................................................................................................................................................................... 6
Standards ......................................................................................................................................................................................................................... 6
Document Conventions ............................................................................................................................................................................................. 7
Related Publications .................................................................................................................................................................................................... 7
Service and Support: Service and support always available from GE Energy. .............................................................................. 7
Estimated ime to Complete asks ...................................................................................................................................................................... 7
Product Specs ................................................................................................................................................................................................................. 7
Weight (lbs.) .................................................................................................................................................................................................................. 7
Views ............................................................................................................................................................................................................................... 8
History and Types.................................................................................................................................................... 9
AKD ...................................................................................................................................................................................................................................... 9
AKD-5—AK-25, AK-50, AK -50, AK-75, AK-100 ............................................................................................................................................... 9
AKD-6—AKR-30/30H, AKR-50/50H/ 50H, AKR-75/75H, AKR-100 ........................................................................................................ 9
AKD-8—AKR-30/30H/30L, AKR-50/50H/ 50H, AKR-75/75H, AKR-100, AKR125 .......................................................................... 10
AKD-10—WPS-08, WPH-08, WPX-08, WPS-16, WPH-16, WPS-20, WPS-32, WPH-32 WPX-32, WPS-40, WPX-40,
WPS-50, WPX-50 ......................................................................................................................................................................................................... 10
AKD 8—Retrofill Breaker ........................................................................................................................................ 11
AKD-8-Breaker Models ............................................................................................................................................................................................. 11
AKD-8—Mechanical Drawings ............................................................................................................................................................................. 13
AKD 8 Compartment .............................................................................................................................................. 16
Interior View .................................................................................................................................................................................................................. 16
Interior Components ................................................................................................................................................................................................. 17
Interior View .................................................................................................................................................................................................................. 17
Interior Components ................................................................................................................................................................................................. 18
Unpack CB ................................................................................................................................................................. 19
Quality .............................................................................................................................................................................................................................. 20
Information Label ....................................................................................................................................................................................................... 20
Product and Catalog Serial Numbers ............................................................................................................................................................... 20

2
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Remove Circuit Breaker from Container ......................................................................................................................................................... 20
Inspect.............................................................................................................................................................................................................................. 20
Store Circuit Breaker .............................................................................................................................................. 20
Check Before Installing........................................................................................................................................... 21
Clean and Grease Breaker ..................................................................................................................................... 22
Modify Retrofill ......................................................................................................................................................... 23
Modify AKD 8—AKR30S Switchgear Compartment, Only ................................................................................ 23
AKD-8 AKR-30S—Remove Glastic Sheet of compartment ..................................................................................................................... 24
AKD-8 AKR-30S —Modify Bracket ....................................................................................................................................................................... 24
Install AKD 8 (800 2000A) Retrofill Breaker ........................................................................................................ 25
AKD-8—Racked-In ...................................................................................................................................................................................................... 28
Install AKD 8 & substructure type 3200, 4000 & 5000A Retrofill Breaker. ................................................... 29
AKD-8—Racked-In ...................................................................................................................................................................................................... 30
AKD 8—Install Accessories .................................................................................................................................... 31
AKD-8—Secondary Disconnects, Bullets ......................................................................................................................................................... 31
Wire Secondary Disconnect Assembly—AKR30/30H/50/50H/30L/30S, -50H ......................................................................... 36
AKD-8—Programmer Disconnects ..................................................................................................................................................................... 38
Procedures ................................................................................................................................................................................................................. 38
Wiring and Completion......................................................................................................................................................................................... 41
AKD-8—Primary Disconnects (Contacts) or “Fingers” ............................................................................................................................... 41
Remove and Replace ............................................................................................................................................................................................ 42
Mechanical Views ................................................................................................................................................................................................... 44
Remove and Replace- AKR-75/100/125 ...................................................................................................................................................... 45
Mechanical Views-AKR-75/100/125 .............................................................................................................................................................. 48
AKD-8—Position Switch Actuator........................................................................................................................................................................ 48
AKD-8—Shutter Actuation ...................................................................................................................................................................................... 51
Install Door Interlock System ................................................................................................................................ 52
AKD-8— Kirk Key Interlock ...................................................................................................................................................................................... 55
Modify AKD 8—Switchgear Compartment ......................................................................................................... 55
Cut Power to AKD-8—Switchgear ....................................................................................................................................................................... 55
Rack Out AKD-8—Legacy/Existing CB .............................................................................................................................................................. 55
Check, Clean, Grease AKD-8—Compartment ............................................................................................................................................... 55
Install New Door .......................................................................................................................................................................................................... 56
Install AKD 8—Neutral Rogowski Current Transformer (CT) ........................................................................... 56
AKD-8—Neutral Disconnect Assembly ............................................................................................................................................................. 56
AKD-8—Neutral Disconnect Assembly, Bus Compartment .................................................................................................................... 57
AKD-8—Rogowski Assembly Part Numbers ................................................................................................................................................... 57

3
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
AKD-8-Neutral C Adapter 400A-5000A ......................................................................................................................................................... 57
Procedures ..................................................................................................................................................................................................................... 58
AKD-8—Multi-Source Ground Fault ................................................................................................................................................................... 59

4
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Preface
Hazards
he following important highlighted information appears throughout this document to warn of potential
hazards or to call attention to information that clarifies a procedure. Carefully read all instructions and
become familiar with the devices before trying to install, operate, service, or maintain this equipment.
Danger
his indicates a hazardous situation which, if not avoided, results in death or serious injury. A variety of
electrical hazards warnings are displayed here and are applied to installation manuals. hese are standard
or generic alerts and labels that must be taken quite seriously when installing Retrofill circuit breakers in AKD
switchgear and when working with potentially dangerous electrical equipment (Table 1). here are also
dangers, pertaining to product safety, that need to be custom-written for particular or specific
circumstances (Table 2).
Table 1
.
Generic
Danger Alerts and Labels Used for Documentation and
Dangerous Equipment
Table
2
.
Custom
Danger
Alerts and Labels Used for
Documentation and Dangerous
Equipment

5
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Warning
his indicates a hazardous situation, which, if not avoided, would result in death or serious injury. A variety of
electrical hazards warnings are displayed here and are applied to installation manuals. hese are standard
or generic alerts and labels that must be taken quite seriously when installing Retrofill circuit breakers in AKD
switchgear and when working equipment that can cause injury, but may not be necessarily fatal (Table 3).
here are also warnings, pertaining to product safety, that need to be custom-written for particular or
specific circumstances (Table 4).
Tabl
e 3
.
Generic
Warning
Alerts and
Labels Used for Documentation and
Dangerous Equipment
Tabl
e 4
.
Custom
Warning
Alerts and
Labels Used for
Documentation and Dangerous Equipment
Caution
his pertains to a hazard that has a low level of risk, which means that if not avoided, it could result in minor
or moderate injury. It also indicates that failure to comply with instructions may result in product damage.
he label here requires a specific message that targets a special product or procedure (Table 5).
Tabl
e 5
.
Custom
Caution
Alerts and Labels Used for Documentation
and Operating Equipment

6
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Notice or Note
his indicates important information in that it aids in job performance, that is, a notice or note is used to
notify practices not related to personal injury (Table 6).
Table
6.
Custom
Notice
Alerts and Labels Used for Documentation
and
Operating Equipment
Warranty
his document is based on information available at the time of its publication. While efforts have been made
to ensure accuracy, the information contained herein does not cover all details or variations in hardware and
software, not does it provide for every possible contingency in connection with installation, operation, and
maintenance.
Features may be described herein that are not present in all hardware and software systems. GE Energy
assumes no obligation of notice to holders of this document with respect to changes subsequently made. GE
Energy makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes
no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained
here-in. No warranties of merchantability or fitness for purpose shall apply.
Contact your local sales office if further information is required concerning any aspect of EntelliGuard R
Circuit Breaker operation or maintenance.
Trademarks and Patents
EntelliGuard* R
EntelliGuard* U
EntelliGuard* rip Unit
EntelliGuard* G
Standards
Agency Certification
Standard Number Title
ANSI C37.13,16,17,20.1,50,51,59 Low-Voltage AC Power Circuit Breakers
NEMA SG 3,5 Low-Voltage Power Circuit Breakers
NEMA AB1 --
UL 1066 Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures

7
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Document Conventions
opics and text are divided into primary, secondary, and tertiary paragraph headings.
Related Publications
Publication
Publication Number
Brochure DEA-532
Snapshot DEE-543
Installation Manual AKD
-
10
DEH
-
41550
Installation Manual AKD8 DEH-41549
Installation Manual AKD6 (800A-2000A) DEH-41548
Installation Manual AKD5 (600A-2000A) DEH-41547
Installation Manual AKD-5/6 (3000A/3200A/4000A) DEH0005240
Accessory: Door Interlock (Door Interlock Kit) DEH-41529
Accessory Retrofill Doors Assembly DEH-41563
Accessory: Position Switch Plate & Position Switch Assembly & Wiring (Position Switch Kit) DEH-41530
Accessory: Neutral Rogowski C Disconnect (Neutral Assemblies) DEH-41531
Accessory: Programmer Disconnects DEH-41532
Accessory: Finger Clusters (Cluster Assemblies) DEH-41533
Accessory: Secondary Disconnects
DEH
-
41534
FAQ DEQ-171
Application Guide DE -753
Guideform Spec DE -754
Spare/Renewal Parts Guide DE -755
Neutral C Adapters DEH0002400
Service and Support: Service and support always available from GE Energy.
Estimated Time to Complete Tasks
Wiring the secondary disconnects and verifying they match the switchgear cublicle may take 1 to 8 hrs
depending on the complexity of the original breaker. Once the retrofill breaker is fully prepared, it should
take about 20 minutes to swap out the old breaker and rack in the new EntelliGuard R retrofill circuit breaker
if the proper lifting bar and hoist are available.
he EntelliGuard R retrofill, when ordered with 4 wire ground fault, will be equipped with a Neutral C
adapter. he adapter will modify the GE MicroVersa rip type Neutral C output to a Rogowski sensor output
compatible with the EntelliGuard R’s rip Unit. With this device, it will not be necessary to change the neutral
C in the switchgear to a Rogowski sensor. Note: Neutral C Adapters are designed to modify the signal
from any Neutral C which is compatible with a MicroVersa rip or any newer GE rip Unit type originally
supplied by GE in AKD-8 switchgear from 1979 to 2015. GE type SVG… neutral C ’s are compatible. he old
GE SS Neutral C ’s are not. Neutral sensors working with any Non-GE trip units installed as the result of a
rip unit conversion kit should be assumed to be incompatible with the NC Adapter.
Product Specs
Weight (lbs.)
Retrofill Breaker Weight Cover Box Wt. Pallet Wt.
~
Accessories
Wt.
~ Shipping
Weight
AKR30S-800A 184 11 24 2 221
AKR-30/30H-800A 230 11 24 2 267
AKR-30L-800A AKR-50/50H-1600A 270 11 24 2 307
AKR
-
50H
-
2000A
270
11
24
2
307
AKR75/AKR75H-3200A 600 15 30 2 647
AKR100-4000A 625 15 30 2 672
AKR125-5000A 700 19 38 2 759

8
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Views
ypical R3 & R6 EntelliGuard R retrofill breakers are shown below. All breakers are drawout types. Each
breaker is constructed by permanently joining an EntelliGuard G circuit breaker in a steel frame, installing
primary and secondary disconnects and driving drawout racking cams thru what looks like the EntelliGuard
G Cassette’s front dashboard.
Figure
1
.
AKD
8
—
AKR30H
\
50H Breaker in Cassette (Front View)
Figure
1
A
.
AKD
8
—
AKR75
\
75
H
\
100
\
125
Breaker in Cassette (Front View)
he EntelliGuard R Circuit Breaker is suitable for application on power systems up to 635 VAC 50/60 Hz.
AKD-8 4000A
AKR-100
AKD-8 3200A
AKR75/75H
AKD-8 5000A
AKR-125

EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
History and Types
AKD
AK—Power Circuit Breaker Equipment
D—Drawout circuit breaker construction
Manufactured from 1951 to 1975, all bolted, copper bus design, all drawout breakers—AK-1, —2, —3,—15 / 25
/ 50 / 75 / 100; with a 4000A-max bus rating. Breakers had a ratcheting drawout mechanism, with an open-
door drawout. Breakers were painted ANSI 61, light gray, manufactured in Philadelphia from 1951 to the
mid-60s and in Burlington, Iowa from the mid-60s to 1975.
he breaker compartment was a welded assembly, and the equipment frame was bolted. Breaker boxes
were stacked to make a vertical section with equipment frame around the breaker boxes. here were no bus
compartment barriers, just an open bus design. Ring silver-plating was applied to bolted connections.
AKD 5—AK 25, AK 50, AKT 50, AK 75, AK 100
Manufactured from 1960 until 1977, the aluminum bus had copper that was “flash-butt welded” to the
aluminum at bolted connections. During that time, AK-2A, 3A -25 / 50 / 50 / 75 / 100 (“A” signifies AKD-5
drawout) were produced. Breakers up to 2000A had primary finger clusters. 3000 & 4000A breakers had a
circular primary finger cluster arrangement in the switchgear compartment. Pull-lanyard drawout
mechanism in the switchgear on early designs was replaced by a single jackscrew mechanism and then
later replaced by a double jack-screw mechanism. Featured is a closed-door, drawout with inner house
breaker compartment, where door moves with the breaker as it is racked in or out. wo bus levels are
available with a ring bus used at 4000A. Particulars include: welded/riveted frame, bus compartment
barriers, line/load separation barriers on mains and ties, isolation barriers on transformer transitions, copper
runbacks on feeder breakers, ring silver-plating on copper, and aluminum bus un-plated (welded
connections). he switchgear is painted sand-gray (beige), with some instrument doors painted blue. AKR-
30/50 in 22"-wide sections were introduced in AKD-5 construction, early 70s. AK25s and AK50s were also
available as substructure kits for OEMs to build around customer gear.
Note: All legacy AK & AKR breakers have a draw out letter code “A”. EntelliGuard R Retrofill breakers for this
gear will have a catalog number beginning with R1 for AK replacements or R2 for AKR-30/50 replacements.
AKD 6—AKR 30/30H, AKR 50/50H/T50H, AKR 75/75H, AKR 100
AKD-6 was manufactured in Salisbury, NC from 1977 to 1981. Some AKD-5s, which were built in Salisbury
from 1975 until 1977, got name-plated as AKD-6. here is no “flash-butt” welded aluminum to copper.
Aluminum bus is tin-plated and bolted at shipping splits (but welded everywhere else). Copper bus design has
ring silver plating at bolted joints. AKR-75 / 100s were introduced during this time. Stab-and-finger
connections on 3200A and 4000A breakers were improvements, versus the round the primary disconnects
on the AKD-5. he 4000A breaker was also narrowed to same width and phase-phase spacing as the 3200A.
he AKD-6 uses inner-house drawout breaker compartments on the 800—2000A breaker compartments.
hey are painted ANSI 61 light gray and breakers have ECS or SS trip units.
AKD-6 should mark a shift away from all AK breakers and to AKR breakers. he AKR-30/50/50H/ 50 breakers
used in AKD6 have a shallow 1” steel front escutcheon are drawout letter code “A” i.e. AKR-4A-30 and will be
replaced by an EntelliGuard R with a catalog number beginning with R2. he AKR-30/50/50H/ 50/75/100
breakers sold to OEMs for their switchgear have a 5” deep plastic front escutcheon & spring loaded sliding
“picture frame”. hese are draw out letter code “B” i.e. AKR-4B-30 which will be replaced by an EntelliGuard R
with a catalog # beginning with R5 up to 2000A frame size and R6 for 3200 & 4000A frame sizes.

10
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
he AKR-75/100 breakers used in AKD-6 have a shallow 1” steel front escutcheon and vertical primary
fingers. hey are drawout letter code”C” i.e. AKR-4C-75 and will be replaced by EntelliGuard R with catalog
number beginning with R2
AKD 8—AKR 30/30H/30L, AKR 50/50H/T50H, AKR 75/75H, AKR 100, AKR125
AKD-8 was manufactured in Salisbury, NC from 1980 to 1984 and in Burlington, Iowa from 1984 to 1999. It
was mostly replaced by AKD-10 in 1999 to 2000 but was available thru 2015. Model 1 and 2 have extruded
vertical bus. Model 2 was introduced in 1983 to accommodate revised wire harness routing. Model 3 was
introduced in 1991, using a flat bar vertical bus. AKR breakers use MicroVersa rip 9, MV RMS9, EPIC, MV
Plus, MV PM, or EntelliGuard U trip units. Aluminum bus was removed from the design in 1996 in favor of
the standard tin-plated copper bus (silver plated optional).
he AKR-30/50/50H/ 50 breakers used in AKD8 have 5” deep plastic front escutcheon& spring loaded sliding
“picture frame”. hey are drawout letter code “D” i.e. AKR-7D-30. In AKD-8, most 800-2000A breakers are
“feeder” breakers with vertical lower stud & primary disconnect fingers clusters, but 800-2000A breakers
designated as “Main” breakers, have horizontal lower finger clusters, which is the same as “D” letter code
breakers sold to OEM’s. A lower stud rejection bracket differentiates between lower stud orientations.
EntelliGuard R breakers with a catalog number beginning with R3 replace an AKR-30/50/50H/ 50 breaker
with vertical lower stud & fingers. EntelliGuard R breakers with a catalog number beginning with R6 replace
an AKR-30/50/50H/ 50 breaker with horizontal lower stud & fingers.
AKR-75/100/125 circuit breakers used in AKD-8 switchgear have a 5” deep plastic front escutcheon & spring
loaded sliding “picture frame” similar to the small frame breakers. he positions DISC/ ES /CONN are shown
on the side of the front escutcheon by position of the sliding “picture frame”. he GE AKD-8 breakers have a
drawout letter code “D”. OEM versions are drawout letter code “B” and GE Switchboard versions are drawout
letter code “F”. “B” & “F” breakers only differed by appearance items. All Primary disconnect stabs are
vertically oriented. he AKR-125 is a 5000A breaker that had cooling fan. It was release in 1995. None of the
retrofill breakers utilize fans.
EntelliGuard R breakers with a catalog number beginning with R3 replace and AKR-75/100/125 breakers in
AKD-8 switchgear. EntelliGuard R breakers with a catalog number beginning with R6 replace and AKR-
75/100/125 breakers in OEM switchgear or switchboards or GE Switchboard which all utilize an OEM
substructure mounted on a shelf. he R6 breakers will require a different door with a “bump inward” as the
original compartment depth is 1.4” greater than AKD-8.
AKD 10—WPS 08, WPH 08, WPX 08, WPS 16, WPH 16, WPS 20, WPS 32, WPH 32 WPX 32,
WPS 40, WPX 40, WPS 50, WPX 50
AKD-10 was manufactured in Burlington, IA from 1999 thru 2015. he switchgear compartment sizes and
main & vertical bus arrangements are the same as AKD-8 Model 3. he compartments have pull-out rails.
AKD-10 uses WavePro * drawout-only style breakers. All breakers have 4 rollers which align with the
compartment rails. he secondary control wiring for all functions is connected thru either one or two 36
point secondary disconnects with gold plated contacts. Secondary control wiring terminates at fixed
standard locations on the 36 point disconnects. Each breaker has a pump style manual charging handle and
manual push OPEN and Push CLOSE buttons. he front escutcheon is 5” deep with a sliding picture frame,
but is wide enough so the trip unit and new style bell alarm are visible thru the front door of the switchgear.
EntelliGuard R breakers with a catalog number beginning with R7 will replace a WavePro breaker with a
catalog number beginning with WE or W1. EntelliGuard R breaker with a catalog number beginning with R8
will replace a WavePro breaker with a catalog number beginning with WS or W2. Note GE Switchboard
plants initially shipped “WS” style breakers and later shifted to “WE” style breakers to be consistent with GE
Switchgear from Burlington, Iowa. he 5000A breaker had cooling fans. None of the retrofill breakers utilize
fans.

11
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
AKD 8—Retrofill Breaker
AKD 8 Breaker Models
he Table 7 depicts the key differences between Model 1 & 2 AKD8 Retrofill breakers (800-1600A).
Note: All features of Model 2 (800-1600A) Retrofill breakers are incorporated in all the 2000A breakers.
able 7. AKD-8—Model 1 & 2 Retrofill Breakers
Feature Model 1 Retrofill Breaker (800 1600A) Model 2 Retrofill Breaker*
(800 1600A & 2000A) – except AKR 30S
Secondary
Disc Bullet
mounting
Secondary disconnect bullets mounted
on spring loaded bracket assembly
Secondary disconnect bullets mounted directly
on metal bracket
Kirklock
Actuator
Not provided –Kirklock Mechanism (to
achieve kirklock feature through
existing compartment installed kirklock
lever) is not present
AKD-8 Compartment Kirklock can lock out the
Model 2
*EntelliGuard R Retrofill breakers for AKR-30S have not been redesigned with model 2 features.

12
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Table 7A. AKD 8—Retrofill Breakers (AKR75/75H,AKR100,AKR125)
Feature Retrofill Breaker (3200 5000A)
Secondary
Disc Bullet
mounting
Secondary disconnect bullets
mounted directly on metal bracket
as on the legacy AKR breakers
Kirk lock
Actuator/
Compartment
Release lever
AKD-8 compartment Kirk lock can
lockout all 3200-5000A EntelliGuard
R types
Compartment
Release Lever
Kirk lock
I
nterface

13
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
AKD 8—Mechanical Drawings
he following engineering or assembly drawings describe the layout and dimensions of the AKD-8 Retrofill
breaker (Figure 2, Figure 3, Figure 4, Figure 5).
Figure 2
.
AKD
8
—
AKR30/30H
—
Retrofill
Breaker, Dimensioning
Figure 3
.
AKD
8
—
AKR30S
—
Retrofill
Breaker, Dimensioning

14
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Figure 4
.
AKD
8
—
AKR50/50H/30L
—
Retrofill
Breaker, Dimensioning
(Model 1)
R3 type
Figure 5
.
AKD
8
—
AKR50/50H/30L
/AKRT
50H
—
Retrofill
Breaker, Dimensioning
(Model
2
)
R3 type
R6
type

15
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Figure 5A
.
AKD
8
—
AKR75/75H/AKR
100
—
Retrofill
Breaker, Dimensioning
Figure 5B
.
AKD
8
—
AKR
125
—
Retrofill
Breaker, Dimensioning

16
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
AKD 8 Compartment
Interior View
he figures (Figure 6, 7, 8 & 9) below present a ypical AKR-30/50/ 50 AKD-8 compartment.
Figure 6. AKD 8—(new) Empty Compartment, View 1
Figure 7.
AKD
8
—
(new)
Empty Compartment, View
2,
Racks/Rails Extended
Figure 8 is a photo of the interior of the AKD-8. he photos point out the shutter assembly and telescopic rails
in the AKD-8.
F
igur
e 8.
AKD
8
—
Compartment
Assemblies
Position Switch
Neutral
Disconnect

17
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Interior Components
Figure 9 points out the major components of an AKD-8 compartme t.
Figure
9.
AKD
8
—
Circuit Breaker Compartment (22
Inch) for AKR
30/50/T50 Breakers
Interior View
he figures Figure 6A, 7A, 8A & 9A below present a ypical 30” AKR-75/100 AKD-8 compartment.
(AKR-125 is similar but 38” wide)
Figure 6A. AKD 8—Empty Compartment, View 1
Figure 7
A
.
AKD
8
—
Empty Compartment, View
2,
Drawout
Tray
Extended

18
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Figure 8A is a photo of the interior of the AKD-8. he photos point out the shutter assembly and Draw out
tray assembly in the AKD-8.
F
igure 8
A
.
AKD
8
—
Compartment Assemblies
Interior Components
Figure 9A points out the major components of an AKD-8 compartment.
Figure
9
A
.
AKD
8
—
Circuit Breaker Compartmen
t
for AKR
75/75H/100/125
Breakers
Draw out Tray
Assembly
Locating Pins

1
EntelliGuard R Circuit Breaker Retrofill AKD-8 Installation Manual DEH4154 R05
Unpack CB
•Turn off all power to switchgear. Tagout
and lockout main source, up stream or main
breaker.
•Failure to comply with these instructions
will result in death or serious injury from
severe burns caused by arc flashing that has
exceedingly high temperatures.
•
Always wear personal protection equipment
according to OSHA standards and
appropriate to the severity of potential
burns.
•
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
Falling Object
•Do not walk or remain under any heavy assembly while
hoisted above head as the chains securing the
assembly may give way
•
Ensure lifting equipment has capability for device being lifted.
•
Wear hard hat, gloves, and safety shoes.
•Failure to comply with these instructions could result in serious injury.
PRODUCT DAMAGE
•Ensure circuit breaker and its accessories
are always used within their designated
ratings.
•Do not allow the circuit breaker to hit a
hard surface while handling.
•
Do not drag or slide the circuit breaker
across a hard or rough surface
•
A factory-installed rejection feature prevents mismatching circuit breakers and cassettes/
substructure, preventing the insertion of a circuit breaker with a lower rating into a higher rated
cassette/substructure, or the insertion of a higher rated circuit breaker into a lower rated
cassette/substructure.
By following the procedures below, you should be able to install the breaker with minimum effort
and time.
This manual suits for next models
10
Table of contents
Other GE Circuit Breaker manuals

GE
GE Power Break II User manual

GE
GE Shunt Trip User manual

GE
GE Power Break II SPUV012DC User manual

GE
GE AM-4.16-250-6 User manual

GE
GE AK-15 User manual

GE
GE Spectra Series AMC6FGB User manual

GE
GE PVDB-28kV User manual

GE
GE AK-50 Series Technical specifications

GE
GE PowerVac User manual

GE
GE AK-2-15 User manual

GE
GE AKR Series Configuration guide

GE
GE A Series Pro-Stock THQB User manual

GE
GE AM-2.4/4.16-100/150- 3 User manual

GE
GE AKR-30 Series User manual

GE
GE WavePro LVPCB User guide

GE
GE EntelliGuard G User guide

GE
GE AKR User manual

GE
GE S2500 User manual

GE
GE AK-1-15 Series User manual

GE
GE AKR-30S User manual