SEA GATE 2 DG R1B User manual

67411387 REV. 16 - 04/2021
SEA USA Inc.
10850 N.W. - 21st - unit 160 - Doral - MIAMI
Florida (FL) - 33172 - USA
Telephone - : ++1-305.594.1151 ++1-305.594.7325
Toll free: 800.689.4716
www.sea-usa.com
[email protected]
GATE 2 DG R1B
CONTROL UNIT FOR ONE OR TWO OPERATORS 230V/115V MANAGEMENT
IMPORTANT SAFETY INFORMATION
Clean and grease parts in movement (wheels, counter-connecting rod, release, etc.)
Check for corroded parts and replace if necessary
Check if the screws and all mounting hardwares are properly tighten
Check the conditions of wear and tear of the devices in movement
Check the correct drain of the rainwater
Check the integrity of the connection cables
Inspect the track for any signs of cracking or separation
Ensure that the gate moves freely
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
Check and confirm the proper operation of all safety devices (photocells, edge sensors etc)
Check and confirm the operation of all installed accessories
Check and confirm the operation of the manual release
Check the battery conditions and be sure that connections are free of corrosion
Verify the functionally of the battery backup, or power failure option
GENERAL SAFETY PRECAUTIONS
The following precautions are an integral and essential part of the product and must be supplied to the user;
Read them carefully as they contain important indications for the safe installation, use and maintenance.
1. These instruction must be kept and forwarded to all possible future users of the system.
2. This product must be used only for that which it has been expressly designed.
3. Any other use is to be considered improper and therefore dangerous.
4. The manufacturer cannot be held responsible for possible damage caused by improper or unreasonable use.
5. Avoid operating in the proximity of the hinges or moving mechanical parts.
6. Do not enter the path of the moving gate while in motion.
7. Do not obstruct the motion of the gate as this may cause a situation of danger.
8. Do not allow children to play or stay within the path of the moving gate.
9. Keep remote control or any other control devices out of the reach of children, in order to avoid possible involuntary
activation of the gate operator.
10. In case of break down or malfunctioning of the product, disconnect from the main power source. Do not attempt to
repair or intervene directly, contact only qualified personnel for repair.
11. Failure to comply with the above may create a situation of danger.
12. All cleaning, maintenance or repair work must be carried out by qualified personnel.
13. In order to guarantee that the system works efficiently and correctly it is important to have the manufacturer's
instructions on maintenance of the gate and operator carried out by qualified personnel.
14. In particular, regular checks are recommended in order to verify that the safety devices are operating correctly.
All installation, maintenance and repair work must be documented and made available to the user.
IMPORTANT SAFETY INSTRUCTIONS
WARNING – TO REDUCE THE RISK OF INJURY OR DEATH:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4.Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or stop when an object
activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to
adjust and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving
6. KEEP GATES PROPERLY MAINTAINED. Read the owner’s manual. Have a qualified service person make repairs to
gate hardware.
7. The entrance is for vehicles only. PEDESTRIANS MUST USE SEPARATE ENTRANCE.
8. Every gate operator installation MUST have secondary protection devices agains entrapments, such as edge
sensors and photo beams more in particulary in places where the risk of entrapments is more likely to occur
9. SAVE THESE INSTRUCTIONS
OPERATORS PERIODIC MAINTENANCE
TURNING OFF THE POWER
BY MAIN SOURCE TURNED-OFF
TURNING ON THE POWER
!
YEARLY
YEARLY
YEARLY
YEARLY
YEARLY
ALL THE ABOVE DESCRIBED OPERATIONS MUST BE MADE EXCLUSIVELY BY AN AUTHORIZED INSTALLER
2
GENERAL SAFETY INFORMATION
An appliance shall be provided with an instruction manual.
The instruction manual shall give instructions for the installation, operation, and user maintenance of the appliance.
The installation instructions shall specify the need for a grounding-type receptacle for connection to the supply and
shall stress the importance of proper grounding.
The installation instructions shall inform the installer that permanent wiring is to be employed as required by local
codes, and instructions for conversion to permanent wiring shall be supplied.
INFORMATION SHALL BE SUPPLIED WITH A GATE OPERATOR FOR:
a. The required installation and adjustment of all devices and systems to effect the primary and secondary protection
against entrapment (where included with the operator).
b. The intended connections for all devices and systems to effect the primary and secondary protection against en-
trapment. The information shall be supplied in the instruction manual, wiring diagrams, separate instructions, or the
equivalent.
VEHICULAR GATE OPERATORS (OR SYSTEMS)
A vehicular gate operator shall be provided with the information in the instruction manual that defines the different
vehicular gate operator Class categories and give examples of each usage. The manual shall also indicate the use for
which the particular unit is intended as defined in Glossary, Section 3. The installation instructions for vehicular gate
operators shall include information on the Types of gate for which the gate operator is intended.
A gate operator shall be provided with the specific instructions describing all user adjustments required for proper
operation of the gate. Detailed instructions shall be provided regarding user adjustment of any clutch or pressure relief
adjustments provided. The instructions shall also indicate the need for periodic checking and adjustment by a qualified
technician of the control mechanism for force, speed, and sensitivity.
Instructions for the installation, adjustment, and wiring of external controls and devices serving as required protection
against entrapment shall be provided with the operator when such controls are shipped with the operator.
Instructions regarding intended installation of the gate operator shall be supplied as part of the installation instructions
or as a separate document. The following instructions or the equivalent shall be supplied where applicable:
IMPORTANT INSTALLATION INSTRUCTIONS
1. Install the gate operator only when:
a. The operator is appropriate for the construction of the gate and the usage Class of the gate
b. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 4 feet
(1.22 m) above the ground to prevent a 2-1/4 inch (57.2 mm) diameter sphere from passing through the openings
anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position
c. All exposed pinch points are eliminated or guarded
d. Guarding is supplied for exposed rollers
2. The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a
separate access opening. The partial access opening shall be designed to promote pedestrian usage. Locate the gate
such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
3. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent
structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access
areas.
4. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do
not over-tighten the operator clutch or pressure relief valve to compensate for a damaged gate.
5. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving and
AWAY FROM THE GATE PATH PERIMETER.
6. Controls intended for user activation must be located at least six feet (6’) away from any moving part of the gate and
where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or
easily accessible controls shall have a security feature to prevent unauthorized use.
7. The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not
cause the operator to start.
8. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible
9. FOR GATE OPERATORS UTILIZING A NON-CONTACT SENSOR:
a. See instructions on the placement of non-contact sensors for each Type of application
b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the
gate is still moving
c. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the
perimeter reachable by a moving gate or barrier
3
10. FOR A GATE OPERATOR UTILIZING A CONTACT SENSOR:
a. One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the
leading edge, trailing edge, and postmounted both inside and outside of a vehicular horizontal slide gate.
b. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
c. One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
d. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor
and the gate operator is not subjected to mechanical damage.
e. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for
entrapment protection functions shall be located where the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall
function under the intended end-use conditions.
f. One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if
the bottom edge of a swing gate is greater than 6 inches (152 mm) above the ground at any point in its arc of travel,
one or more contact sensors shall be located on the bottom edge.
g. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
INSTRUCTION REGARDING INTENDED OPERATION OF THE GATE OPERATOR SHALL BE PROVIDED AS PART OF THE USER
INSTRUCTIONS OR AS A SEPARATE DOCUMENT. THE FOLLOWING INSTRUCTIONS OR THE EQUIVALENT SHALL BE PROVIDED
NOTICE
As for misunderstandings that may arise refer to your area distributor or call our help desk. These instructions are part
of the device and must be kept in a well known place. The installer shall follow the provided instructions thoroughly.
SEA products must only be used to automate doors, gates and wings. Any initiative taken without SEA USA Inc. explicit
authorization will preserve the manufacturer from whatsoever responsibility. The installer shall provide warning notices
on not assessable further risks. SEA USA Inc. in its relentless aim to improve the products, is allowed to make
whatsoever adjustment without giving notice. This doesn’t oblige SEA to up-grade the past production. SEA USA Inc.
can not be deemed responsible for any damage or accident caused by product breaking, being damages or accidents
due to a failure to comply with the instructions herein. The guarantee will be void and the manufacturer responsibility
will be nullified if SEA USA Inc. original spare parts are not being used. The electrical installation shall be carried out by
a professional technician who will release documentation as requested by the laws in force. Packaging materials such
as plastic bags, foam polystyrene, nails etc must be kept out of children’s reach as dangers may arise.
TO RESPECT THE LAWS IN FORCE IT IS RECOMMENDED TO USE THE ENCODER WITH THE ELECTRONIC CONTROL UNIT
UL 325 ED. 6th ENTRAPMENT PROTECTION REQUIREMENTS
VEHICULAR GATE OPERATOR CLASSES
Residential Vehicular Gate Operator-Class I: A vehicular gate operator (or system) intended for use in garages or
parking areas associated with a residence of one-to-four single families
Commercial/General Access Vehicular Gate Operator-Class II: A vehicular gate operator (or system) intended for
use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotel,
garages, retail store, or other buildings accessible by or servicing the general public
Industrial/Limited Access Vehicular Gate Operator–Class III: A vehicular gate operator (or system) intended for
use in an industrial location or building such as a factory or loading dock area or other locations not accessible by or
intended to service the general public
Restricted Access Vehicular Gate Operator–Class IV: A vehicular gate operator (or system) intended for use in an
industrial location or building such as a factory or loading dock area or other locations not accessible by or intended to
service the general public
THIS VEHICULAR GATE OPERATOR MUST BE INSTALLED WITH AT LEAST TWO INDEPENDENT ENTRAPMENT PROTECTION MEANS
AS SPECIFIED IN THE TABLE BELOW
HORIZONTAL SLIDE
VERTICAL LIFT - VERTICAL PIVOT
ENTRAPMENT
PROTECTION
TYPES
TYPE A
TYPE B1
TYPE B2
TYPE C
Inherent entrapment protection system
Non-contact sensors such as photoelectric sensors or equivalents
Contact sensors such as edge sensors or equivalent devices
Inherent force limiting, inherent adjustable clutch or inherent pressure relief device
TYPE D Actuating device requiring constant pressure to maintain opening or closing motion of the gate
SWING
VERTICAL BARRIER (ARM)
A , B1*, B2* or D A , B1*, B2*, C or D
GATE OPERATORS CATEGORY (Effective January, 12 2016)
4
NOTES:
1. The same type of device shall not be used for both entrapment protection means. Use of a single device to cover both
the opening and closing directions is in accordance with the requirement; however, a single device is not required to
cover both directions. Tice installer is required to install entrapment protection devices in each entrapment zone
2. FOR VERITICAL BARRIERS ONLY: Barrier gate operators (arm) that is not intended to move toward a rigid objact
closer than 16 inches (406 mm) are not required to be provided with a means of entrapment protection
* B1 and B2 means of entrapment protection MUST be MONITORED
Changes to UL 325 ED. 6th for Gate Operators
Starting on Jan. 12, 2016, new UL 325 changes take effect, bringing a series of new mandates for the gate
operator industry. Here’s a quick guide to the key modifications
1. ENTRAPMENT-PROTECTION DEVICES: Gate operators are required to have a minimum of two independent means of
entrapment protection where the risk of entrapment or obstruction exists. A manufacturer can use two inherent-type
systems, two external-type systems, or an inherent and an external system to meet the requirement. However, the
same type of device cannot be used for both means of protection.
2. MONITORING REQUIRED: An external non-contact sensor or contact sensor may be used as a means of entrapment
protection. However, the sensor must be monitored once every cycle for:
a. the correct connection to the operator
b. the correct operation of the sensor
If the device is not present, not functioning, or is shorted, then the gate operator can only be operated by constant
pressure on the control device. Portable wireless controls will not function in this case.
3. ENTRAPMENT RISK IDENTIFICATION: As in the past, it’s up to the installer to examine the installation and determine
where a risk of entrapment or obstruction exists. Manufacturers are required to provide instructions for the placement
of external devices, but they give only examples of suggested entrapment protection in their installation manuals. If the
installer identifies a risk of entrapment or obstruction, at least two independent means of entrapment protection are
required.
4.TERMINOLOGY CHANGE: The terms «primary» and «secondary» have been removed in the description of entrapment
protection devices. This was done to emphasize that all entrapment protection devices are equally important.
5. THE END OF TYPE E: Type E (audible alarm) devices can no longer be used for entrapment protection. This change
was made because the Type E device is really a warning device, not an entrapment-protection device. Also, all gate
operator classes are now required to have an audio alarm that sounds when two successive obstructions are
encountered via a contact-type system.
6. ACCESS CONTROL LOCATION FOR EMERGENCY USE: An exception has been added in the manufacturer’s instructional
requirements for the location of controls that operate the gate.
The instructional requirements state that these controls must be at least 6' away from any moving part of the gate. In the
new exception, «Emergency access controls only accessible by authorized personnel (e.g., fire, police, EMS) may be
placed at any location in the line-of-sight of the gate».
7. BARRIER-ARM OPERATOR EXCEPTION: An exception has changed for barrier-arm gate operators requiring entrapment
protection. The previous exception stated that a barrier-arm operator did not require entrapment protection if the arm
did not move toward a rigid object closer than 2". The distance has been reduced to 16" so it more closely aligns with the
industry-defined entrapment protection provisions in ASTM F2200.
8. GATE OPERATOR CLASS II AND CLASS III DEFINITIONS: The definitions for installation classes for gate operators were
modified. Class II now includes commercial locations accessible to the general public. Class III was refined to specify
industrial locations not accessible to the general public. These changes, while seemingly minor, may affect which gate
operator is suitable for a particular installation location.
5
INDEX
8
8
9
9
9
9
9
9
9
10
10
10
10
11
11
12
12
12
13
13
13
13
13
14
14
14
14
14
15
15
15
15
CHAPTER PAGE CHAPTER PAGE
1
2
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
4
4.1
4.2
4.3
4.4
5
5.1
5.2
6
6.1
7
7.1
8
8.1
9
9.1
9.2
9.3
9.4
10
10.1
10.2
11
12
13
14
15
16
17
--
--
Connections
Contacts
Connections on CN1
Start
Partial opening Start
Stop
Photocells 1 and 2
24V AUX
Timer
Flashing lamp
Safety edge
10K Photocell
Buzzer
Safety loop
Connections on 24VAUX
External receiver
Latch opening/closing
LB management unit
Connections on CN2
Limit switch
Electric lock
External receiver
Synchronized photocells
Connections on CN3/CN4
Motor connection
Three-phase module
Connections on CN5
Courtesy light
Connections on CN6
Control unit power supply
Connections on CN7
Encoder
Connections on EXP
SEM 2 management unit
Temperature probe
Additional limit switches
Potentiometer
Additional functions
Amperometric management
Surge Protector circuit
Display/programming
Basic Menu
Input management
Working times
Logics
Password
Receivers - remote controls
Menu table
Alarms indications
16
16
16
16
17
18
18
19
19
20
21
23
25
25
26
28
36
6
6,85 inches
6,61 inches
OK
UP DOWN
BLACK
WHITE RED
CNA
JOLLY
EXP
CN7
CNP
CN1
F3 R3
CN2
T2
T1
R1
TR1
R4
F1
R2
F2
CN6 CN5 CN4 CN3
POWER SUPPLY
WORKING TEMPERATURE
STAND-BY ABSORPTION
EXTERNAL BOX
230 Vac 50/60 Hz
115Vac 50/60 Hz
30 mA
12,82x9,70x5,51 inches
IP55
TECHNICAL DATA
-4°F +122°F
COMPONENTS
CN3
CN4
CN5
CN6
CNP
EXP
CN1
CN2
CN7
CNA
JOLLY
T1
T2
TR1
R1
R2
R3
F1
F2
R4
F3
input / output
limit switch - 24V - electric lock
motor 1 - capacitor M1
motor 2 - capacitor M2
courtesy light
power supply
encoder
RX receiver
programming
external module
JOLLY 3 - SEACLOUD
motor control - triac
motor control - triac
motors relay
courtesy light relay
photocell self-test relay
electric lock relay
1 A accessories fuse
6.3AT fuse (230V) - 10AT fuse (115V)
electric lock 6.3 A fuse
power transformer
7
Partial opening Start
Photocell 2
Safety Edge 1
Safety Edge 2
Common
Common
Common
Photocell 1
Italiano
ENGLISH
International registered trademark n. 804888
Start
Stop
Common
* THE MAXIMUM INDICATED LOAD OF 800 MA REFERS TO THE MAXIMUM LOAD DISTRIBUTED
ON ALL 24V OUTPUTS INCLUDED THE ABSORPTION OF THE RECEIVER ON BOARD (30 MA)
ON THE 24V AUX OUTPUT IT IS POSSIBLE TO CONNECT A MAXIMUM LOAD OF 800 MA
THE HEREIN REPORTED FUNCTIONS ARE AVAILABLE STARTING FROM SOFTWARE REVISION 03.02
OF THIS CONTROL UNIT AND IT IS COMPATIBLE WITH JOLLY 3 PROGRAMMER
PROGRAMMING
BUTTONS
2 - CONTACTS
N.C. CONTACTS
The inputs excluded in self-learning can be restored in the «INPUTS STATUS CHECK »
menu (chapter 13) without need to repeat the control unit self-learning
WARNING!
TH E C O N T R O L U N I T I S
D E S I G N E D F O R T H E
AUTOMATIC DETECTION OF
NOT USED N.C. INPUTS
(PHOTOCELLS, STOP, LIMIT
SWITCHES AND SAFETY
EDGES)
Antenna
Flashing lamp
500 mA max.
24V DC AUX
* (800 mA max)
CN1
98
7
6
5
4
3
2
110 13
12
11
-
+
ANT COM START STPD STOP COM PH1 PH2 EDGE1 EDGE2 COM 24 A FLS V
Opening Limit Switch 1
Closing Limit Switch 1
Opening Limit Switch 2
Closing Limit Switch 2
CN3 CN4
31 32 33 34 35 36 37 38 39 40
M1
Motor 1 closing
Motor 1 neutral
Motor 1 opening
CLM1 NM1 OPM1 CAPM1
-
-
M1
-
-
CLM2 NM2 OPM2 CAPM2
Motor 1 capacitor
CN5
Lamp
Lamp N
CN6
41 42 L N
Line
Neutral
CN7
-
-
24V~
(800 mA max)
-
-
24VPH
(800 mA max)
-
-
Electric lock
CN2
CN2
14 15 16 17 18 19 20 21 22 23
14 15 16 17 18 19 20 21 22 23
LSO1 LSC1 LSO2 LSC2 COM 24V~ 24VPH LOCK
LSO1 LSC1 LSO2 LSC2 COM 24V~ 24VPH LOCK
+24 ENC 1 ENC 2 GND
OPEN
(Firmware update)
RADIO MODULE
CONNECTOR
EXTERNAL
MODULE
CONNECTOR
CNA
ENCODER
CONNECTOR
CNP JOLLY
JOLLY3
SEACLOUD
CONNECTOR
EXP
UP DOWN OK
BLACK WHITE RED
CN1
98
7
6
5
4
3
2
110 13
12
11
-
+
ANT COM START STPD STOP COM PH1 PH2 EDGE1 EDGE2 COM 24 A FLS V
24V DC CONTACTS
24V AC CONTACTS
NO JUMPERS ARE NEEDED
ON N.C. CONTACTS
Motor 1 closing
Motor 1 neutral
Motor 1 opening
Motor 1 capacitor
WARNING: CONNECT ALL DEVICES WITH SWITCHED-OFF CONTROL UNIT
Partial opening Start
Photocell 2
Safety Edge 1
Safety Edge 2
Common
Common
Common
Photocell 1
Start
Stop
Common
Antenna
Flashing lamp
500 mA max.
24V DC AUX
* (800 mA max)
Opening Limit Switch 1
Closing Limit Switch 1
Opening Limit Switch 2
Closing Limit Switch 2
24V~
(800 mA max)
24VPH
(800 mA max)
Electric lock
1 - CONNECTIONS
8
Italiano
ENGLISH
International registered trademark n. 804888
IMPORTANT: on menu 89-TRAFFIC LIGHTS RESERVATION it is
possible to activate the priority in opening or closing to be associated
to the START and the PARTIAL OPENING START buttons
(only with SEM management unit)
3 - CONNECTIONS ON CN1
CN1
8
7
6
5
4
3
2
1
CN2
7 18 19 20 21 22 23
Start
Stop
Partial START
Common
Antenna
Common
TX
RX
TX
RX
Photocell 1
Photocell 2
3.1 - START (N.O.)
On clamps 3 and6
The automation can be opened or closed through an impulse
transmitted to this input (via key button, keyboard, etc.). To
connect other START devices (for ex. the magnetic loop) refer
to the respective instructions
Note 1: For details on the logics that can be associated to the
START button, see chapter 15 (LOGICS)
Note 2: If this contact is engaged during the pause (ie. Timer),
the gate will not close until releasing
3.2 - PARTIAL OPENING START (N.O.)
On clamps 4 and 6
The input allows to obtain the partial opening. It is possible to
manage the opening space through the menu-90 or through
the JOLLY 3. It is also possible to manage the partial opening
pause time through the menu- 91
Note 1: For details on the logics that can be associated to the
PARTIAL OPENING START button, see chapter 15 (LOGICS)
Note 2: If this contact is engaged during the pause (ie. Timer),
the gate will not close until releasing
3.3 - STOP (N.C.) On clamps 5 and 6
If this button is pressed the engine stops immediately in whatever condition or position it is. A new Start
command will be required to restore the movement.
Note: After the Stop command, the engine will always re-start in closing
3.4 - PHOTOCELL 1 AND PHOTOCELL 2 (N.C.)
24V~ max 800mA - COM = 0V (clamps 19 e 20) 24VPH max 800mA - COM = 0V (clamps 20 e 21)
Ph1 = Photocell 1(clamp 7) PH2 = Photocell 2 (clamp 8)
Note 1: To perform the photocells self-test, connect the positive of the TX photocell to the clamp 20 and 21;
From the 95-PHOTOTEST menu options it is possible to choose where to enable the self-test
Note 2: The default settings are: 97-PHOTOCELL 1 = «closing»; 98-PHOTOCELL 2 = «opening and
closing»; for further functions and management, see menu-97 and menu-98
3.5 - OPTIONS max 800mA24V DC AUX
From menu 94-24VAUX or through the JOLLY 3 it is possible to choose when to have voltage on the AUX
output. On the AUX output it is also possible to connect a relay (i.e. in paragraph 3.12) for the connection
and the management of additional accessories (electric brake, additional warning lights, etc.)
3.6 - TIMER (N.O.)
On clamp 4 (Partial Opening Start) or on clamp 8 (Photocell 2)
It can be enabled through menu 92-TIMER or via JOLLY 3. It opens and keeps the automation open until
the contact is released. When released, the operator will wait for the pause time set then will close again
Note 1: If connected to the Partial Opening Start, this command will also be disabled on the remote control
Note 2: If the timer is enabled, in the event of a safety device intervention, the timer automatically reset
after 6 seconds
Note 3: In case of a power failure when the gate is open, if the TIMER is still active, the gate automatically
closes when the power is restored; if no longer active, a new START impulse will be required
9
Italiano
ENGLISH
International registered trademark n. 804888
Common
Edge
-
+
24V 800 mA max
Flashing Lamp
FL(+)
CN1
13
12
11
10
9
3.8 - SAFETY EDGE (N.C.)
Safety edge 1 on clamps 9 and 11
Safety edge 2 on clamps 10 and 11
If enabled, the safety edge opens the contact causing a partial inversion of the motion both in opening and
closing. The functions can be managed from menus 100-SAFETY EDGE 1 and 101-SAFETY EDGE 2;
The direction can be managed from menus 102-EDGE 1 DIRECTION and 103-EDGE 2 DIRECTION
Note 1: among the options of the menu-100 and menu-101, there is the 8K2 balanced edge (single or
double): the safety edge contact will be controlled by a specific resistance value which detects any
possible short-circuit of the device. If the device is unbalanced, a specific alarm will appear on the display
Note 2: it is possible to manage the functions of the safety edges also from the JOLLY 3 programmer
Common
Safety
edge
Flashing Lamp
FL(-)
CN1
13
12
11
10
9
100
UP
OK
PHOTO
10K
OK
100
UP
OK
PHOTO 10K
DOUBLE
OK
Up to 4 10K Photocells
CN1
13
12
11
10
9
GREY
WHITE
BROWN
BLUE
GREY
WHITE
GREY
WHITE
GREY
WHITE
EXAMPLE OF
LAMP AND
SAFETY EDGE
CONNECTION
Safety Edge 1
Safety Edge 2
3.7 - 24V FLASHING LIGHT - MAX 3W
On clamps 11 and 13
It warns of the gate movement by performing 1 blink per
second on opening, 2 blinks per second on closing and
remaining on steady during pause. Through the flashing light
it is also possible to read the alarm signals linked to the Stop,
Photocell1, Photocell2 and Edge devices.
From menu 86-FLASHING LIGHT or JOLLY3 it is possible
to modify its functions.
Furthermore it is possible to manage the pre-flashing
function from menu 85- PRE-FLASHING
EXAMPLE
OF 10K
PHOTOCELLS
CONNECTION
Common
Edge1
24VAUX 800 mA max
Edge2
BROWN
BLUE
BROWN
BLUE
BROWN
BLUE
GREY
WHITE
BROWN
BLUE
EXAMPLE OF 10K PHOTOCELL
AND BUZZER CONNECTION
Photocell 10K
3.9 - 10K SINGLE OR DOUBLE PHOTOCELL
On clamps 9 - 11 - 12 and 10 - 11 - 12
It is possible to connect up to four 10K photocells by setting menus
100-SAFETY EDGE 1 and/or 101-SAFETY EDGE 2 on the respective
options (each contact allows you to connect up to 2 10K photocells).
The 10K photocells will work according to the settings of menu
97-PHOTOCELL 1 and menu 98-PHOTOCELL 2
Note1: The 10K photocell gives additional protection even in the event
of a short circuit on the cables
SINGLE OR DOUBLE PHOTOCELL SETTINGS
EDGE 1
EDGE 1
3.10 - BUZZER 24V
On clamps 11 and 13
The Buzzer is a sound alarm that can be used as a safety device.
Use a self-oscillating 24V and 100 dB Buzzer
The Buzzer can be connected instead of the flashing light and it is
necessary to set on «BUZZER» in the menu 86-FLASHING LIGHT
The Buzzer will activate after 2 consecutive interventions of the anti-
crushing protection; to reset it press the STOP button;
In any case, the sound of the Buzzer turns off automatically after 5
minutes and the automation will stand waiting for a new command
IF BUZZER DOES NOT WORK, BE SURE THAT
MENU 86-FLASHING LIGHT IS SET ON «BUZZER»
10
BROWN
GREEN
GREEN
GREEN
GREEN
PINK
EXAMPLE OF
SAFETY LOOP CONNECTION
C1 = OPEN CONTACT
C2 = CLOSED CONTACT
GREY
YELLOW
Italiano
ENGLISH
International registered trademark n. 804888
Loop 1
Safety Exit
Loop 2
Shadow Loop
Loop 3
Free Exit
Shadow Loop (Loop 2)
Connection scheme of the
2 readers loop detector
8 = Photocell 2 contact (N.C.)
6 = Common
NOTE: Menu 98-PHOTOCELL 2
must be set on «SHADOW LOOP»
Free Exit Loop (Loop 3)
Connection scheme of the
1 reader loop detector
3 = Start contact (N.O.)
6 = Common
CN1
98
7
6
5
4
3
2
110 13
12
11
CN1
98
7
6
5
4
3
2
110 13
12
11
11 / C (-) = 0 V
12 = 24 V
CN1
Loop1
Loop2
Loop3
98
7
6
5
4
3
2
110 13
12
11
C C2 C2C1
11 - Common
12 - AUX 24V
(800 mA max)
-
COM
NO
NC
1 2 3 4 5 67
COM (-)
Alimentazione esterna
12V/24V DC oppure 230V
NO
NC COM
+
+
+
-
+
+
11 - Common
12 - AUX 24V
(800 mA max)
3.11 - SAFETY LOOP
Safety Exit Loop (Loop 1)
Connection scheme of the
1 reader loop detector
7 = Photocell 1 contact (N.C.)
6 = Common
Example: Magnetic Lock
Magnetic
Lock
Example:
Vertical Electric Lock
EXAMPLE OF WITH RELAY CODE 23105340CONNECTION
EXAMPLE OF WITH RELAY CODE 54020285CONNECTION
Relay Type 23105340
External Power Supply
12V/24V DC (or 230V)
Relay Type 54020285
External Power Supply
12V/24V DC (or 230V)
Vertical
Electric Lock
3.12 - CONNECTIONS ON THE 24V AUX OUTPUT THROUGH RELAY
On clamps 11 and 12
It is possible to connect additional accessories via relay connected to the 24V AUX output and manage
them through the menu 94-24V AUX. The menu options allow you to choose how to have voltage on the
output and, consequently, to choose the option that best manages the accessory you want to connect.
WARNING! connect the accessory AFTER selecting the option
EXAMPLE: It is possible to connect a magnetic lock (MagLock) or a vertical lock through the Relay card
code 23105340 (or old model code 54020285) to the control unit and to the external power supply (12 / 24V
DC power supply in case of 12V / 24V lock or 230V power supply in case of 230V lock)
In this case, set 94-24V AUX to «NEGATIVE BRAKE» before connecting the lock!
11
LATCH CLOSING
CLOSES AND KEEPS CLOSED
LATCH OPENING
OPENS AND KEEPS OPEN
NO OTHER COMMAND ACCEPTED
Italiano
ENGLISH
International registered trademark n. 804888
EXAMPLE OF EXTERNAL RECEIVER CONNECTION
NO OTHER COMMAND ACCEPTED
CN1
98
7
6
5
4
3
2
110 13
12
11
CN1
98
7
6
5
4
3
2
110 13
12
11
3.13 - EXTERNAL RECEIVER
An external receiver can be connected to the
control unit, according to the connection
diagram on the side. In this case, it is
necessary to set the 94-24VAUX menu to
the " A LWAY S " opti o n to ensur e the
continuous power supply of the output
It is also possible to connect the external
receiver to the 24VAC outputs of CN2 - see
paragraph 4.3
12
11
6
6
34
4
Common
On clamps 4 and 6
A button for the Latch Opening or Closing function can be connected to the control unit. To activate it,
connect the N.O. contact on the Partial Opening Start (this function will be disabled). Through the menu
118-LATCH it is possible to choose between the various Latch options. To deactivate the Latch function,
press again the button used for its activation
LATCH OPENING: opens and keeps the automation open. If active, no other type of Start command is
accepted until the function is deactivated
LATCH CLOSING: closes and keeps the automation closed. If active, no other type of Start command is
accepted until the function is deactivated
Note 1: The Latch function can also be enabled on the second channel of the remote control; see
paragraph 17.2 for details
Note 2: The Latch function can also be enabled through the SEACLOUD. Please refer to the SEACLOUD
instructions for more details
24V DC AUX
(800 mA max)
3.15 - «LB» MANAGEMENT UNIT FOR «STAR 400/800»
+
-
CM
NONC
+
-
+
-
12V 12V CN1
7
6
5
4
3
2
1
On clamps 2 and 3
The «STAR 400/800» emergency UPS can be
connected to the control unit via the «LB»
management unit which controls the battery
charge and allows the operator to carry out
one last maneuver before the batteries are
completely discharged. The «LB» unit and
the batteries can be managed through the
113-EMERGENCY menu
FOR FURTHER DETAILS ON THE «LB» MANAGEMENT UNIT, ON THE «STAR 400/800» EMERGENCY UPS AND
ON ALL THE CONNECTIONS, SEE THEIR TECHNICAL INSTRUCTIONS
3.14 - LATCH OPENING OR LATCH CLOSING BUTTON
12
Italiano
ENGLISH
International registered trademark n. 804888
14 15 16 17 18 19 20
CN2
17 18 19 20 21 22 23
CN2
EXAMPLE OF ELECTRIC LOCK CONNECTION
CN1
7
6
5
4
3
2
1
6
34
17 18 19 20 21
CN2
17 18 19 20 21
CN2
19 20
4.4 - SYNCRONIZED PHOTOCELLS CONNECTION
JP1
Tx1
JP1
Rx1
1 2 3 4 5 6
0 +12 +24 C N N
O O C
M
JP1
Rx2
JP1
1 2 3
Tx2
0 +12 +24
RED
1 2 3 4 5 6
0 +12 +24 C N N
O O C
M
BLACK
RED
BLACK
RED
BLACK
1 2 3
0 +12 +24
JP1
4 - CONNECTIONS ON CN2
4.1 - LIMIT SWITCH
For the limit switch function, both the closing
and opening limit switches must be
connected. It is also possible to activate the
anti-intrusion function, which is linked to
the presence of one limit switch at least; If it
is released, it forces the operator to reclose
For the correct operation of the limit
switches the correspondence between
the operators movement direction and
the respective limit switch direction is
required
NOTE:
In the menu 104-SELECT LIMIT SWITCH
it is possible to choose whether to work
with the opening limit switch only or with
the closing one only or with both
N.C.
18
14
18
15
18
16
18
17
N.C.
N.C.
N.C.
!
4.2 - 12V ELECTRIC LOCK
On clamps 22 and 23
An Electric Lock (12V - 15W max) can be connected
Through menu 77-LOCK TIME it is possible to adjust the
electric lock release time from 0 to 5 seconds
Through menu 78-LOCK it is possible to select when to
activate the electric lock, if only in opening, only in closing or
in both directions
4.3 - EXTERNAL RECEIVER
It is possible to connect an external
receiver according to the connection
diagram on the side. The clamps 19
and 20 of CN2 supply 24V~AC,
therefore the receiver will always be
powered
OPENING LIMIT SWITCH
MOTOR 1
CLOSING LIMIT SWITCH
MOTOR 1
OPENING LIMIT SWITCH
MOTOR 2
CLOSING LIMIT SWITCH
MOTOR 2
EXAMPLE OF EXTERNAL
RECEIVER CONNECTION
It is possible to connect one or two pairs of
synchronized photocells on the clamps 19 and
20 of CN2 (24V~AC), according to the aside
diagram (for further details refer to the photocell
instructions).
It is also possible to change the photocell
settings through the 97-PHOTOCELL1 and
98-PHOTOCELL 2 menus
JP1 ON
SYNCHRONIZATION ENABLED
13
Italiano
ENGLISH
International registered trademark n. 804888
6.1 - COURTESY LIGHT CONNECTIONS (230V or 115V)
42 - Courtesy light (neutral)
Example:
Timed Courtesy light from 0 up to 4 minutes
Max. 50W 230V Max. 100W 115V
6 - CONNECTIONS ON CN5
CN5
41 42
41 - Courtesy light (phase)
5 - CN3 AND CN4CONNECTIONS ON
5.1 - OPERATORS CONNECTION ON THE CONTROL UNIT
CN3
31 32 33 34 35
-
-
CLM1 NM1 OPM1 CAPM1
31 32 33 34 35
CN4
-
-
36 37 38 39 40
CLM2 NM2 OPM2 CAPM2
= CLOSE
= NEUTRAL
= OPEN
CLM1
NM1
OPM1
MOTOR 1
M
~
M1
~
**
** **
*
= CLOSE
= NEUTRAL
= OPEN
CLM2
NM2
OPM2
MOTOR 2
M
~
IN CASE OF CONNECTION AND MANAGEMENT OF A SINGLE OPERATOR, USE THE CN3 TERMINAL FOR MOTOR 1
5.2 - THREE-PHASE MODULE CONNECTION WARNING!
Set the menu
3-MOTOR on
«5-THREE-PHASE-BOLLARD»
N L
T1
CN1
NNF
COM
OP.
CL.
K2
K1
FST1
R (2T1)
S (4T2)
T (6T3)
CN2
U
V
W
31
32
N L
T S R N
CN6 CN3
CLM1 NM1 OPM1
33
*
È POSSIBILE CONNETTERE FINO A 2 MODULI TRIFASE; IL SECONDO MODULO TRIFASE ASSOCIATO AL MOTORE 2 (M2)
VA COLLEGATO ALLA MORSETTIERA CN4 (MORSETTIERA DI COLLEGAMENTO MOTORE 2) ALLO STESSO MODO DELLA CN3
*
A timed courtesy light (from 0 to 240 seconds) can
be connected to the CN5, according to the aside
connection diagram
See the menu 88-COURTESY LIGHT for settings
The drawing shows two operators
for swing gate only as an exemple
BLU CABLE = 230V OPERATORS
WHITE CABLE = 115V OPERATORS
Capacitor
Capacitor
THREE-PHASE
SUPPLY 380V
THREE-PHASE
MODULE
M1
example:
BIG 4000
THREE-PHASE
THREE-PHASE MODULE CONNECTORS
CN1 = On board power connector (220V)
CN2 = Motor connector (380V)
SFT1 = Ground connection Faston
K1 = 230V ~ 16A contactor
K2 = 230V ~ 16A contactor
T1 = Thermal switch *
* T1 intervention threshold:
3,7A BIG 4000 THREE-PHASE
1,8A LEPUS
14
Italiano
ENGLISH
International registered trademark n. 804888
8 - CN7CONNECTIONS ON
8.1 - ENCODER CONNECTION
SPECIAL MENU
LANGUAGE
-
-
1
OP. LEAF DELAY
-
-
26
UP
-
-
16
OK
-
-
ON
UP
ENCODER
-
-
32
OK
ENCODER
-
-
32
OK
UP
ENCODER PAR M1
-
-
47
-
XXX
OK
ENCODER
-
-
32
OK
UP
ENCODER TOT M1
-
-
48
-
-
XXX
OK
UP
ENCODER PAR M1
-
-
47
8.2 - ENCODER SETTINGS
-
-
33
UP
DOWN
OK
-
-
XX%
OK
-
-
34
UP
DOWN
OK
-
-
XX%
OK
7.1 -CONTROL UNIT CONNECTION
CN6
N L
115V~ ± 5%
o
230V~ ± 5%
7 - CONNECTIONS ON CN6
CN7
+24 ENC 1 ENC 2 GND
red/brown
blue/white
blue/white
black/green
THE EXAMPLE REFERS ONLY TO MOTOR 1 (M1) BUT IT IS ALSO POSSIBLE TO DISPLAY THE PARAMETERS
REFERRING TO MOTOR 2 (M2) ON MENUS 49 AND 50
THE EXAMPLE REFERS ONLY TO MOTOR 1 (M1) BUT IT IS ALSO POSSIBLE TO DISPLAY THE PARAMETERS
REFERRING TO MOTOR 2 (M2) ON MENUS 35 AND 36
NEUTRAL
LINE
Fuse 3,6A delayed on 230V~ power supply
Fuse 6,3A delayed on 115V~ power supply
CAUTION!: for the connection to the power grid refer to the regulations
in force
NOTE: It is recommended to use a 10A differential switch to protect the
power supply system
NOTE: In case of unstable power supply, we recommend the use of an
external UPS of minimum 800VA
The ENCODER can be connected on CN7 by respecting the
cable colors, as shown in the figure aside
OLD TYPE ENCODER BROWN - WHITE - GREEN
NEW TYPE ENCODER RED - BLUE - BLACK
To enable the Encoder set the menu 32-ENCODER in «ON» (if not ON by default)
SPECIAL MENU
OPENING
SENSITIVITY M1
CLOSING
SENSITIVITY M1
47-ENCODER PAR M1
shows the pulses read
during operation
48-ENCODER TOT M1
shows the total pulses
stored during programming
values can be set from a minimum of 10% (rapid intervention) to a maximum of 99% (slow intervention).
If parameters are OFF (intervention excluded) the Encoder will only work in position detection mode
SETTING OF OPENING INTERVENTION TIME SETTING OF CLOSING INTERVENTION TIME
15
Italiano
ENGLISH
International registered trademark n. 804888
9 - EXPCONNECTIONS ON
24V~ / (ac/dc)
or 230V~
DS1
DS2
RL4 RL3 RL2 RL1
L4 L3 L2
IC2
- M2+
1 CNP
CN1
L1
1
2
3
4
8 7 6 5 4 3 2 1
M1
P01 P02
GND
I3
D1 P11 D2 P12 I1 I2 I4
M1
124567
38910 11
M2
DS1
1 2
ON
CN1
POT ENC
CNP
+
-
D1
P11
P01
TO INCREASE THE SLOWDOWN SPACE, MOVE BACK
THE CAM OF THE SLOWDOWN LIMIT SWITCH
1
1
ON
ON
OFF
OFF
2
2
DIP SWITCH 1 = OFF
DIP SWITCH 2 = OFF
DIP SWITCH 1 = OFF
DIP SWITCH 2 = OFF
WITHOUT INVERTER
EXP
EXP
P01 P02
GND
I3
D1 P11 D2 P12 I1 I2 I4
M1
124567
38910 11
M2
DS1
1 2
ON
CN1
POT ENC
CNP
+
-
EXP
I4
I3
I2
I1
GND
1
ON
OFF
2
DIP SWITCH 1 = OFF
DIP SWITCH 2 = ON
WITH INVERTER
9.1 - «SEM 2» MANAGEMENT UNIT CONNECTION
The «SEM 2» management unit can be
connected through the EXP connector
The SEM 2 unit manages:
- The TRAFFIC LIGHT functions
- The COURTESY LIGHT functions
- The V ERTI CAL E LECT RIC LOCK
functions
- The POSITIVE AND/OR NEGATIVE
ELECTRIC BRAKE functions
- The LIMIT SWITCH status
For further details on the «SEM 2» unit,
refer to its TECHNICAL INSTRUCTION
P11 = BLACK
D1 = WHITE
ADJUST BOTH
DIP-SWITCH IN OFF
TEMPERATURE PROBE
TO BE SCREWED TO REPLACE
THE MOTOR OIL CAP
9.2 - TEMPERATURE PROBE CONNECTION THROUGH «LSE» or «LE» UNITS
Example: «LSE» MANAGEMENT UNIT
Through the LSE management unit (or the
LE management unit) it is possible to wire up
a TEMPERATURE PROBE to detect the
engine oil temperature; If the oil tempera-
ture falls below the set value, the probe will
activate heating up to the values defined in
the set temperature range
TEMPERATURE PROBE can be enabled
through the menu 109-THERMOMETER;
TEMPERATURE RANGES can be set on:
110-LOW TEMPERATURE THRESHOLD
111-HIGH TEMPERATURE THRESHOLD
For further details on the LSE or LE units,
refer to the TECHNICAL INSTRUCTIONS
The «LSE» management unit can be
connected through the EXP connector
THE «LSE» UNIT MANAGES 4 ADDITIONAL
LIMIT SWITCHES to set the slowdown
starting points
The opening and closing limit switches
must be connected to the control unit
The additional limit switches can be
managed from 104-SELECT LIMIT SWITCH
For further details on the «LSE» unit, refer
to its TECHNICAL INSTRUCTION
9.3 - LIMIT SWITCH WITH «LSE» MANAGEMENT UNIT CONNECTION
16
Italiano
ENGLISH
International registered trademark n. 804888
* The cables colors change
depending on whether
it is the old or the new
model of potentiometer
9.5 - «POSITION GATE» POTENTIOMETER SETTING
LANGUAGE
-
-
1
OP.LEAF DELAY
-
-
26
UP
MENÚ SPECIALE
-
-
16
OK
UP
ENCODER
-
-
32
UP
DOWN
POTENTIOMETER
-
-
OK
UP
-
-
DOWN
OK
ON
POTENTIOMETER 1
P01 P02
GND
I3
D1 P11 D2 P12 I1 I2 I4
M1
124567
38910 11
M2
DS1
1 2
ON
CN1
POT ENC
CNP
+
-
P11 = BROWN D1 =WHITE OR BLACK* P01 = GREEN OR BLUE*
EXP
POTENTIOMETER 2
P12 = BROWN D2 = WHITE OR BLACK* P02 = GREEN OR BLUE*
1
ON
OFF
2
MENÚ 32 - POTENZTIOMETER - MANAGEMENT SUB-MENUS:
-
-
OK
UP
-
52
UP
I. PAR. M1
-
-
51
UP
-
-
53
I. AP. M1 I. CH. M1
OK
-
XX
UP
DOWN
Example: «LSE» MANAGEMENT UNIT
9.4 - «POSITION GATE» CONNECTION THROUGH «LSE» or «LE» UNITS
TO USE THE POTENTIOMETER
IT IS NECESSARY TO ADJUST
BOTH DIP-SWITCHES IN OFF
Through the LSE management unit (or LE
management unit) it is possible to connect
the «POSITION GATE», a potentiometer
able to manage the correct position of the
gate and the reversing on obstacle
POSITION GATE can be enabled on menu
32-ENCODER POTENZIOMETER ON
For further details on the LSE (or LE)
man ag em ent u nit s r efe r t o the ir
TECHNICAL INSTRUCTIONS
TO ENABLE POTENTIOMETER
SPECIAL MENU
51-I.PAR.M1 (PARTIAL PULSES MOTOR 1) displays the current position of the operator
52-I.AP.M1 (OPENING PULSES MOTOR 1) displays the impulses with the leaf completely open and it is
possible, accessing through OK, to increase or decrease the total pulses using the UP and DOWN buttons
53-I.CH.M1 (CLOSING PULSES MOTOR 1) displays the impulses with the leaf completely closed and it is
possible, accessing through OK, to increase or decrease the total pulses using the UP and DOWN buttons
54-I.PAR.M2 (PARTIAL PULSES MOTOR 2) displays the current position of the operator
55-I.AP.M2 (OPENING PULSES MOTOR 2) displays the impulses with the leaf completely open and it is
possible, accessing through OK, to increase or decrease the total pulses using the UP and DOWN buttons
56-I.CH.M2 (CLOSING PULSES MOTOR 2) displays the impulses with the leaf completely closed and it is
possible, accessing through OK, to increase or decrease the total pulses using the UP and DOWN buttons
Example:
POTENTIOMETER
NOTE 1: If the potentiometer reading is reversed in respect to the operator movement , the display will
show the alarm "POTENTIOMETER DIRECTION" (see the last chapter "Alarms"); it is therefore
necessary to invert the brown cable with the green cable (or Blue) and repeat the programming
17
Italiano
ENGLISH
International registered trademark n. 804888
123
UP
OK OK
--
03.02 VP 1
-
XXX
menu adjusts the intervention time in opening33-OPENING SENSITIVITY MOTOR 1
menu 34- adjusts the intervention time in closingCLOSING SENSITIVITY MOTOR 1
menu adjusts the intervention time in opening35-OPENING SENSITIVITY MOTOR 2
menu 36- adjusts the intervention time in closingCLOSING SENSITIVITY MOTOR 2
menu 37- adjusts the inversion time during the slow-downSLOW-DOWN SENSITIVITY
menu 38-OPENING POTENTIOMETER THRESHOLD M1 adjusts the intervention threshold in opening
menu 39-CLOSING POTENTIOMETER THRESHOLD M1 adjusts the intervention threshold in closing
menu 40-OPENING POTENTIOMETER THRESHOLD M2 adjusts the intervention threshold in opening
menu 41-CLOSING POTENTIOMETER THRESHOLD M2 adjusts the intervention threshold in closing
menu 42-POTENTIOMETER DECELERATION THRESHOLD IN OPENING M1
menu 43-POTENTIOMETER DECELERATION THRESHOLD IN CLOSING M1
menu 44-POTENTIOMETER DECELERATION THRESHOLD IN OPENING M2
menu 45-POTENTIOMETER DECELERATION THRESHOLD IN CLOSING M2
9.6 - «POSITION GATE» POTENTIOMETER PARAMETERS SETTING
NOTE 1: For a quick reverse on obstacle it is necessary to decrease the sensitivity parameters
NOTE 2: The sensitivity parameters can also be set in OFF (intervention excluded); in this case the
potentiometer will only work in pulse detection mode (it does not reverse on obstacle)
SEE CHAP. 13
AT THE SAME TIME
9.7 - ACCESS TO THE HIDDEN «DEBUG» MENU FOR POTENTIOMETER
To view the instantaneous speed
values «VP1» and «VP2» (referred to
motor 1 and motor 2) ACCESS THE
H I D D E N « D E B U G » M E N U :
The view of these values allows to
adjust a maximum threshold below
which the potentiometer (or the encoder) intervenes. The maximum threshold can be adjusted through
menus 38 - 39 - 40 - 41 (while the maximum slowdown threshold can be adjusted through menus 42 - 43 -
44 - 45) and must always be higher than the instantaneous speed value shown in VP1 or VP2
10 - ADDITIONAL FUNCTIONS
10.1 - AMPEROMETRIC MANAGEMENT
The control unit is equipped with an obstacle detection system, (working ONLY on ELECTRO-
MECHANICAL OPERATORS) which allows reversing in opening and closing; On electromechanical
operators, the amperometric function is set to OFF by default, but it automatically activates if values
different from OFF are set on menu 37-SLOWDOWN SENSITIVITY.
If the obstacle detection system intervenes in opening, it causes a reverse of the motion for about 2
seconds; If the obstacle detection system intervenes in closing, it causes the partial or total reopening of
the gate depending on the settings on menu 46-CLOSING INVERSION
NOTE: If the 7-PAUSE TIME menu is NOT set to OFF, the «automatic reclosing» function is active: in
case of obstacle, allows the operator to attempt the reclosing for 5 times, then a new START input
will be required to restore the motion
It is possible to adjust the torque value, i.e. the inversion force on obstacle, through the menus:
28/30-MOTOR 1/MOTOR 2 OPENING TORQUE adjustable from 10% to 100%
29/31-MOTOR 1/MOTOR 2 CLOSING TORQUE adjustable from 10% to 100%
NOTE: with high torque values (max.100%), the force required to reverse on obstacle will be greater
It is possible to adjust the sensitivity for each direction (opening or closing) through the menus:
33/35-MOTOR 1/MOTOR 2 OPENING SENSITIVITY
34/36-MOTOR 1/MOTOR 2CLOSING SENSITIVITY
NOTE 1: with high sensitivity values ( max.100%), the inversion on obstacle will occur after 5 seconds
NOTE 2: The sensitivity parameters can also be set in OFF (intervention excluded); in this case the
amperometric management will only work according to the settings of the menu-37
ATTENTION: In case of power failure, when the power is restored the first maneuver will be at high
speed in order to allow the automatic recognition of the mechanical stop
18
Italiano
ENGLISH
International registered trademark n. 804888
10.2 - «I/O SURGE PROTECTOR» CIRCUIT CONNECTION
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1 2 3 4 5 6 7
1 2 3 4 5 6 7
OUTPUT
INPUT
ON
Power ON
03.02
-
-
-
-
UP
1
LANGUAGE
-
-
ON
Power ON
03.02
-
-
UP
1
LANGUAGE
-
-
-
-
UP
UP
DOWN
-
1
-
26
-
1
UP
-
16
OK
12
!
- - - -
- - -
- - -
SEA
SET
MENU
--
-
00111110
-
11111000
LANGUAGE LANGUAGE
-
OP.LEAF DELAY
-
- - -
-
00111110
11111000
00111110
11111000
26
-
GROUND
WIRE
It is possible to connect the «SURGE
PROTECTOR» device, to protect up
to 6 inputs + 24V power supply from
overvoltages due, for example, to the
lightning strikes. Simply connect the
cable of the accessory to be protected
t o t h e I N P U T o f t h e S U R G E
PROTECTOR circuit and then, from
the corresponding number on the
OUTPUT terminal block, connect the
cable to the control unit
NOTE: connect the common and
the power supply negative directly
on the control unit
OUTPUT
CONNECTIONS ON CONTROL UNIT
INPUT
ACCESSORIES CONNECTIONS
24V DC ACCESSORIES
CONTACT 1 (Eg. PHOTOCELL)
CONTACT 2 (Eg. SAFETY EDGE)
CONTACT 3 (Eg. START)
CONTACT 4
CONTACT 5
CONTACT 6
24V DC ACCESSORIES
CONTACT 1 (Eg. PHOTOCELL)
CONTACT 2 (Eg. SAFETY EDGE)
CONTACT 3 (Eg. START)
CONTACT 4
CONTACT 5
CONTACT 6
11 - DISPLAY AND PROGRAMMING
WARNING! MAKE ALL DEVICES CONNECTIONS ON SWITCHED-OFF CONTROL
UNIT BEFORE THE PARAMETERS CONFIGURATION THROUGH DISPLAY
Starting from the software revision 03.02, the
electronic control unit is equipped with the new
BINGO display with different DIAGNOSTICS
symbols. For the old version display functions,
consult the manual of the previous revision
NEW BINGO DISPLAY
FROM SOFTWARE REV 03.02
OLD DISPLAY
PREVIOUS MANUAL
11.1 - SWITCHING ON THE CONTROL UNIT
When a new control unit is powered on, the display shows the software revision first and the INPUT
STATUS after 5 seconds.
If a control unit is already programmed, the display immediatetly shows the INPUT STATUS view
NEW CONTROL
UNIT OR
AFTER RESET
ALREADY
PROGRAMMED
CONTROL UNIT
SOFTWARE
REVISION
SOFTWARE
REVISION
5
SECONDS
INPUT STATUS
(CHAPTER 13)
INPUT STATUS
(CHAPTER 13)
BASIC PROGRAMMING
MENU
BASIC PROGRAMMING
MENU
11.2 - BASIC PROGRAMMING MENU AND SPECIAL MENU
The control unit is equipped with a basic programming menu which can be accessed through the
procedure above indicated when a control unit is switched on. The control unit is also equipped with a
special menu that allows the setting of various parameters and the configuration of the accessories.
To access THE SPECIAL MENU choose one of the following 2 procedures:
SPECIAL MENU SPECIAL MENU
OP.LEAF DELAY
AT THE SAME TIME
FOR 5 SECONDS
SPECIAL MENU
19
12 - BASIC MENU FUNCTIONS
Italiano
ENGLISH
International registered trademark n. 804888
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
Press next Tx button
to be stored
Skip this step if no need Tx programming
Press the TX
button
to be stored
2
TRANSMITTERS
START
3
MOTOR
4
MOTOR
NUMBER
6
LOGIC
7
PAUSE
TIME
8
START IN
PAUSE
9
PROGRAM-
MING
10
TEST
START
1
LANGUAGE
ENGLISH
if
this message
appears
verify the receiver
connection
MISSING
RECEIVER
5
REVERSE
MOTOR
15
END
UP
OK
DOWN
MOVE THROUGH
OR
OK
UP
UP
UP
OK OK
TO CONFIRM AND EXIT
OK
MEMORIZED
!
UP
DOWN
CHOOSE THE MOTOR TYPE THROUGH
OR
OK
UP
DOWN
CHOOSE «1» FOR THE SINGLE LEAF OR «2» FOR
DOUBLE LEAVES BY PRESSING OR
OK
OK
UP
DOWN
CHOOSE «ON» TO REVERSE MOTOR
DIRECTION THROUGH OR
UP
UP
OK
UP
OK
UP
OK
UP
OK
CHOOSE «ON» TO START THE WORKING TIMES
SELF-LEARNING THROUGH
AT THE END OF THE SELF-LEARNING
THE VIEW WILL AUTOMATICALLY
RETURN ON THE MAIN MENU
OK
The gate will perform the following cycle: CLOSE - OPEN - CLOSE
OK
CHOOSE «ON» TO TEST THE START
COMMAND THROUGH
Skip this step if a Tx has already been stored
UP
UP
OK
THE OPERATOR STARTS UP AND
THE VIEW WILL AUTOMATICALLY
RETURN ON THE MAIN MENU
PRESS TO EXIT FROM BASIC MENU AND RETURN
TO THE «INPUT STATUS» VIEW ON THE DISPLAY
OK
OK
Skip these steps to work
in semi-automatic logic
UP
PRESS TO ACCESS
THE SPECIAL MENU
OK
16
SPECIAL
MENU
NOTE
All other parameters have useful default
settings for the 90% of applications; however
they can be set through the special menu
OK
14
RESET
HOLD PRESSED AND A 5 SECONDS COUNT-DOWN
WILL START; AT THE END, THE MESSAGE «INIT» WILL
APPEAR TO CONFIRM THE CONTROL UNIT RESET
OK
UP
UP
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS TO CONFIRM
AND RETURN TO THE
MAIN MENU
OK
PRESS
BUTTON
UP
DOWN
CHOOSE THE DESIRED WORKING
LOGIC THROUGH OR
UP
DOWN
CHOOSE THE AUTOMATIC RE-CLOSING
DELAY THROUGH OR
UP
DOWN
CHOOSE BETWEEN «ON» OR «OFF»
THROUGH OR
UP
DOWN
OR
UP
DOWN
OR
*
*
See chapter 17
before programming
remote controls
20

Other manuals for GATE 2 DG R1B

1

Other SEA Control Unit manuals

SEA USER 1 - 24v DG R1 User manual

SEA

SEA USER 1 - 24v DG R1 User manual

SEA GATE 1 DG R2BF User manual

SEA

SEA GATE 1 DG R2BF User manual

SEA GATE 1 DG R1 User manual

SEA

SEA GATE 1 DG R1 User manual

SEA GATE 1 DG R1 User manual

SEA

SEA GATE 1 DG R1 User manual

SEA SLIDE DG R2F User manual

SEA

SEA SLIDE DG R2F User manual

SEA USER 1 - 24v DG R1 User manual

SEA

SEA USER 1 - 24v DG R1 User manual

SEA USER 1 - 24v DG R1 User manual

SEA

SEA USER 1 - 24v DG R1 User manual

SEA GATE 1 DG R2BF User manual

SEA

SEA GATE 1 DG R2BF User manual

SEA 9521 User manual

SEA

SEA 9521 User manual

SEA USER 1-24V User manual

SEA

SEA USER 1-24V User manual

SEA GATE 1 DG R2BF User manual

SEA

SEA GATE 1 DG R2BF User manual

SEA Orion User manual

SEA

SEA Orion User manual

SEA UNIGATE 1I User manual

SEA

SEA UNIGATE 1I User manual

SEA USER 1 - 24v DG R1 User manual

SEA

SEA USER 1 - 24v DG R1 User manual

SEA GATE 1 DG R2BF User manual

SEA

SEA GATE 1 DG R2BF User manual

SEA SLIDE DG R2F User manual

SEA

SEA SLIDE DG R2F User manual

SEA USER 2 24V DG R1B ALL-IN User manual

SEA

SEA USER 2 24V DG R1B ALL-IN User manual

SEA GATE 1 DG R1 User manual

SEA

SEA GATE 1 DG R1 User manual

SEA GATE 2 - 24V PLUS User manual

SEA

SEA GATE 2 - 24V PLUS User manual

SEA SLIDE NEW MAG User manual

SEA

SEA SLIDE NEW MAG User manual

SEA GATE 1 DG R2BF User manual

SEA

SEA GATE 1 DG R2BF User manual

SEA CUBE R. NW User manual

SEA

SEA CUBE R. NW User manual

SEA PRE-GATE User manual

SEA

SEA PRE-GATE User manual

SEA USER 2 24V DG ALL IN User manual

SEA

SEA USER 2 24V DG ALL IN User manual

Popular Control Unit manuals by other brands

ICP DAS USA MDC-700 Series user manual

ICP DAS USA

ICP DAS USA MDC-700 Series user manual

Edwards GSA-CC1 Installation sheet

Edwards

Edwards GSA-CC1 Installation sheet

Baumuller BM4-O-CAN-06 operating instructions

Baumuller

Baumuller BM4-O-CAN-06 operating instructions

Telit Wireless Solutions BlueMod+S50/AI Hardware user's guide

Telit Wireless Solutions

Telit Wireless Solutions BlueMod+S50/AI Hardware user's guide

Laird MSD50NBT user guide

Laird

Laird MSD50NBT user guide

Vaillant Control Center VR 65 installation instructions

Vaillant

Vaillant Control Center VR 65 installation instructions

Danfoss TS 12.5 installation guide

Danfoss

Danfoss TS 12.5 installation guide

Moen 1225 manual

Moen

Moen 1225 manual

janitza 800-CT8-A User manual and technical data

janitza

janitza 800-CT8-A User manual and technical data

LEGRAND 0 746 85 manual

LEGRAND

LEGRAND 0 746 85 manual

ITR MUPASZ 710 plus user manual

ITR

ITR MUPASZ 710 plus user manual

Carel PCOS00KXN0 user manual

Carel

Carel PCOS00KXN0 user manual

Icop VDX2-6518-E user manual

Icop

Icop VDX2-6518-E user manual

Cadis Aquavision Control user manual

Cadis

Cadis Aquavision Control user manual

Pepperl+Fuchs VAA-2E-G4-SN instruction manual

Pepperl+Fuchs

Pepperl+Fuchs VAA-2E-G4-SN instruction manual

DeZurik VPB V-PORT instruction manual

DeZurik

DeZurik VPB V-PORT instruction manual

Honeywell VC Series installation instructions

Honeywell

Honeywell VC Series installation instructions

White Rodgers 1127 installation instructions

White Rodgers

White Rodgers 1127 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.