ADTRAN OC-48/STM-16 DWDM SFP User manual

jobAid
1
DESCRIPTION
The OC-48/STM-16 DWDM 1559.79nm 80 km SFP (DWDM SFP)
is a full duplex serial electric, serial optic device with both
transmit and receive functions contained in a single module that
provides a high speed serial link at SONET OC-3, OC-12, OC-48,
SDH STM-1, STM-4, STM-16, and GigE rates. The DWDM SFP
operates on Optical Channel 22 (1559.79 nm). When installed in
the appropriate host module, the DWDM SFP provides an optical
interface to the supporting system.
The transmit side of the DWDM SFP converts serial NRZ
electrical data at the line rate to a standard compliant optical
signal. The receive side converts the incoming DC balanced serial
NRZ optical data at the line rate into serial electrical data.
NOTE
To ensure compatibility, refer to the documentation provided
with the host module.
The DWDM SFP supports the following features:
•1559.79 nm optical signals for up to 80 km reach
•Low power consumption (<1.5 W max)
•Bit error rate 10^–12
CAUTION
!
Due to compliance certification requirements, use only SFPs/
XFPs supplied by ADTRAN with the host module. ADTRAN
cannot certify system integrity with other SFP/XFPs.
Small Form-Factor Pluggable
OC-48/STM-16 DWDM 1559.79nm 80 km SFP
OPERATIONAL SPECIFICATIONS
•Channel Spacing: 100 GHz
•Data Rate: 150 Mbps to 2.5 Gbps
•Optical distance: 80 km nominal
•Transmit Wavelength: 1559.79 nm (Channel 22)
•Receive Wavelength: 1525nm to 1565 nm
•Optical transmit levels: 0.0 to +5.0 dBm
•Spectral Width: 0.4 nm (20 dB spectral width)
•Extinction Ratio: 8.2 dB
•Optical receive level: –29.0 dBm to –8.0 dBm
•Receiver Damage Threshold: –5.0 dBm
•Optical Path Penalty: 2.0 dB max
•Minimum Span Attenuation: 13 dB
•Optical Budget: –27 dB
•Dispersion Tolerance: 1600 ps/nm
•Optical connectors: LC
•Environmental Support:
oOperational temperature range: –40°C to +65°C
oStorage temperature range: –40°C to +85°C
oRelative humidity: up to 85%, noncondensing
INSTALLATION
To install the DWDM SFP into an appropriate module, complete
the following steps:
1. Inspect the DWDM SFP. If damaged, file a claim with the
carrier and then contact ADTRAN Customer Support.
CAUTION
!
Do not remove the protective end cap from the SFP until the fiber
optic cable is ready to be connected.
2. Insert the DWDM SFP into the SFP cage on the module.
Ensure that the manufacturer label on the SFP is facing
upward for correct installation.
3. Slide the DWDM SFP all the way into the receptacle until
there is an audible “click.”
NOTE
Use the latch on the DWDM SFP to remove the SFP from the SFP
cage mounted on the printed circuit board.
CLEI: SOOTALWJ__
Product P/N: 1442707G2
Issue Date: October 2011
Document P/N: 61442707G2-22A
Warranty: ADTRAN will replace or repair this product
within the warranty period if it does not meet its
published specifications or fails while in
service. Warranty information can be found
online at www.adtran.com/warranty.
©2011 ADTRAN, Inc. All Rights Reserved.
ADTRAN CUSTOMER CARE:
From within the U.S. 1.800.726.8663
From outside the U.S. +1 256.963.8716
PRICING AND AVAILABILITY 1.800.827.0807
*61442707G2-22A*
C A U T I O N
C A U T I O N
!
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
The DWDM SFP is to be installed in ADTRAN products in
Restricted Access Locations only, and installed by trained service
personnel.
This device complies with Part 15 of the FCC rules. Operation is
subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN
could void the user's authority to operate this equipment.
The DWDM SFP is designed to meet the following environmental
classes:
•ETSI EN 300 019-1-1 “Classification of environmental
conditions; Storage,” Class 1.2
•ETSI EN 300 019-1-2 “Classification of environmental
conditions; Transportation,” Class 2.3
•ETSI EN 300 019-1-3 “Classification of environmental
conditions; Stationary use at weather-protected locations,”
Class 3.3
The equipment is designed to function without degradation
during exposure to all test severities per Class 3.3 of ETSI EN 300
019-1-3.
The OC-48/STM-16 DWDM 1559.79nm 80 km SFP meets EU
RoHS Directive 2002/95/EC and/or applicable exemptions. Refer
to www.adtran.com for further information on RoHS/WEEE.
SAFETY AND REGULATORY COMPLIANCE
WARNING
!
Read all warnings and cautions before installing or servicing this
equipment.
CAUTION
C
This product contains a Class 1 Laser module that complies with
21 CFR 1040.10 and 1040.11 and IEC 60825-1, IEC 60825-2, EN
60825-1 and EN 60825-2. For continued compliance with the
above standards, only approved Class 1 laser modules from an
ADTRAN approved vendor list (located on the ADTRAN
website) should be installed in this product. ADTRAN cannot
certify system integrity with other laser modules.
CAUTION
!
• Electrostatic Discharge (ESD) can damage electronic modules.
When handling modules, wear an antistatic discharge wrist
strap to prevent damage to electronic components. Place
modules in antistatic packing material when transporting or
storing. When working on modules, always place them on an
approved antistatic mat that is electrically grounded.
• Per GR-1089-CORE this product is designed and intended for
installation as part of a Common Bonding Network (CBN).
This product is not designed nor intended for installation as
part of an Isolated Bonding Network (IBN).
• Per GR-1089-CORE Section 9, this product does not have an
internal DC connection between battery return and frame
ground. This product can be installed in a DC-I (isolated) or
DC-C (common) installation. For installations where other
cards or the host system have internal connections between
battery return and frame ground, the system would be
intended for deployment only in a DC-C installation.
• The chassis frame ground terminal must be connected to an
earth ground to ensure that the front panel of the module is
properly grounded via the backplane connector.
NOTE
• The Gigabit Ethernet port(s) are optical and therefore are not
classified as any type of port as defined in Appendix B of GR-
1089-CORE.
• This DWDM SFP is compliant with SFF-8472 “Digital
Diagnostics Monitoring Interface for Optical Transceivers,”
Revision 9.3.
• This DWDM SFP is compliant with the XFP Multi-Source
Agreement (MSA).
• This DWDM SFP is designed to be deployed in GR-3108-CORE
environmental class 1 or 2 as defined in GR-3108-CORE.
The DWDM SFP meets or exceeds all the applicable requirements
of NEBS, Telcordia GR-63-CORE, GR-1089-CORE, and ETSI EN
300368. The DWDM SFP is intended for deployment in Central
Office type facilities, EEEs, EECs, and locations where the NEC
applies (for example, Customer Premises).

This manual suits for next models

1

Other ADTRAN Control Unit manuals

ADTRAN 1200315L1 User manual

ADTRAN

ADTRAN 1200315L1 User manual

ADTRAN NetVanta Octal T1/E1 Wide Module User manual

ADTRAN

ADTRAN NetVanta Octal T1/E1 Wide Module User manual

ADTRAN U-BR1TE Instruction Manual

ADTRAN

ADTRAN U-BR1TE Instruction Manual

ADTRAN SFP GPON ONU User manual

ADTRAN

ADTRAN SFP GPON ONU User manual

ADTRAN 1200065L1-1 User manual

ADTRAN

ADTRAN 1200065L1-1 User manual

ADTRAN ATLAS 800 Series Module QUAD E1 User manual

ADTRAN

ADTRAN ATLAS 800 Series Module QUAD E1 User manual

ADTRAN MX2820 User manual

ADTRAN

ADTRAN MX2820 User manual

ADTRAN 1200068L1 HS Series User manual

ADTRAN

ADTRAN 1200068L1 HS Series User manual

ADTRAN Job Aid+ 1442981G8C User manual

ADTRAN

ADTRAN Job Aid+ 1442981G8C User manual

ADTRAN Job Aid+ 1442910G2 User manual

ADTRAN

ADTRAN Job Aid+ 1442910G2 User manual

ADTRAN 1200791L1 User manual

ADTRAN

ADTRAN 1200791L1 User manual

ADTRAN Total Access 351 Series User manual

ADTRAN

ADTRAN Total Access 351 Series User manual

ADTRAN E220 HFAC HDSL Instruction Manual

ADTRAN

ADTRAN E220 HFAC HDSL Instruction Manual

ADTRAN FXS+ Quad User manual

ADTRAN

ADTRAN FXS+ Quad User manual

ADTRAN 1200222L1 User manual

ADTRAN

ADTRAN 1200222L1 User manual

ADTRAN Job Aid+ 1442910G1 User manual

ADTRAN

ADTRAN Job Aid+ 1442910G1 User manual

ADTRAN Job Aid+ Total Access 5000 1442910G1C User manual

ADTRAN

ADTRAN Job Aid+ Total Access 5000 1442910G1C User manual

ADTRAN Total Access 300 Series User manual

ADTRAN

ADTRAN Total Access 300 Series User manual

ADTRAN Job Aid+ 1442704PG2 User manual

ADTRAN

ADTRAN Job Aid+ 1442704PG2 User manual

ADTRAN Quad T1 User manual

ADTRAN

ADTRAN Quad T1 User manual

ADTRAN Total Access Quad BNC Instruction Manual

ADTRAN

ADTRAN Total Access Quad BNC Instruction Manual

ADTRAN Job Aid+ 1442707G3 User manual

ADTRAN

ADTRAN Job Aid+ 1442707G3 User manual

ADTRAN NetVanta SHDSL User manual

ADTRAN

ADTRAN NetVanta SHDSL User manual

ADTRAN T200 H2TU-R User manual

ADTRAN

ADTRAN T200 H2TU-R User manual

Popular Control Unit manuals by other brands

Philips LCN7700 installation instructions

Philips

Philips LCN7700 installation instructions

LSI LASTEM ALIEM EL03305 user manual

LSI LASTEM

LSI LASTEM ALIEM EL03305 user manual

Franklin Fueling Systems Healy 8701VV manual

Franklin Fueling Systems

Franklin Fueling Systems Healy 8701VV manual

ATEN Altusen PN9108A quick start guide

ATEN

ATEN Altusen PN9108A quick start guide

Omron CS1W-NC113 - REV 02-2008 manual

Omron

Omron CS1W-NC113 - REV 02-2008 manual

LOVATO ELECTRIC EXP10 16 instruction manual

LOVATO ELECTRIC

LOVATO ELECTRIC EXP10 16 instruction manual

Acconeer XM112 Hardware user's guide

Acconeer

Acconeer XM112 Hardware user's guide

FoxESS Mira-HV25 user manual

FoxESS

FoxESS Mira-HV25 user manual

MTT MS3766 user manual

MTT

MTT MS3766 user manual

Velleman K2664 manual

Velleman

Velleman K2664 manual

Leviton Decora Illumatech RTF01-10 installation instructions

Leviton

Leviton Decora Illumatech RTF01-10 installation instructions

Nordson Auto-Flo II Customer product manual

Nordson

Nordson Auto-Flo II Customer product manual

Siemens SIMOTION D4 Series manual

Siemens

Siemens SIMOTION D4 Series manual

CHINT Astronergy CHSM6610M installation manual

CHINT

CHINT Astronergy CHSM6610M installation manual

Unitron Johansson 5951 user manual

Unitron

Unitron Johansson 5951 user manual

Emerson Bettis 2000 Series user manual

Emerson

Emerson Bettis 2000 Series user manual

Red Valve 2600 Series Installation, operation and maintenance manual

Red Valve

Red Valve 2600 Series Installation, operation and maintenance manual

Rohde ST 310 instruction manual

Rohde

Rohde ST 310 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.