Azbil Infilex ZM WY5122 User manual

AB-6439
Azbil Corporation’s controller Infilex series: Infilex is named for “Infinity” and “Flexible”.
1
Specifications/Instructions
InfilexZM
Zone Manager
Model WY5122
General
Infilex ZM (Infilex: named for “Infinity” and “Flexible”) Model
WY5122, integrated into savic-net FXBMS (building
management system), manages remote units (also called
sub-controllers), such as Infilex VC, Infilex FC, and Infilex
SC.
Up to 50 remote units can be connected. Infilex ZM can
control these units separately as well as per group.
Infilex ZM communicates with the savic-netFX center unit
through the transmission trunk line NC-bus and with the
remote units through the transmission trunk line SC-bus.
Features
Compact design:
Small size body ensures space saving.
Installation:
A quick-fit screwless (clamp) terminal block is used for
the communication terminal block of the I/O module,
ensuring the labor saving of the wiring work.
Additionally, either DIN rail mounting or screw mounting
can be selected.
Management of remote units:
Infilex ZM manages up to 50 connected remote units
(Infilex VC, Infilex FC, Infilex SC, etc.), allowing ON/OFF,
failure monitoring, measuring, and setting individually
from the BMS center unit. Infilex ZM can perform such
managements of remote units by group and is applicable
to any group configuration consisting of up to 50 units of
Infilex VC and Infilex FC. Additionally, Infilex ZM
provides flexible management. For example, group
ON/OFF can be commanded even when individual
measuring is commanded.
Risk diversification and high-speed supervision:
Infilex ZM has 50 programs of time schedules, analog
alarm monitoring, and runtime/cycle-count integrating in
order to manage the connected Infilex VC, Infilex FC,
Infilex SC, etc. This achieves diversification of risks and
high-speed supervision of BMS.
One Infilex ZM controls up to 4 sets of VAV (VAV:
variable air volume, controlled by Infilex VC) and AHU
(controlled by Infilex GC). Load reset control of supply
air temperature, fan speed control, interlocking operation
are available. Additionally, the mixing loss control of the
interior VAV and perimeter FCU (fan coil unit) can be
performed.
Support functions:
Infilex ZM supports to adjust VAV by setting the
max./min. air volume levels of all VAV units included in a
specified set. Infilex ZM also supports to adjust
AHU/FCU flow rate and to flush the piping by fully
opening and closing all the valves that the Infilex ZM
controls.
CE Marking certified product:
Infilex ZM Model WY5122W0000 (NC-bus model (Line
A)) conforms to all the applicable standards of CE
Marking (Class A).

AB-6439
2
Safety Instructions
Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual near by for ready
reference.
Usage Restrictions
This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil
Corporation’s sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators.
WARNING
DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product
power supply before performing any wiring.
Be sure to ground with 100 or lower ground resistance. Improper grounding may cause electrical shock or
equipment damages.
Do not detach the terminal cover at any time except when wiring. After wiring, be sure to attach the terminal cover.
Before attaching/detaching the terminal cover, make sure that the wires are not current-carrying to prevent
electrical shock.
Disconnect power before the product replacement to prevent electrical shock.
Wire strip length to be connected to the quick-fit screwless terminal block must be 8 mm. If the strip length is longer
than 8 mm, the conductor will be exposed, causing electrical shock or short circuit between adjacent terminals. If
it is shorter, the conductor will not contact the connector.
Do not disassemble the product. Disassembly may result in electrical shock or equipment damage.
CAUTION
Installation and wiring must be performed by qualified personnel in accordance with all applicable safety
standards.
This product must be operated under the operating conditions (power, temperature, humidity, vibration, shock,
installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages.
All wiring must comply with local codes of indoor wiring and electric installation rules.
Use crimp terminal lugs with insulation for electric wires connected to the screw terminals.
Connect cables to the power source with terminals or the like for permanent connection.
Make sure all the wires are tightly connected to prevent heat generation or equipment damages.
If more than the rated power supply voltage is applied, product replacement is required for safety.
Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel cabinet)
Lightening protection based on the regional characteristics and the building structure is needed to minimize
equipment damages.
Noise protection is necessary when the product is installed in a location close to many noise sources.
Do not block the vent holes on the upper or lower part of the product to prevent equipment damages. Remove
protective sheet after installation and wiring.
After mounting on DIN rail, make sure that the holding parts of all the connected modules are securely fixed on the
DIN rail. The modules may drop from the DIN rail and get damaged due to improper mounting.
Dispose of the lithium battery in accordance with your local regulations.
Dispose of this product in accordance with your local regulations. Do not reuse all or a part of this product.
Trademark information:
Infilex, Neopanel, PARAMATRIX and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries.
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

AB-6439
3
System Configurations
Note:
MIS may be used instead of SMS and DSS for your system. Note that MIS cannot be mixed with SMS or DSS in the same system.
Figure 1. System configuration example
Model Numbers
Model number Description
WY5122 Basic model number
W 100 V AC to 240 V AC power
0000
NC-bus model (Line A)
* CE Marking (Class A) certified
0010
Redundant NC-bus model (Lines A and B)
Parts for Installation
Part number Description
83165861-001 Screw tab
83104567-001 DIN rail mounting bracket
Note:
For mounting Infilex ZM, either the screw tab (for screw mounting) or the DIN rail mounting bracket (for DIN rail mounting) is required. Be
sure to separately order depending on your mounting type.
Client PC
SCS
SMS
InfilexAC
Model WY5117C
InfilexGC
Model WY5111
InfilexGD
Model WY5110
PMX-III
Model WY2001
InfilexZM
Model WY5122
Infilex
FC
Model WY5205
Infilex
VC
Model WY5206
BMIF: Building Multi Air-Conditioning Interface
DIF: DGP (Data Gathering Panel) Interface
DIF-II: DGP Interface-II
DSS: Data Storage Server
MIS: Management Integration Server
NC-bus: New Controller bus
PMX-III: PARAMATRIX-III
SC-bus: Sub Controller bus
SCS: System Core Server
SMS: System Management Server
Neopanel
Model QY7205
(Digital user terminal)
Neoplate Model QY7290
(Analog user terminal)
NC-bus* (Max. 25 units and 500 m, but extendable up to 1000 m with the repeater module.)
SC-bus (Max. 50 units and 1000 m)
BACnetIP
Other connectable units to NC-bus: DIF/DIF-II/BMIF/energy meter
Note that the number of units to be connected must satisfy the following formula.
(Infilex ZM + DIF + DIF-II + BMIF) 5 units number of NC-bus lines
InfilexSC
Model WY5207W
Neopanel
Model QY7205
(Digital user terminal)
DSS
MIS
Neopanel
Model QY7205
(Digital user terminal)
Neoplate Model QY7290
(Analog user terminal)

AB-6439
4
Specifications
Basic specifications
Item Specification
Rated voltage 100 V AC to 240 V AC, 50 Hz/60 Hz
Allowable voltage
range 85 V AC to 264 V AC, 50 Hz/60 Hz
Power shutdown
detection 80 V AC or less
Power consumption 35 VA
(when 50 remote units (sub- controllers) are connected from the Infilex ZM)
Power supply
Leakage current 1 mA or less
Ambient temperature 0 C to 50 C
Ambient humidity 10 %RH to 90 %RH (non-condensing)
Altitude 2000 m or lower
Rated operating
conditions
Vibration Max. 5.9 m/s2 (0.6 G) at 10 Hz to 150 Hz
Ambient temperature -20 C to 60 C
Ambient humidity 5 %RH to 95 %RH (non-condensing)
Vibration for storage Max. 5.9 m/s2 (0.6 G) at 10 Hz to 150 Hz
Environmental
conditions
Transport/
storage conditions Vibration for
transportation Max. 9.8 m/s2 (1 G) at 10 Hz to 150 Hz
Green LED ON: Power ON
Power supply
(POWER) Green LED OFF: Power OFF
Red LED ON: Major failure or system restart
Major failure (ERR1) Red LED OFF: Normal operation
Red LED ON: Minor failure or system restart
Operation
Minor failure (ERR2) Red LED OFF: Normal operation
NC-bus Transmit (TX), Receive (RX)
Communication
SC-bus Transmit (TX), Receive (RX)
LED Flashing ON OFF
POWER ON OFF
NC-bus TX Normal Abnormal
NC-bus RX Normal Abnormal
SC-bus TX Normal Abnormal
SC-bus RX Normal Abnormal
ERR1 Abnormal Normal
LED indication
Description of LED
indication
ERR2 Abnormal Normal
RAM, RTC* Lithium battery backup
Power failure backup Data file Non-volatile memory (flash memory) backup
Transmission system Current transmission
Transmission speed 4800 bps
Transmission distance 500 m
NC-bus
Remote units
(controllers) Max. 25 units connectable
Transmission system Voltage transmission
Transmission speed 4800 bps
Transmission distance 1000 m
Communications
SC-bus
Remote units
(sub-controllers) Max. 50 units connectable
Weight 400 g
Material (housing), color Modified PPE, light gray
Power supply, ground M3 (7.62 mm pitch between terminals)
Terminal block NC-bus communication Quick-fit screwless terminal block
Note:
RTC: Real Time Clock. RTC is backed up by a lithium battery to ensure accurate clocking while the power is OFF.

AB-6439
5
Wiring specifications
Item Wiring Wiring length Condition
Power supply JIS IV2.0 mm2or JIS CVV 2.0 mm2or greater
Ground JIS IV 2.0 mm2or JIS CVV 2.0 mm2or greater Ground resistance: 100 or lower
NC-bus JCS IPEV-S 0.9 mm2500 m
SC-bus LAN cable compliant with EIA/TIA-568 category 3 or over 1000 m
Notes:
As M3 screw terminal block is used for power supply and ground, crimped terminal lug is required for the cable end.
Since a quick-fit screwless terminal block is provided for NC-bus connection, the wires can be connected only by stripping the sheath.
Sheath stripped length: 8 mm (Pin terminal cannot be used.)
Organize the cables with cable binding bands so as not to hide LED, Data Setter connector, ►mark, switch, battery holder, or tag.
JIS: Japanese Industrial Standards
JCS: Japanese Electric Wire and Cable Makers’ Association
CE Marking Conformity
This product must be installed in a panel cabinet. Besides, the product in the panel cabinet must be out of reach of unauthorized
people who are not well-trained for electric facilities.
This product complies with the following Electromagnetic Compatibility (EMC) and the Low Voltage Directive (LVD).
EMC: EN61326-1 Class A, Table 2 (For use in an industrial electromagnetic environment)
LVD : EN61010-1 Overvoltage category II
Pollution degree 2
Input/Output Terminal Arrangement
Figure 2. Input/output and terminal arrangement example
SC-bus
RJ-45 modular jack
100 V AC to 240 V AC
NC-bus Line A
1
2
3
4
TX IN
TX OUT
TX IN
TX Out
(+)
(-)
Shield
Shield
(+)
(-)
(+)
(-)
5
6
7
8
9
10
11
12
NC-bus Line B

AB-6439
6
Dimensions
Figure 3. Dimensions (mm)
140
60 90
8mm
Stripping Length
BATT.
S
-
+
S
~
NC-bus
NC-bus
+
-
CN1
O
3
2
1
POWER
I
SC-bus
ERR1
ERR2
S1
H-MMI
RX
Tx
RX
Tx
6
5
7
8
9
10
SC-bus
E
4
12
11
-
+

AB-6439
7
Parts Identification
Figure 4. Parts identification
Table 1. Indication and operation of operating status LED
LED indication LED operation
Data transmitting NC-bus TX LED: flashing
Data receiving NC-bus RX LED: flashing
Data transmitting SC-bus TX LED: flashing
Data receiving SC-bus RX LED: flashing
Major failure / initializing ERR1: ON
Minor failure / initializing ERR2: ON
Connections of Data Setter (H-MMI)
1) Connection of Data Setter Model QY5111A
No conversion cable is required. Directly insert the male connector of the Data Setter into the female connector provided on
the Infilex ZM main unit.
At this time, hold the male connector with the ◄mark facing left and insert it as the mark points to the ►mark on the Infilex
ZM main unit.
2) Connection of Data Setter Model QY7211A
Convert the D-SUB connector to the mini DIN connector with the conversion cable (Part No. 83104995-001).
At this time, hold the male connector with the ◄mark facing left and insert it as the mark points to the ►mark on the Infilex
ZM main unit.
Figure 5. Connecting Data Setter
Insert the connector as
the two arrows point to
each other.
Power switch
LED for power
ON/OFF
Battery holder
LED for
operating status
S1 switch*
Connector (female)
for Data Setter
Do not press S1 switch.
DIN rail
mounting
hook
8mm
Stripping Length
BATT.
S
-
+
S
~
NC-bus
NC-bus
+
-
CN1
O
3
2
1
POWER
I
SC-bus
ERR1
ERR2
S1
H-MMI
RX
Tx
RX
Tx
6
5
7
8
9
10
SC-bus
E
4
12
11
-
+

AB-6439
8
20 60 20
92
(60)
Duct
Infilex ZM
Duct
(60)
Duct
(122.5)*1(132.5)*1
65 75
(45) 35 140 35 (45)
DIN rail mounting bracket
(for bilateral sides)
Part No. 83104567-001
DIN rail position is shifted
5 mm downward from the
center of Infilex ZM.
DIN rail
Infilex ZM
DIN rail
Hook
Holder
Infilex ZM
Mounting Dimensions
DIN rail mounting
Mount and fix Infilex ZM on DIN rail so that it does not fall from the DIN rail.
Fasten the bilateral sides of Infilex ZM with two DIN rail mounting brackets (Part No. 83104567-001, separate order is required).
Notes:
1 Pitch between upper/lower duct and DIN rail.
2 Hatched area shows the maintenance clearance.
Figure 6. Mounting dimensions: DIN rail mounting (mm)
Direct screw-mounting
When Infilex ZM is mounted with screws, the screw tab (Part No. 83165861-001) is required.
Mount and fix Infilex ZM on the wall with two M4 8 screws.
Lengthwise mounting
Incorrect mounting:
Crosswise*2(face-up)
Notes:
1 Hatched are shows the maintenance space.
2 Do not mount Infilex ZM in crosswise (face-up) direction. Do not mount it with the surface plate facing upward or downward, either.
Figure 7. Mounting dimensions: Direct screw mounting (mm)
DIN rail holder
Pull out the DIN rail holder.
Screw tab
Part No. 83165861-001
To attach the screw tab,
insert the screw tab into
the slit provided on the
rear side of Infilex ZM.
Screw tab
Rear
side
35 140 35
154
20 60 20
*1
Infilex ZM
Vertical direction
Infilex ZM

AB-6439
9
Wiring
Wiring from power supply to terminal block
Attach the crimp terminals for the M3 screw terminal
block to the wire ends, and connect them to the terminal
block.
Wiring to the NC-bus Terminal Block
Since quick-fit screwless terminal block is used for the
NC-bus terminal block, the procedure for wiring is
specified as follows.
1) Strip the wire sheath 8 mm. (The gauge for the strip
length is located at the front lower part of Infilex ZM
main unit. If the stripped part is longer than 8 mm, the
conductor will be exposed, causing electrical shock or
short circuit between adjacent terminals. If it is shorter,
the conductor may not contact the connector.)
2) Make sure that no wire fiber is protruded from the
stripped conductor.
3) Press the button on the terminal block deeply enough
to insert the wire using a slotted screwdriver.
(Maximum button-pressing force is 14 N {1.4 kgf}.)
4) Release the button, and gently pull out the wire to
make sure that it is tightly fastened. (If you pull out the
wire diagonally, it may be disconnected.)
Make sure that no wire fiber is protruded from the
stripped conductor.
Precautions for connected cables
Neatly place the cables connected to Infilex ZM so as
not to hide the parts shown in Fig. 8.
Make sure there is no slack in the wires from the cable
ducts to Infilex ZM.
Figure 8. Connected wires in position
System indication label for the controller number
The indication tag has the system indication label on its
back.
Turn it over and fill in the controller number on the label.
Figure 9. System indication label
Protective sheet
After wiring installation, be sure to peel off the protective
sheet before turning on the power.
1) Adhesive is applied to the sheet approximately 20 mm
from the front edge. Peel off this area.
2) Tear off the sheet along the perforations.
Figure 10. Protective sheet
Tube marker
Since Infilex ZM adopts quick-fit screwless terminal
block for communication, communication cables are
connected to the terminals without crimp terminal lugs.
Therefore, if normal tube markers are used, they may
come off when the cables are disconnected. To prevent
this, use the Flat Tube Marker. It is held on a cable by
friction and thus does not come off easily.
Manufacturer Phoenix Contact
Part name Flat Tube Marker
Part number 5880029
Model TMC-3
Applicable wire size 0.4 mm2to 2 mm2
Package unit 200 m/roll
LED
S1 switch
Connector for
Data Setter
Battery holder
Indication tag
Power switch
LED
Turn over.
Indication tag
1) Peel off the adhesive area.
2) Tear off.

AB-6439
10
Maintenance (Lithium Battery Replacement)
Replace the lithium battery for backup (Part No. 83104934-001) every 5 years.
IMPORTANT:
Only authorized service personnel is allowed to replace the battery.
Do not touch the power supply unit when replacing the battery.
Since the remaining battery capacity cannot be checked by measuring the terminal voltage, be sure to replace
the battery every 5 years.
Replace the lithium battery with the power ON.
Replace the lithium battery every 5 years if the product is always in use (in ON state).
If the product has never or hardly been operated (in OFF state) for a year, replace the lithium battery before the
product operation.
Battery replacement
Replace the battery with the Infilex ZM in ON state.
Figure 11. Battery replacement
1) Pull out the battery holder using a slotted screwdriver.
2) Disconnect the connector and detach the lithium battery from the battery holder.
3) Place a new lithium battery in the battery holder and connect the connector to it.
4) Insert the battery holder into the main unit.
5) Fill in the date for next replacement (5 years after the replacement) on the tag using an oil-based pen.
1)
4)
Lithium battery
for backup
2)
3) Infilex ZM
main body
Battery holder Battery Connector
5)

AB-6439
11
Protective sheet
Battery label
on the Indication tag
Precautions for Use
Do not mount the product under the conditions of high temperature and humidity.
Do not drop the product.
For the wire replacement, be sure to shut down the power. (Disconnect the wiring between the power supply and the
product power terminals.)
Before turning on the power, make sure that the wires are correctly connected.
Several tens of seconds are required for the product normal operation after the power is turned on. During this time, the red
LED “ERR1” (major failure) on the front lights up indicating major failure temporarily, but this does not indicate an error.
Do not connect wires to vacant terminals.
Leave at least 35 mm clearance between the top/bottom surfaces of the product and other devices.
Peel off the protective sheet on the top surface of the product before turning ON the power.
(See Figs. 10 and 12.)
Figure 12. Battery label on the indication tag and protective sheet

AB-6439
Specifications are subject to change without notice.
Building Systems Company
http://www.azbil.com/
Rev.8.0 Sep. 2015 AB-6439 H (W03)
(J: AI-6439 Rev. 4.2) Printed in Japan.
12
Table of contents
Other Azbil Controllers manuals

Azbil
Azbil AUR890 Series User manual

Azbil
Azbil SDC15 User manual

Azbil
Azbil Micro Flow MQV9020 User manual

Azbil
Azbil SDC26 Instruction Manual

Azbil
Azbil C15 User manual

Azbil
Azbil BC-R35 Series User manual

Azbil
Azbil BC-R25 Series User manual

Azbil
Azbil Infilex WY5317C User manual

Azbil
Azbil C26 User manual

Azbil
Azbil SDC45 User manual

Azbil
Azbil Infilex VC User manual

Azbil
Azbil Infilex AC WY5117C1 Series User manual

Azbil
Azbil C1M User manual

Azbil
Azbil SDC35 Instruction Manual

Azbil
Azbil DCP31 User manual

Azbil
Azbil C36 User manual

Azbil
Azbil SLPC1F User manual

Azbil
Azbil KFPA User manual

Azbil
Azbil C25 User manual

Azbil
Azbil RA890G User manual