GEM R90 User manual

GEMÜ R90
Metal disco check valve
Operating instructions
EN
further information
webcode: GW-R90

All rights including copyrights or industrial property rights are expressly reserved.
Keep the document for future reference.
© GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
08.09.2020
www.gemu-group.com2 / 21GEMÜ R90

Contents
1 General information .................................................. 4
1.1 Information ......................................................... 4
1.2 Symbols used ..................................................... 4
1.3 Definition of terms ............................................. 4
1.4 Warning notes .................................................... 4
2 Safety information .................................................... 5
3.1 Construction ....................................................... 5
3.2 Description ......................................................... 5
3.3 Function .............................................................. 5
3.4 Product label ...................................................... 6
4 Correct use ............................................................... 6
5 Order data ................................................................. 7
5.1 Order codes ........................................................ 7
5.2 Order example .................................................... 8
6 Technical data .......................................................... 9
6.1 Medium ............................................................... 9
6.2 Temperature ....................................................... 9
6.3 Pressure .............................................................. 9
6.4 Product compliance ........................................... 12
6.5 Mechanical data ................................................. 12
7 Dimensions ............................................................... 13
8 Manufacturer's information ....................................... 15
8.1 Delivery ............................................................... 15
8.2 Packaging ........................................................... 15
8.3 Transport ............................................................ 15
8.4 Storage ............................................................... 15
9 Installation in piping .................................................. 15
9.1 Preparing for installation ................................... 15
9.2 Installation .......................................................... 16
10 Commissioning ......................................................... 17
11 Troubleshooting ........................................................ 18
12 Inspection and maintenance ...................................... 19
12.1 Spare parts ......................................................... 19
13 Removal from piping ................................................. 19
14 Disposal .................................................................... 19
15 Returns ..................................................................... 19
16 Declaration of conformity according to 2014/68/EU
(Pressure Equipment Directive) ................................. 20
GEMÜ R90www.gemu-group.com 3 / 21

www.gemu-group.com4 / 21GEMÜ R90
1 General information
1 General information
1.1 Information
– The descriptions and instructions apply to the stand-
ard versions. For special versions not described in this
document the basic information contained herein ap-
plies in combination with any additional special docu-
mentation.
– Correct installation, operation, maintenance and repair
work ensure faultless operation of the product.
– Should there be any doubts or misunderstandings, the
German version is the authoritative document.
– Contact us at the address on the last page for staff
training information.
1.2 Symbols used
The following symbols are used in this document:
Symbol Meaning
Tasks to be performed
Response(s) to tasks
– Lists
1.3 Definition of terms
Working medium
The medium that flows through the GEMÜ product.
1.4 Warning notes
Wherever possible, warning notes are organised according to
the following scheme:
SIGNAL WORD
Type and source of the danger
Possible
symbol for the
specific
danger
Possible consequences of non-observance.
Measures for avoiding danger.
Warning notes are always marked with a signal word and
sometimes also with a symbol for the specific danger.
The following signal words and danger levels are used:
DANGER
Imminent danger!
▶Non-observance can cause death or
severe injury.
WARNING
Potentially dangerous situation!
▶Non-observance can cause death or
severe injury.
CAUTION
Potentially dangerous situation!
▶Non-observance can cause moderate
to light injury.
NOTICE
Potentially dangerous situation!
▶Non-observance can cause damage to
property.
The following symbols for the specific dangers can be used
within a warning note:
Symbol Meaning
Danger of explosion
Danger - bodily injury!
Corrosive chemicals!
Hot plant components!
Replacement of spare parts

www.gemu-group.com 5 / 21 GEMÜ R90
2 Safety information
The safety information in this document refers only to an in-
dividual product. Potentially dangerous conditions can arise
in combination with other plant components, which need to
be considered on the basis of a risk analysis. The operator is
responsible for the production of the risk analysis and for
compliance with the resulting precautionary measures and
regional safety regulations.
The document contains fundamental safety information that
must be observed during commissioning, operation and
maintenance. Non-compliance with these instructions may
cause:
– Personal hazard due to electrical, mechanical and
chemical effects.
– Hazard to nearby equipment.
– Failure of important functions.
– Hazard to the environment due to the leakage of dan-
gerous materials.
The safety information does not take into account:
– Unexpected incidents and events, which may occur
during installation, operation and maintenance.
– Local safety regulations which must be adhered to by
the operator and by any additional installation person-
nel.
Prior to commissioning:
1. Transport and store the product correctly.
2. Do not paint the bolts and plastic parts of the product.
3. Carry out installation and commissioning using trained
personnel.
4. Provide adequate training for installation and operating
personnel.
5. Ensure that the contents of the document have been fully
understood by the responsible personnel.
6. Define the areas of responsibility.
7. Observe the safety data sheets.
8. Observe the safety regulations for the media used.
During operation:
9. Keep this document available at the place of use.
10. Observe the safety information.
11. Operate the product in accordance with this document.
12. Operate the product in accordance with the specifica-
tions.
13. Maintain the product correctly.
14. Do not carry out any maintenance work and repairs not
described in this document without consulting the manu-
facturer first.
In cases of uncertainty:
15. Consult the nearest GEMÜ sales office.
3 Product description
3.1 Construction
1
2
3
4
Item Name Materials
1 Body 1.4408, CC333G, 1.0619, 1.4469
(super duplex)
2 Disc 1.4408, CC333G, 1.0619, 1.4469
(super duplex)
3 Spring 1.4571, C4 (Hastelloy)
4 Spring cross 1.4408, CC333G, 1.0619, 1.4469
(super duplex)
3.2 Description
The GEMÜ R90 is a metal disco check valve with flange con-
nection and standardized length to DIN EN 558. The valve
body, disc and seal are available in various materials. In the
version with metallic seal, the GEMÜ R90 valve can be used
at high temperatures up to 400 °C.
3.3 Function
The flow of fluid causes disc 2 in the check valve to open.
Check valves need a low opening pressure. The resulting
opening force moves the disc 2 against the spring 3 by over-
coming the the weight force of the disc 2 and the spring force
of the spring 3 so that the medium is released.
3 Product description

www.gemu-group.com6 / 21GEMÜ R90
4 Correct use
3.4 Product label
Fritz-Müller-Str. 6-8
D-74653 Ingelfingen
R90323354406
88716070
PS 16 bar
12000-3
DN50
Tmax. 120° C
S.Nr.: 0028
1002877963 Pos. 20
PN 6-40
02/20 0035
Serial number Year of manufacture
Device-specific data
Item number
Design in accordance with order data
Flow direction
Order specific data
4 Correct use
DANGER
Danger of explosion
▶Risk of death or severe injury.
●Do not use the product in potentially
explosive zones.
WARNING
Improper use of the product
▶Risk of severe injury or death.
▶Manufacturer liability and guarantee will be void.
●Only use the product in accordance with the operating
conditions specified in the contract documentation and
in this document.
The product is designed for installation in piping systems
and for controlling a working medium.
The product is not intended for use in potentially explosive
areas.

5 Order data
The order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
Order codes
1 Type Code
Disco check valve, metal R90
2 DN Code
DN 15 15
DN 20 20
DN 25 25
DN 32 32
DN 40 40
DN 50 50
DN 65 65
DN 80 80
DN 100 100
DN 125 125
DN 150 150
DN 200 200
DN 250 250
DN 300 300
3 Operating pressure Code
16 bar 3
25 bar 5
40 bar 6
4 Connection type Code
PN 6 / flange EN 1092, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
1
PN 10 / flange EN 1092, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
2
PN 16 / flange EN 1092, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
3
PN 25 / flange EN 1092, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
5
PN 40 / flange EN 1092, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
6
ANSI B16.5, Class 150, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
D
ANSI B16.5, Class 300, face-to-face dimension
FTF EN 558-1 series 49 (R90), series 16 (R91)
M
5 Body material Code
1.4408 / ASTM A351 / CF8M 4
1.0619 / ASTM A216 / WCB 5
1.4469, SUPERDUPLEX / ASTM A890 Grade 5A D
CC333G / 2.0975 / C954 G
6 Shut-off element material Code
1.4408 / ASTM A351 / CF8M 4
1.4469, SUPERDUPLEX / ASTM A890 Grade 5A D
CC333G / 2.0975 / C954 G
7 Guide element material Code
1.4408 / ASTM A351 / CF8M 4
1.4469, SUPERDUPLEX / ASTM A890 Grade 5A D
CC333G / 2.0975 / C954 G
8 Shut-off seal material Code
Steel 0
EPDM (DVGW water approval, FDA compliant) 2
PTFE 5
EPDM E
NBR N
FPM (FKM) V
9 Spring material Code
1.4571 6
HASTELLOY C-4 / 2.4610 7
10 Special version Code
Without
ATEX version X
11 Type of design Code
Without
Media wetted area cleaned to ensure suitability for
paint applications, parts sealed in plastic bag
0101
Valve free of oil and grease, media wetted area
cleaned and packed in PE bag
0107
5 Order data
www.gemu-group.com 7 / 21 GEMÜ R90

Order example
Order option Code Description
1 Type R90 Disco check valve, metal
2 DN 32 DN 32
3 Operating pressure 3 16 bar
4 Connection type 3 PN 16 / flange EN 1092, face-to-face dimension FTF EN 558-1 series
49 (R90), series 16 (R91)
5 Body material 5 1.0619 / ASTM A216 / WCB
6 Shut-off element material 4 1.4408 / ASTM A351 / CF8M
7 Guide element material 4 1.4408 / ASTM A351 / CF8M
8 Shut-off seal material 0 Steel
9 Spring material 6 1.4571
10 Special version Without
11 Type of design Without
5 Order data
www.gemu-group.com8 / 21GEMÜ R90

6 Technical data
6.1 Medium
Working medium: Corrosive, inert, gaseous and liquid media which have no negative impact on the physical and
chemical properties of the body, disc and seal material.
6.2 Temperature
Media temperature: Seal material:
Steel (code 0): -196 to 400 °C (design 1)
NBR (code N): -30 to 90 °C
EPDM (code 2, E): -45 to 120 °C
FPM (code V): -15 to 200 °C
PTFE (code 5): -200 to 250 °C
For temperatures above 300 °C a compression spring made of Hastelloy C4 (code 7) is required.
Ambient temperature: -20 to 95 °C
6.3 Pressure
Operating pressure: max. 40 bar
Pressure loss:
1
10
100
1000
DN 15
1
DN 40
DN 32
DN 20
DN 25
DN 100
DN 80
DN 50
DN 65
DN 125
DN 300
DN 250
DN 150
DN 200
0,1 0,2 0,3 0,4 0,9
0,8
0,7
0,60,5
Pressure loss [bar]
Volumetric flow [m³/h]
GEMÜ R90www.gemu-group.com 9 / 21
6 Technical data

Disc opening pressure: DN Piping
without spring
15 ~ 20 ~ 16 ~ 24 ~ 4
20 ~ 20 ~ 15 ~ 25 ~ 5
25 ~ 20 ~ 15 ~ 25 ~ 5
32 ~ 20 ~ 14 ~ 26 ~ 6
40 ~ 20 ~ 13 ~ 27 ~ 7
50 ~ 20 ~ 12 ~ 28 ~ 8
65 ~ 20 ~ 11 ~ 29 ~ 9
80 ~ 20 ~ 10 ~ 30 ~ 10
100 ~ 20 ~ 7 ~ 33 ~ 13
125 ~ 30 ~ 46 ~ 14 ~ 16
150 ~ 30 ~ 47 ~ 13 ~ 17
200 ~ 30 ~ 51 ~ 9 ~ 21
250 ~ 40 ~ 64 ~ 16 ~ 24
300 ~ 40 ~ 68 ~ 12 ~ 38
Pressures in mbar
Leakage rate: A acc. to EN 12266-1 (with plastic seal)
G acc. to EN 12266-1 (metallic sealing)
Pressure/temperature
correlation:
DN Material 1.4408 (code 4)
Temperature [°C]
20 100 150 200 250 300
15 40 40 40 40 40 40
20 40 40 40 40 40 40
25 40 40 40 40 40 40
32 40 40 40 40 40 40
40 40 40 40 40 40 40
50 40 40 40 40 40 40
65 40 40 40 40 40 40
80 40 40 40 40 40 40
100 40 40 40 40 40 40
125 40 36 32.7 29.7 27.5 25.6
150 40 33.1 30.2 27.3 25.3 23.2
200 40 29 26.5 23.9 22.2 20.7
250 40 28.9 26.1 23.8 21.8 20.5
300 40 28.1 25.7 23.1 21.5 20
Pressures in bar
www.gemu-group.com10 / 21GEMÜ R90
6 Technical data

Pressure/temperature
correlation:
DN Material 1.0619 (code 5)
Temperature [°C]
20 100 150 200 250 300
15 40 40 40 40 40 40
20 40 40 40 40 40 40
25 40 40 40 40 40 40
32 40 40 40 40 40 40
40 40 40 40 40 40 40
50 40 40 40 40 40 40
65 40 40 40 40 40 40
80 40 40 40 40 40 40
100 40 40 40 40 40 40
125 40 36 32.7 29.7 27.5 25.6
150 40 33.1 30.2 27.3 25.3 23.2
200 40 29 26.5 23.9 22.2 20.7
250 40 28.9 26.1 23.8 21.8 20.5
300 40 28.8 26.5 23.8 22.1 20.6
Pressures in bar
Kv values: DN Kv values
15 4
20 7
25 10
32 17
40 24
50 37
65 61
80 74
100 115
125 201
150 286
200 553
250 643
300 867
Kv values in m³/h
If disc springs are used, the Kv value is reduced.
GEMÜ R90www.gemu-group.com 11 / 21
6 Technical data

6.4 Product compliance
Pressure Equipment
Directive:
2014/68/EU
Food: FDA*
BfR XXI cat. 4*
Drinking water: KTW*
DVGW*
* only with seal material EPDM
Explosion protection: ATEX (2014/34/EU)
6.5 Mechanical data
Weight: DN Version
12345
20 0.19 0.19 0.2 0.2 0.19
25 0.31 0.31 0.32 0.32 0.31
32 0.5 0.5 0.52 0.51 0.5
40 0.6 0.61 0.62 0.62 0.61
50 1.02 1.03 1.06 1.05 1.03
65 1.64 1.66 1.71 1.69 1.66
80 2.45 2.48 2.54 2.52 2.48
100 3.83 3.89 3.98 3.95 3.88
125 - - 8.44 8.37 8.23
150 - - 12.37 12.26 12.06
200 - - 23.94 23.74 23.35
250 - - 39.21 38.88 38.23
300 - - 58.26 57.81 56.81
Weights in kg
www.gemu-group.com12 / 21GEMÜ R90
6 Technical data

7 Dimensions
DN 15 to 100
DN ø d ø D F L
15 15 43 56 16
20 19 53 69 19
25 25 63 76 22
32 32 75 87 28
40 38 80 101 31.5
50 47 95 114 40
65 63 115 136 46
80 77 131 154 50
100 97,5 150 178 60
Dimensions in mm
DN 125 to 300
DN
Connection type
PN 10 (code 2), PN 16 (code 3) PN 25 (code 5) PN 40
(code 6)
ANSI
(code D)
L DN
C D R C R D D
125 194 194 - 194 - 194 194 90 118.5
150 220 220 - 220 - 220 220 106 141
200 275 280 11 286 30 294 280 140 190
250 331 340 11 344 33 356 340 145 229
GEMÜ R90www.gemu-group.com 13 / 21
7 Dimensions

DN
Connection type
PN 10 (code 2), PN 16 (code 3) PN 25 (code 5) PN 40
(code 6)
ANSI
(code D)
L DN
C D R C R D D
300 380 386 11 404 33 421 404 160 280
Dimensions in mm
www.gemu-group.com14 / 21GEMÜ R90
7 Dimensions

www.gemu-group.com 15 / 21 GEMÜ R90
8 Manufacturer's information
8.1 Delivery
●Check that all parts are present and check for any dam-
age immediately upon receipt.
The product's performance is tested at the factory. The
scope of delivery is apparent from the dispatch documents
and the design from the order number.
8.2 Packaging
The product is packaged in a cardboard box which can be re-
cycled as paper.
8.3 Transport
1. Only transport the product by suitable means. Do not
drop. Handle carefully.
2. After the installation dispose of transport packaging ma-
terial according to relevant local or national disposal reg-
ulations / environmental protection laws.
8.4 Storage
1. Store the product free from dust and moisture in its ori-
ginal packaging.
2. Avoid UV rays and direct sunlight.
3. Do not exceed the maximum storage temperature (see
chapter "Technical data").
4. Do not store solvents, chemicals, acids, fuels or similar
fluids in the same room as GEMÜ products and their
spare parts.
9 Installation in piping
9.1 Preparing for installation
DANGER
Danger - bodily injury!
▶Risk of severe injury.
●Depressurize the plant before per-
forming any work on the product.
●Observe correct handling procedures.
WARNING
The equipment is subject to pressure!
▶Risk of severe injury or death.
●Depressurize the plant.
●Completely drain the plant.
WARNING
Corrosive chemicals!
▶Risk of caustic burns.
●Wear suitable protective gear.
●Completely drain the plant.
CAUTION
Hot plant components!
▶Risk of burns.
●Only work on plant that has cooled
down.
CAUTION
Exceeding the maximum permissible pressure.
▶Damage to the product.
●Provide precautionary measures against exceeding the
maximum permitted pressures caused by pressure
surges (water hammer).
CAUTION
Use as step.
▶Damage to the product.
▶Risk of slipping-off.
●Choose the installation location so that the product can-
not be used as a foothold.
●Do not use the product as a step or a foothold.
NOTICE
Suitability of the product!
▶The product must be appropriate for the piping system
operating conditions (medium, medium concentration,
temperature and pressure) and the prevailing ambient
conditions.
9 Installation in piping

www.gemu-group.com16 / 21GEMÜ R90
9 Installation in piping
NOTICE
Tools
▶The tools required for installation and assembly are not
included in the scope of delivery.
●Use appropriate, functional and safe tools.
1. Ensure the product is suitable for the relevant application.
2. Check the technical data of the product and the materials.
3. Keep appropriate tools ready.
4. Wear appropriate protective gear, as specified in the plant
operator's guidelines.
5. Observe appropriate regulations for connections.
6. Have installation work carried out by trained personnel.
7. Shut off plant or plant component.
8. Secure plant or plant component against recommission-
ing.
9. Depressurize the plant or plant component.
10. Completely drain the plant (or plant component) and let it
cool down until the temperature is below the media va-
porization temperature and cannot cause scalding.
11. Correctly decontaminate, rinse and ventilate the plant or
plant component.
12. Lay piping so that the product is protected against trans-
verse and bending forces, and also from vibrations and
tension.
13. Only install the product between matching aligned pipes
(see chapters below).
14. Pay attention to the installation position: horizontal or
vertical.
15. Pay attention to the direction of the working medium: po-
sitioned in-line with flow direction
9.2 Installation
1. Carry out preparations for installation (see chapter "Pre-
paring for installation").
2. Inspect check valve and suitable gaskets for possible
damage before installation. Check the check valve for
freedom of movement. Damaged parts must not be in-
stalled.
3. Make sure that you only install check valves whose pres-
sure class, chemical resistance, connection and dimen-
sions are appropriate for the conditions of use.
4. Provide a straight pipe section of at least 5 times the
nominal diameter upstream and downstream of the check
valve.
5 x DN
5 x DN5 x DN
5. Use flanges to EN1092-1 or EN1092-2 for metal piping.
6. Do not mount directly on a pump flange.
7. Avoid pulsating flow conditions and water hammer.
8. If the medium flows horizontally through the check valve,
the eye bolt must point upwards.
9. Guide the check valve between the flanges with the eye
bolt. Centring is performed with the outside diameter of
the body against the inside of the flange bolts.
10. Observe the flow direction of the check valve.
11. Tighten flange bolts to the appropriate torque in a diag-
onal pattern.
Flange bolt torques
Thread M12 M16 M 20 M24 M27
Torque [Nm] 20 35 60 100 165

www.gemu-group.com 17 / 21 GEMÜ R90
10 Commissioning
WARNING
Corrosive chemicals!
▶Risk of caustic burns.
●Wear suitable protective gear.
●Completely drain the plant.
CAUTION
Leakage
▶Emission of dangerous materials.
●Provide precautionary measures against exceeding the
maximum permitted pressures caused by pressure
surges (water hammer).
1. Check the tightness and the function of the product
(close and reopen the product).
2. Flush the piping system of new plant and following repair
work (the product must be fully open).
ðHarmful foreign matter has been removed.
ðThe product is ready for use.
3. Commission the product.
10 Commissioning

www.gemu-group.com18 / 21GEMÜ R90
11 Troubleshooting
11 Troubleshooting
Error Possible cause Troubleshooting
The product doesn't open or doesn't
open fully
Foreign matter in the product Remove and clean the product
Faulty product Replace product
The product doesn't close or doesn't
close fully
Seal or disc faulty Send the product to GEMÜ for repair
Connection between product and piping
is leaking
Incorrect installation Check installation of product in piping
Gasket between flange and valve body
faulty
Send the product to GEMÜ for repair
Screws not tightened Tighten screws
The product is leaking The product is faulty Check the product for potential damage,
replace if necessary
O-ring of disc is faulty Send the product to GEMÜ for repair

www.gemu-group.com 19 / 21 GEMÜ R90
12 Inspection and maintenance
WARNING
The equipment is subject to pressure!
▶Risk of severe injury or death.
●Depressurize the plant.
●Completely drain the plant.
CAUTION
Hot plant components!
▶Risk of burns.
●Only work on plant that has cooled
down.
CAUTION
●Servicing and maintenance work must only be performed
by trained personnel.
●GEMÜ shall assume no liability whatsoever for damage
caused by improper handling or third-party actions.
●In case of doubt, contact GEMÜ prior to commissioning.
The operator must carry out regular visual examination of the
GEMÜ products depending on the operating conditions and
the potential danger in order to prevent leakage and damage.
The product also must be disassembled and checked for
wear in the corresponding intervals.
1. Have servicing and maintenance work performed by
trained personnel.
2. Wear appropriate protective gear as specified in plant op-
erator's guidelines.
3. Shut off plant or plant component.
4. Secure plant or plant component against recommission-
ing.
5. Depressurize the plant or plant component.
6. Actuate GEMÜ products which are always in the same
position four times a year.
12.1 Spare parts
The product can only be repaired at GEMÜ. The replacement
of spare parts may only be carried out by GEMÜ. If this pro-
cedure is not observed, the purchaser's guarantee rights and
the manufacturer's legal liability cease. This can also lead to
a loss of all rights to claim damages.
CAUTION
Replacement of spare parts
▶Damage to the GEMÜ product.
●Do not dismantle the product but send
it completely to GEMÜ.
1. Remove the product completely from the plant using ap-
propriate tools.
2. Send the product with return declaration to GEMÜ.
13 Removal from piping
NOTICE
▶If defective, the entire product must be replaced.
1. Observe (see “Safety information“, page5) the safety in-
formation.
2. Undo the flange screws.
3. Pull out the check valve between the flanges.
4. Insert and centre the new check valve with new seals.
5. Tighten the flange screws.
14 Disposal
1. Pay attention to adhered residual material and gas diffu-
sion from penetrated media.
2. Dispose of all parts in accordance with the disposal regu-
lations/environmental protection laws.
15 Returns
Legal regulations for the protection of the environment and
personnel require that the completed and signed return deliv-
ery note is included with the dispatch documents. Returned
goods can be processed only when this note is completed. If
no return delivery note is included with the product, GEMÜ
cannot process credits or repair work but will dispose of the
goods at the operator's expense.
1. Clean the product.
2. Request a return delivery note from GEMÜ.
3. Complete the return delivery note.
4. Send the product with a completed return delivery note to
GEMÜ.
15 Returns

16 Declaration of conformity according to 2014/68/EU (Pressure Equipment Directive)
EU Declaration of Conformity
in accordance with 2014/68/EU (Pressure Equipment Directive)
We, GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the product listed below complies with the safety requirements of the Pressure Equipment Directive 2014/68/EU.
Description of the pressure equipment: GEMÜ R90
Notified body: TÜV Rheinland Industrie Service GmbH
Number: 0035
Certificate no.: 01 202 926/Q-02 0036
Conformity assessment procedure: Module H
Technical standards used (in parts): AD2000-leaflet. EN 16668
Note for products with a nominal size ≤ DN 25:
The products are developed and produced according to GEMÜ process instructions and quality standards which comply with
the requirements of ISO 9001 and ISO 14001.
According to Article 4, Paragraph 3 of the Pressure Equipment Directive 2014/68/EU these products must not be identified by
a CE-label.
2020-07-31
Joachim Brien
Head of Technical Department
www.gemu-group.com20 / 21GEMÜ R90