Mixing valves
Three-way mixing valve wiTh bonneT
r298
ISO
14001
0032A/3
OHSAS
18001
0064L/1
ISO
9001
0006/7
F.C.F.O. 34
0,5
1
2
1000
800
600
500
400
300
200
100
Q [l/h]
∆p [mm H2O]
80
90
70
60
50
40
30
20
10
10
20
30
40
50
60
70
80
90
100
200
300
400
500
600
700
800
900
1000
Opening
Shutter
Kv
(direct + by-pass)
Primary side
ow rate Qp
By-pass
ow rate Qbp
F.C. 3,25 0 % 100 %
0,5 mm 3,48 11 % 89 %
1 mm 3,79 18 % 82 %
2 mm 3,78 29 % 71 %
3 mm 3,12 44 % 56 %
4 mm 2,35 74 % 26 %
F.O. 1,78 100 % 0 %
Table 1
Operation
R298 + handwheel for manual operation
The three-way R298 mixing valve is equipped with a handwheel to allow for
manual operation, which are carried out via a simple clockwise rotation for
the valve opening and anticlockwise for closure.
Total opening of the bonnet, and therefore of the primary side supply, is
obtained by screwing down the handwheel, while unscrewing it fully frees
the thread for the drive motor connection.
bypass Direct
SYSTEM SIDE
BOILER ROOM
SIDE
SYSTEM SIDE
BOILER ROOM
SIDE
clockwise
rotation
anticlockwise
rotation
SYSTEM SIDE
BOILER ROOM
SIDE
SYSTEM SIDE
BOILER ROOM
SIDE
clockwise
rotation
R298 + K281 actuator for automatic operation
The handwheel can be replaced with a K281 actuator for automatic mixing
adjustment, in combination with electronic thermoregulation. The K281
actuator is mounted manually, by screwing the brass ring nut in a clockwise
direction until it stops. This does not require the use of any tools.
bypass Direct
SYSTEM SIDE
BOILER ROOM
SIDE
SYSTEM SIDE
BOILER ROOM
SIDE
SYSTEM SIDE
BOILER ROOM
SIDE
SYSTEM SIDE
BOILER ROOM
SIDE
Description
The R298 mixing valve allows for the interception and mixing of heating uid
in radiant heating and cooling systems for oors or ceilings and in medium-
size radiator heating systems that require precise control of water delivery
temperature. The R298 valve is equipped with a handwheel for manual
operation, or alternatively, it can be coupled to a K274 actuator for automatic
control.
Versions and product codes
Product code Connections Actuator connection Center distance [mm]
R298Y001 1 1/2” M x 1 1/2” F M28 x 1,5 mm
120
R298Y027 1 1/2” M x 1 1/2” F M30 x 1,5 mm
Completion codes
• Actuators K281 or K282
Accessories
• P19Y001: ring nut M30x1,5 mm for adapting valve R298 M28x1,5 mm
threading.
• P19Y002: ring nut M28x1,5 mm for adapting valve R298 M30x1,5 mm
threading.
Technical data
• Heating uid: water for air-conditioning systems
• Max. working temperature: 90 °C
• Max. working pressure: 10 bar
• Maximum dierential pressure: 1,2 bar
• Center distance: 120 mm
• Connections: 1 1/2”at seat
• Mixing: by bonnet DN20, which is normally closed on the primary side
Materials
• Body, bonnet and nut in brass CW617N - UNI EN12165
• EPDM sealing rings
Losses of pressure
In Table 1, values in Kv and mixing percentage ratios (between the by-pass
"QBP" ow rate and the primary side "Qp") corresponding to the various
opening positions are displayed.
SYSTEM SIDE
BOILER ROOM
SIDE
Qp
Qbp
R298