SATEL CA-64 E 3
2. Installation and start-up
All connections should only be made when power supply of the alarm
system is disconnected.
1. Fasten the expander board in its housing.
2. Using the DIP-switches, set the suitable expander address and define how it is to
be identified.
3. Using cables, connect the CLK, DTA and COM terminals to the corresponding
terminals of the control panel communication bus.
4. Connect the cables of housing tamper contact to the TMP and COM terminals (or
short the TMP terminal to the COM terminal).
5. Connect the detector leads (for connection description refer to the alarm control
panel installer manual).
6. Connect the module power supply cables to the +12V and COM terminals. Supply
may be provided from the control panel mainboard, from an additional power
supply unit or from an expander with power supply (see: installer manual for alarm
control panel).
7. Turn on power supply of the alarm system.
8. Start the identification function in the control panel. When the identification is
completed, the zones will be assigned respective numbers in the alarm system
(zone numeration rules are described in the alarm control panel manual).
3. Specifications
Supply voltage ......................................................................................... 12 V DC ±15%
Number of programmable zones ................................................................................... 8
Current consumption, standby...............................................................................70 mA
Current consumption, maximum............................................................................70 mA
Dimensions of electronics board .................................................................. 57 x 80 mm
Environmental class according to EN50130-5............................................................... II
Operating temperature range ................................................................. -10 °C…+55 °C
Weight....................................................................................................................... 47 g
The latest EC declaration of conformity and product approval certificates
are available for downloading on website www.satel.pl