DIP SWITCH SETTINGS
REQUEST TO EXIT PERIOD – The Request to Exit (REX) time is selectable for 1, 15, 20, or 30 seconds. The REX time is the
period of time the lock will remain “bypassed”, after a remote normally open contact switch is momentarily activated. When activated
with an access control system, the REX time cycle begins immediately after the access control open time expires. The ExitCheck™
will automatically relock if the door is opened, and then closed during the REX time cycle.
TRIGGER TYPE – The trigger type is selectable for “REMOTE” or “INTERNAL”. Selecting INTERNAL mode uses the internal trigger
sensor to activate the Exit Delay cycle. Selecting REMOTE mode disables the internal trigger. Activation of the Exit Delay cycle is
triggered by an external exit device equipped with a normally open contact switch.
POWER-UP OPTION
*
– The power-up option, indicating the state of the ExitCheck
TM
upon restoration of system power, is selectable
to “UNLOCKED” or “LOCKED”. In the LOCKED mode, the ExitCheck
TM
will attempt to reset to secure mode. In the UNLOCKED
mode, the ExitCheck
TM
will remain unlocked and the digital display will indicate two horizontal bars “--“. Turning the reset switch
momentarily to the reset position will relock and rearm the door. This feature enables the ExitCheck
TM
to comply with code
requirements in jurisdictions that require manual reset/relock upon loss and restoration of system power.
ALARM TYPE – The alarm type is selectable to “TONE ONLY” or “VOICE”. When secure, the ExitCheck
TM
digital display will
indicate a 15 second delay time. Upon activation of the irreversible Exit Delay cycle, the digital display begins counting down to zero.
In VOICE mode, the countdown will be accompanied by a warning beeping tone and verbal exit instructions. When the digital display
indicates zero, the ExitCheck
TM
releases. The speaker output changes to a continuous warning tone and the verbal instruction
announces “Exit Now”. In TONE ONLY mode, the countdown will be accompanied by a warning beeping tone only, which changes to
a continuous tone once the Exit Delay cycle expires.
MESSAGE TYPE – The message type is selectable to “MSG1” or “MSG2”.
MSG1: (Female Voice) “Exit in 12 seconds, facility staff has been notified...Exit in 5 seconds...exit now...”
MSG2: (Male Voice) “Exit in 12 seconds, security has been alerted...Exit in 5 seconds...exit now…”
Both messages repeat “Exit now” until the lock is reset.
P:\INSTALLATION INST\Delayed Egress\INST-1511ST\INST-1511ST.vsd Rev E 09-08 Page 8
WARNING!
CONTACT AUTHORITY HAVING JURISDICTION FOR APPROVAL
PRIOR TO SELECTING DELAY TIME OR PWR-UP SETTINGS
*
OFF
MESSAGE TYPE
VOICE / TONE
PWR-UP OPTION
*
REQUEST TO EXIT
RELOCK DELAY
(SEC)
NUISANCE
DELAY
*
20 1530
1
LOCKED UNLOCKED
VOICE TONE
ONLY
MSG #2MSG #1
21 76
543 8
ON
TRIGGER TYPEREMOTE INTERNAL
ON
NUISANCE DELAY
*
– The Nuisance delay time feature, intended to avoid accidental triggering, is selectable for 1 or 2 seconds.
Releasing the door latch and pushing on the door will activate the internal trigger sensor. Activating the trigger beyond the nuisance
delay time will start the irreversible Exit Delay cycle time. The Nuisance Delay time period is included in the lock release cycle and it
will not increase or decrease the “total time to unlock” once the ExitCheck
TM
is activated. Releasing the door before the end of the
Nuisance delay time will turn off the warning alarm and reset the ExitCheck
TM
to secure mode.
RELEASE TIME
*
– The Release time is selectable for 15 or 30
seconds. The Nuisance Delay time period is included in the
door release cycle and it will not increase or decrease the “total
time to unlock” once the ExitCheck
TM
is activated.
1 SEC. 2 SEC.
RELEASE
TIME
*
15 SEC. 30 SEC.
JUMPER SETTINGS
JUMPER J6 (Fire Alarm Input) – Factory Installed. Remove
J6 only if a dry, normally closed contact from a fire alarm OR
smoke detector system is connected to the Fire Panel [FP]
terminals.
JUMPER J7 (Door Prop) – When removed, the ExitCheck™
will allow the user to prop the door open indefinitely after a
valid REX input, without causing an alarm. The lock will
automatically relock once the door is closed.
With J7 installed, the ExitCheck™ will go into its alarm mode if
the door remains open after to the REX time expires.