manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Circuit Breaker
  8. •
  9. GE AK-4-75 User manual

GE AK-4-75 User manual

MAINTENANCE
MANUAL
(
SUPPLEMENT
)
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
labl
-
8
b
135
B
Supplement
to
GEK
-
7303
This
manual
when
used
in
conjunction
with
Publication
GEK
-
7303
(
Maintenance
Manual
for
the
AK
-
50
,
75
&
100
frame
breakers
)
provides
maintenance
instructions
on
the
breaker
models
and
trip
devices
tabu
-
lated
below
.
Breaker
Type
&
Mounting
Trip
Device
Type
Frame
Size
(
Amp
)
ECS
SST
Stationary
Drawout
AK
-
4
-
75
,
75
C
AK
-
4
A
-
75
,
75
C
X
3000
AK
-
5
A
-
75
,
75
C
AK
-
5
-
75
,
75
C
X
AK
-
4
A
-
100
X
AK
-
4
-
100
4000
AK
-
5
A
-
100
X
AK
-
5
-
100
*
%
#
m
m
vU
:
»
A
”
I
v
V
AK
-
5
A
-
75
Rear
View
•
'
/
%
GENERAL
W
ELECTRIC
Courtesy of NationalSwitchgear.com
PUSH
TO
RESET
\
SHORT
TIME
«
NST
.
PICKUP
GROUND
r
V
FIG
.
1
.
SST
Programmer
Unit
CONTENTS
3
Introduction
3
Type
SST
Overcurrent
Trip
Device
Components
Trip
Characteristics
Flux
Shift
Trip
Device
Troubleshooting
SST
Test
Set
TAK
-
TS
1
False
Tripping
(
Ground
Fault
)
...
Replacement
of
Current
Sensors
.
Cabling
Diagrams
Ground
Fault
Defeat
Cable
3
6
7
10
10
11
1 1
12
13
14
Type
ECS
Overcurrent
Trip
Device
Components
Trip
Characteristics
Cabling
Diagram
14
15
15
16
ECS
&
SST
Time
-
Current
Curves
2
Courtesy of NationalSwitchgear.com
MAINTENANCE
MANUAL
SUPPLEMENT
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
TM
TM
TYPES
AK
-
75
/
100
WITH
ECS
AND
SST
TRIP
DEVICES
INTRODUCTION
TYPE
SST
OVERCURRENT
TRIP
DEVICE
The
SST
is
a
solid
-
state
,
direct
-
acting
,
self
-
pow
-
ered
trip
device
system
.
Referring
to
Figures
l
through
8
,
it
comprises
the
following
individual
com
-
ponents
:
Programmer
Unit
—
provides
the
comparison
basis
for
overcurrent
detection
and
delivers
the
energy
necessary
to
trip
the
breaker
.
Contains
the
electronic
circuitry
for
the
various
trip
elements
.
Their
associ
-
ated
pickup
and
time
delay
adjustments
(
set
-
points
)
are
located
on
the
face
plate
.
Depending
on
the
ap
-
plication
,
programmer
units
may
be
equipped
with
various
combinations
of
Long
Time
,
Short
Time
,
In
-
stantaneous
and
Ground
Fault
trip
elements
.
See
Table
1
for
available
ratings
,
settings
and
trip
char
-
acteristics
.
The
data
in
this
supplement
pertain
to
AK
-
75
and
AK
-
100
frame
breakers
equipped
with
type
ECS
and
SST
solid
-
state
trip
devices
.
The
latter
are
not
treated
in
the
primary
maintenance
manual
(
publica
-
tion
GEK
-
7303
)
covering
these
breaker
frame
sizes
.
In
scope
,
this
supplement
supplies
the
essential
descriptive
and
instructional
material
applicable
to
the
new
trip
devices
.
Although
breakers
so
equipped
carry
new
type
designations
(
AK
-
4
/
4
A
and
AK
-
5
/
5
A
)
,
the
basic
breakers
and
their
other
accessory
devices
are
identical
to
those
equipped
with
Power
Sensor
or
EC
trip
devices
.
Accordingly
,
the
general
operational
and
maintenance
information
contained
in
publication
GEK
-
7303
is
equally
relevant
to
ECS
or
SST
equipped
breakers
and
is
not
duplicated
here
.
In
the
event
that
a
programner
set
knob
is
Note
:
left
untightened
,
the
trip
function
reverts
to
operation
at
its
minimum
or
maximum
set
point
value
as
follows
:
Unless
otherwise
noted
,
the
contents
of
this
sup
-
plement
are
to
be
interpreted
as
applicable
to
both
the
AK
-
75
and
AK
-
100
frames
.
Except
for
the
pro
-
grammer
and
'
sensor
differences
noted
below
,
the
hardware
elements
(
e
.
g
.
,
cabling
,
flux
shift
trip
actua
-
tors
and
linkage
)
and
the
test
/
adjustment
procedures
are
identical
.
Pickup
Delay
Trip
Element
Min
.
,
Min
.
Max
.
Max
.
Long
Time
X X
Examples
:
Programmer
units
without
the
Ground
Fault
element
are
identical
;
with
Ground
Fault
,
however
,
the
programmers
have
different
pickup
ranges
.
Sensor
tap
rat
-
ings
also
differ
for
each
frame
.
Short
Time
X
X
Instantaneous
X
Ground
Fault
X
X
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contin
-
gency
to
be
met
in
connection
with
installation
,
operation
or
maintenance
.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
purchaser
’
s
purposes
,
the
matter
should
be
referred
to
the
General
Electric
Company
.
3
Courtesy of NationalSwitchgear.com
n
The
SST
programmer
units
can
be
optionally
equipped
with
trip
indicators
(
targets
)
.
These
are
pop
-
out
,
mechanically
-
resettable
plungers
located
across
the
top
of
the
programmers
front
.
Units
with
a
ground
fault
element
employ
three
(
3
)
targets
:
from
left
to
right
,
the
first
is
for
overload
,
the
second
for
short
circuit
(
actuated
by
the
short
time
and
instan
-
taneous
elements
)
and
the
third
for
ground
fault
.
The
latter
is
omitted
on
units
without
ground
fault
.
0
i
r
i
SOLID
STATE
SWITCH
•
•
FLUX
SHIFT
-
TRIP
COIL
CURRENT
SENSOR
*
"
*
I
TAP
I
I
CHANGER
0
0
-
4
OVERLOAD
Y
I
TARGET
J
LONG
TIME
DELAY
i
TTT
I
T
0
i
LONG
SHORT
TIME
PICKUP
&
DELAY
LOGIC
I
0
’
TIME
Each
target
pops
out
when
its
associated
trip
ele
-
ment
operates
to
trip
the
breaker
.
After
a
trip
,
the
popped
target
must
be
reset
by
hand
.
However
,
ne
-
glecting
to
reset
does
not
affect
normal
operation
of
any
trip
element
or
prevent
the
breaker
from
being
reclosed
.
NEUTRAL
“
OR
”
PICKUP
f
3
(
)
i
I
SHORT
CIRCUIT
TARGET
SL
JL
I
DIFFERENTIAL
TRANSFORMER
_
INSTANTANEOUS
PICKUP
I
J
/
WHEN
\
t
USED
/
GROUND
TARGET
I
GROUND
FAULT
PICKUP
&
DELAY
REGULATED
40
VDC
POWER
SUPPLY
Current
Sensors
—
each
pole
mounts
a
single
sensor
coil
(
CT
)
which
supplies
the
power
and
signal
inputs
necessary
to
operate
the
trip
system
.
Each
sensor
has
four
taps
which
provide
field
adjustment
of
the
trip
device
’
s
continuous
ampere
rating
.
J
I
PROGRAMMER
UNIT
Fig
.
2
.
SST
Block
diagram
The
SST
Ground
Fault
trip
element
operates
on
the
principle
that
the
instantaneous
values
of
current
in
the
three
conductors
(
four
on
4
-
wire
systems
)
add
to
zero
unless
ground
current
exists
.
On
SST
’
s
equipped
with
Ground
Fault
,
the
ground
trip
signal
is
developed
by
connecting
each
phase
sensor
in
se
-
ries
with
a
companion
primary
winding
on
a
ground
differential
transformer
mounted
in
the
programmer
unit
.
Its
secondary
output
is
zero
as
long
as
there
is
no
ground
current
.
When
used
,
the
neutral
sensor
(
fig
.
6
)
is
separately
mounted
in
the
bus
or
cable
compartment
of
the
switchgear
.
In
drawout
construction
,
its
output
is
au
-
tomatically
connected
to
the
breaker
via
secondary
disconnect
blocks
.
See
Figs
.
4
,
5
and
15
.
Application
of
the
Ground
Fault
element
to
4
-
wire
systems
with
neutral
grounded
at
the
transformer
re
-
quires
an
additional
,
separately
mounted
sensor
(
Fig
.
6
)
inserted
in
the
neutral
conductor
;
its
secondary
is
connected
to
a
fourth
primary
winding
on
the
ground
differential
transformer
.
See
Fig
.
15
.
This
“
fourth
-
wire
”
neutral
sensor
is
an
electrical
duplicate
of
the
phase
sensor
,
including
taps
.
Therefore
,
when
taps
are
changed
on
the
phase
sensors
,
those
on
the
neu
-
tral
sensor
must
be
correspondingly
positioned
.
Flux
Shift
Trip
Device
—
a
low
-
energy
,
elec
-
tromagnetic
device
which
,
upon
receipt
of
a
trip
sig
-
nal
from
the
programmer
unit
,
trips
the
breaker
by
actuating
the
trip
shaft
.
See
Fig
.
8
.
COMPONENT
LOCATION
All
components
except
the
neutral
sensor
are
mounted
on
the
circuit
breaker
.
The
phase
sensors
are
mounted
around
the
lower
studs
at
the
rear
of
the
breaker
(
see
Fig
.
4
)
.
The
programmer
unit
and
the
flux
shift
trip
device
are
mounted
on
the
breaker
’
s
front
frame
.
These
components
are
interconnected
by
wiring
harness
and
disconnect
plugs
as
shown
on
the
cabling
diagrams
(
Figs
.
13
and
14
)
.
/
Fig
.
3
.
SST
phase
sensor
with
tap
board
4
Courtesy of NationalSwitchgear.com
connector
Tap
terminal
board
Shorting
strap
Fig
.
5
.
Neutral
sensor
secondary
disconnect
block
(
equipment
mounted
)
.
Fig
.
6
.
SST
neutral
sensor
(
equipment
mounted
)
5
Courtesy of NationalSwitchgear.com
Fig
.
7
.
AK
-
5
A
-
100
(
front
view
)
TABLE
1
—
SST
TRIP
CHARACTERISTICS
SST
PROGRAMMER
ADJUSTMENT
RANGE
(
Set
Points
)
Sensor
Ampere
Taps
Long
Time
Short
Time
Ground
Fault
Frame
Size
(
Amperes
)
Instantaneous
Pickup
Breaker
Type
Pickup
(
=
L
)
Time
Delay
Band
®
(
Seconds
)
Pickup
Time
Delay
Band
®
(
Seconds
)
Pickup
©
Time
Delay
Band
®
(
Seconds
)
©
©
©
©
(
X
)
Multiple
Multiple
Multiple
Multiple
of
X
of
L
of
L
of
X
1200
,
1600
,
2000
,
3000
AK
-
75
3000
Maximum
3
,
4
,
5
,
6
,
8
,
10
(
L
)
-
or
-
1.75
,
2
,
2.25
,
2.5
,
3
*
4
(
L
)
Maximum
0.35
Intermed
.
0.21
Minimum
0.095
.
20
,
.
22
,
.
25
.
30
,
.
35
,
.
4
(
X
)
Maximum
0.30
Intermed
.
0.165
Minimum
0.065
22
.
6
,
.
7
,
.
8
,
.
9
,
1.0
,
1.1
(
X
)
Intermed
.
4
,
5
,
6
,
8
,
10
,
12
(
L
)
/
10
4000
1600
,
2000
,
3000
,
4000
AK
-
100
Minimum
.
18
,
.
20
,
.
22
,
.
25
,
.
27
,
.
30
(
X
)
4
©
X
=
Sensor
ampere
tap
=
trip
rating
©
Pickup
tolerance
is
±
10
%
©
Time
delay
at
lower
limit
of
band
@
6
L
.
®
Time
delay
at
lower
limit
of
band
.
V
(
See
pages
17
and
19
for
applicable
time
-
current
curves
)
6
Courtesy of NationalSwitchgear.com
Flux
shift
trip
device
Fig
.
8
.
AK
-
5
A
-
75
(
front
view
)
“
reset
”
position
.
Loosen
the
jam
nut
,
rotate
the
ad
-
juster
end
until
the
proper
gap
is
attained
,
then
re
-
tighten
the
jam
nut
.
While
operating
the
breaker
,
insure
that
the
actua
-
tor
bracket
does
not
interfere
with
the
buffer
stud
.
Adjust
if
necessary
.
FLUX
SHIFT
TRIP
DEVICE
The
mounting
arrangement
of
this
component
is
il
-
lustrated
in
Figures
8
,
9
and
10
.
An
electromagnetic
actuator
mounted
to
the
left
side
of
the
front
frame
is
coupled
to
the
breaker
’
s
trip
shaft
via
a
trip
rod
driven
by
the
actuator
arm
.
The
actuator
is
a
sole
-
noid
whose
armature
is
spring
-
loaded
and
held
in
its
normal
(
reset
)
position
by
a
permanent
magnet
.
In
this
state
the
spring
is
in
tension
.
The
actuator
is
a
sealed
,
factory
-
set
device
and
re
-
quires
no
maintenance
or
field
adjustment
.
In
case
of
malfunction
,
the
complete
actuator
unit
should
be
re
-
placed
.
When
making
the
electrical
connection
to
the
replacement
unit
,
it
is
recommended
that
the
breaker
harness
be
cut
at
some
convenient
point
and
the
new
actuator
leads
solder
-
spliced
thereto
.
An
alternate
method
is
to
untie
the
breaker
harness
and
remove
the
old
actuator
leads
directly
from
the
female
AMP
connector
on
the
end
of
the
breaker
harness
.
How
-
ever
,
AMP
extraction
tool
Cat
.
No
.
305183
is
re
-
quired
for
this
method
.
As
long
as
the
actuator
remains
in
the
reset
posi
-
tion
,
the
breaker
can
be
closed
and
opened
normally
at
will
.
However
,
when
a
closed
breaker
receives
a
trip
signal
from
the
programmer
unit
,
the
actuator
is
energized
and
its
solenoid
flux
opposes
the
magnet
,
allowing
the
spring
to
release
the
armature
;
this
drives
the
trip
rod
against
the
trip
shaft
paddle
,
trip
-
ping
the
breaker
.
As
the
breaker
opens
,
the
actuator
arm
is
returned
to
its
normal
(
reset
)
position
via
linkage
driven
by
a
bracket
attached
to
the
breaker
’
s
crossbar
.
The
per
-
manent
magnet
again
holds
the
armature
captive
in
readiness
for
the
next
trip
signal
.
See
Fig
.
9
.
CAUTION
:
IN
THE
EVENT
THAT
THE
SST
TRIP
DEVICE
MUST
BE
RENDERED
IN
-
OPERATIVE
TO
ALLOW
THE
BREAKER
TO
CARRY
CURRENT
WITHOUT
BENEFIT
OF
OVERCURRENT
PROTECTION
,
THE
RECOMMENDED
METHOD
IS
TO
SHORTEN
THE
TRIP
ROD
BY
TURNING
ITS
ADJUSTER
END
FULLY
CLOCKWISE
.
THIS
PREVENTS
ACTUATION
OF
THE
TRIP
SHAFT
PADDLE
.
The
trip
device
requires
one
basic
adjustment
—
the
trip
rod
length
.
As
shown
in
Fig
.
11
,
the
clearance
between
the
trip
rod
end
and
the
trip
shaft
paddle
is
gaged
by
a
.
093
"
dia
.
rod
.
To
adjust
,
open
the
breaker
and
restore
the
breaker
mechanism
to
its
7
Courtesy of NationalSwitchgear.com
BUFFER
STUD
ACTUATOR
BRACKET
Flux
shift
trip
device
—
reset
linkage
attachment
1
.
Actuator
2
.
Actuator
arm
3
.
Trip
rod
4
.
Trip
rod
adjuster
end
5
.
Reset
linkage
6
.
Actuator
bracket
7
.
Mounting
base
/
Flux
shift
trip
device
with
operating
linkages
8
Courtesy of NationalSwitchgear.com
CROSSBAR
(
BKR
.
OPEN
)
/
ACTUATOR
BRACKET
BUFFER
STUD
POSITION
O
/
T
?
TRIP
PADDLE
IN
“
MECHANISM
RESET
’’
POSITION
//
/
JAM
<
9
p
NUT
A
(
B
/
/
/
/
/
/
/
.
093
"
DIA
.
TRIP
ROD
IN
“
RESET
POSITION
ROD
i
J
ADJUSTER
END
Fig
.
11
.
Flux
shift
trip
device
adjustments
SIDE
VIEW
1
.
Trip
rod
length
:
Adjust
gap
to
0.093
"
±
0.015
"
using
0.093
"
diam
.
rod
as
shown
.
2
.
Actuator
bracket
:
As
the
crossbar
travels
between
the
breaker
closed
’’
and
“
breaker
open
”
positions
,
the
tang
of
the
actuator
bracket
must
clear
the
buffer
stud
.
If
in
-
sufficient
clearance
exists
,
loosen
it
’
s
two
mounting
screws
and
rotate
the
bracket
clockwise
to
take
up
mounting
hole
slack
.
Retighten
screws
.
(
i
9
Courtesy of NationalSwitchgear.com
a
.
testing
two
poles
of
the
breaker
in
se
-
nes
or
,
b
.
Using
the
Ground
Fault
Defeat
Cable
as
shown
in
Fig
.
16
.
This
special
test
cable
energizes
all
the
primary
windings
of
the
differential
transformer
in
a
self
-
cancell
-
ing
,
series
-
parallel
connection
so
that
its
secondary
output
is
always
zero
.
TROUBLESHOOTING
When
malfunctioning
is
suspected
,
tne
first
step
in
troubleshooting
is
to
examine
the
circuit
breaker
and
its
power
system
for
abnormal
conditions
such
as
:
a
.
Breaker
tripping
in
proper
response
to
over
-
currents
or
incipient
ground
faults
.
b
.
Breaker
remaining
in
a
trip
-
free
state
due
to
mechanical
interference
along
its
trip
shaft
.
c
.
Inadvertent
shunt
trip
activations
.
Test
the
components
of
the
SST
system
using
portable
Test
Set
type
TAK
-
TS
1
(
Fig
.
12
)
.
The
applicable
test
procedures
are
detailed
in
In
-
struction
Book
GEK
-
64454
and
are
summarized
below
.
2
.
WARNING
:
DO
NOT
CHANGE
TAPS
ON
THE
CURRENT
SENSORS
OR
ADJUST
THE
PROGRAMMER
UNIT
SET
KNOBS
WHILE
THE
BREAKER
IS
CARRYING
CURRENT
.
USING
THE
SST
TEST
SET
Once
it
has
been
established
that
the
circuit
breaker
can
be
opened
and
closed
normally
from
the
test
position
,
attention
can
be
directed
to
the
trip
de
-
vice
proper
.
Testing
is
performed
by
either
of
two
methods
:
The
TAK
-
TS
1
Test
Set
is
a
portable
instrument
designed
for
field
-
checking
the
time
-
current
charac
-
teristics
and
pickup
calibration
of
the
SST
’
s
various
trip
elements
.
It
can
verify
the
ability
of
the
Flux
-
Shift
Trip
Device
to
trip
the
breaker
and
,
in
addi
-
tion
,
includes
means
for
continuity
checking
the
phase
sensors
.
1
.
Conduct
high
-
current
,
single
phase
tests
on
the
breaker
using
a
high
current
-
low
voltage
test
set
.
WARNING
:
BEFORE
CONNECTING
THE
TEST
SET
TO
THE
BREAKER
TRIP
DEVICE
SYSTEM
,
ENSURE
THAT
THE
CIRCUIT
BREAKER
IS
COMPLETELY
DISCON
-
NECTED
FROM
ITS
POWER
SOURCE
.
ON
DRAWOUT
EQUIPMENT
,
RACK
THE
BREAKER
TO
ITS
DISCONNECTED
POSI
-
TION
.
VERIFY
THAT
THE
BREAKER
IS
TRIPPED
.
t
NOTE
:
For
these
single
-
phase
tests
,
spe
-
cial
connections
must
be
employed
for
SST
breakers
equipped
with
Ground
Fault
.
Any
single
-
phase
input
to
the
ground
differential
transformer
will
gener
-
ate
an
unwanted
"
ground
fault
”
output
signal
which
will
trip
the
breaker
.
This
can
be
nullified
either
by
:
/
Fig
.
12
.
SST
/
ECS
test
set
,
CAT
.
NO
.
TAK
-
TS
1
10
Courtesy of NationalSwitchgear.com
If
nuisance
tripping
is
encountered
on
any
breaker
whose
SST
components
have
previously
demon
-
strated
satisfactory
performance
via
the
TAK
-
TS
1
Test
Set
,
the
sensors
and
their
connections
should
be
closely
scrutinized
.
After
disconnecting
the
breaker
from
all
power
sources
,
Either
of
two
test
modes
may
be
employed
:
“
A
"
—
Programmer
Unit
Only
.
These
tests
are
con
-
ducted
with
the
programmer
unit
disconnected
from
the
breaker
.
During
test
,
the
unit
can
remain
at
-
tached
to
the
breaker
or
may
be
completely
removed
from
it
.
a
.
Check
that
all
phase
sensors
are
the
same
type
(
ampere
range
)
.
b
.
Insure
that
the
tap
settings
on
all
3
phase
sen
-
sors
are
identical
.
c
.
Verify
that
the
harness
connections
to
the
sen
-
sors
meet
the
polarity
constraints
indicated
by
the
cabling
diagram
,
i
.
e
.
,
white
wire
to
COM
-
MON
,
black
wire
to
TAP
.
d
.
On
Ground
Fault
breakers
serving
4
-
wire
loads
,
check
that
the
neutral
sensor
is
properly
connected
(
see
cabling
diagram
Fig
.
15
)
.
In
particular
,
1
.
Verify
that
the
neutral
sensor
has
the
same
rating
and
tap
setting
as
the
phase
sensors
.
2
.
Check
continuity
between
the
neutral
sensor
and
its
equipment
-
mounted
secondary
dis
-
connect
block
.
Also
check
for
continuity
from
the
breaker
-
mounted
neutral
secondary
disconnect
block
through
the
female
harness
connector
(
terminals
L
and
N
)
.
3
.
If
the
breaker
’
s
lower
studs
connect
to
the
supply
source
,
then
the
neutral
sensor
must
have
its
“
LOAD
”
end
connected
to
the
source
.
4
.
Insure
that
the
neutral
conductor
is
carrying
only
that
neutral
current
associated
with
the
breaker
’
s
load
current
(
neutral
not
shared
with
other
loads
)
.
e
.
If
the
preceding
steps
fail
to
identify
the
prob
-
lem
,
then
the
sensor
resistances
should
be
mea
-
sured
.
Since
the
phase
and
neutral
sensors
are
electrically
identical
,
their
tap
-
to
-
tap
resistances
should
closely
agree
.
CAUTION
:
NEVER
DISENGAGE
THE
HARNESS
CONNECTOR
FROM
THE
PROGRAMMER
UNIT
ON
A
BREAKER
THAT
IS
ENERGIZED
AND
CARRYING
LOAD
CURRENT
.
THIS
WILL
OPEN
-
CUR
-
CUIT
THE
CURRENT
SENSORS
,
ALLOW
-
ING
DANGEROUS
AND
DAMAGING
VOLTAGES
TO
DEVELOP
.
Test
scope
:
1
.
Verify
the
time
-
current
characteristics
and
pickup
calibration
of
the
various
trip
elements
.
2
.
Verify
operation
of
the
SST
target
indicators
on
programmer
units
so
equipped
.
“
B
”
—
Complete
Trip
Device
System
.
For
these
tests
,
the
programmer
unit
must
be
mounted
on
the
breaker
and
connected
to
its
wiring
harness
.
Test
scope
:
1
.
All
“
A
”
tests
previously
described
,
plus
provi
-
sion
for
optionally
switching
the
programmer
’
s
out
-
put
to
activate
the
Flux
-
Shift
Trip
Device
and
verify
its
operation
by
physically
tripping
the
breaker
.
2
.
Check
phase
sensor
continuity
.
In
the
event
that
any
component
of
the
SST
sys
-
tem
does
not
perform
within
the
limits
prescribed
in
test
instructions
GEK
-
64454
,
it
should
be
replaced
.
FALSE
TRIPPING
-
BREAKERS
EQUIPPED
WITH
GROUND
FAULT
When
nuisance
tripping
occurs
on
breakers
equipped
with
the
Ground
Fault
trip
element
,
a
probable
cause
is
the
existence
of
a
false
“
ground
”
signal
.
As
indicated
by
the
cabling
diagram
of
Fig
.
14
,
each
phase
sensor
is
connected
in
series
with
a
primary
winding
on
the
Ground
Fault
differential
transformer
.
Under
no
-
fault
conditions
on
3
-
wire
load
circuits
,
the
currents
in
these
three
windings
add
to
zero
and
no
ground
signal
is
developed
.
This
current
sum
will
be
zero
only
if
all
three
sensors
have
the
same
electrical
characteristics
.
If
one
sen
-
sor
differs
from
the
others
(
i
.
e
.
,
different
rating
or
wrong
tap
setting
)
,
the
differential
transformer
can
produce
output
sufficient
to
trip
the
breaker
.
Sim
-
ilarly
,
discontinuity
between
any
sensor
and
the
pro
-
grammer
unit
can
cause
a
false
trip
signal
.
REPLACEMENT
OF
CURRENT
SENSORS
Phase
sensors
are
removed
as
follows
(
see
Fig
.
4
)
:
1
.
From
front
of
breaker
,
disconnect
the
harness
wiring
from
the
sensor
tap
board
.
2
.
From
rear
of
breaker
,
unbolt
the
tap
board
;
loosen
and
remove
the
stud
connector
;
the
sensor
and
tap
board
can
now
be
removed
as
a
unit
.
3
.
Reassemble
in
reverse
order
,
taking
care
to
al
-
ign
projections
on
rear
of
sensor
with
notches
in
po
-
sitioning
ring
mounted
on
stud
.
11
Courtesy of NationalSwitchgear.com
<
?
A
<
j
>
B
<
|
»
C
PROGRAMMER
UNIT
BREAKER
_
^
^
BACK
FRAME
|
JT
F
H
>
=
o
=
>
=
o
=
>
=
r
FLUX
SHIFT
TRIP
DEVICE
B
RED
(
48
V
.
dc
)
(
TO
SCR
ANODE
)
<
>
-
<
BLACK
o
-
-
<
9
E
LEFT
POLE
CURRENT
SENSOR
COM
WHITE
o
-
-
<
A
I
C
BLACK
o
-
-
<
I
TAP
WHITE
A
o
-
<
\
lh
D
F
BLACK
I
WHITE
B
o
-
-
<
H
K
BLACK
o
~
“
<
I
C
7
\
/
\/
\
/
TYT
HARNESS
CONNECTOR
(
AMP
201298
-
1
)
PROGRAMMER
CONNECTOR
(
AMP
201297
-
1
)
LOAD
Fig
.
13
.
Cabling
Diagram
-
SST
without
Ground
Fault
$
A
$
B
<
J
>
C
PROGRAMMER
UNIT
AAA
BREAKER
_
,
BACK
FRAME
|
T
[
1
1
)
=
=
oA
=
oAr
FLUX
SHIFT
TRIP
DEVICE
B
RED
(
48
V
.
dc
)
(
TO
SCR
ANODE
)
O
-
-
<
BLACK
o
-
-
<
I
E
LEFT
POLE
CURRENT
SENSOR
COM
WHITE
o
-
-
<
A
I
3
c
BLACK
TAP
WHITE
A
o
-
-
<
D
3
BLACK
I
WHITE
B
H
3
K
BLACK
c
L
7
o
\
/
\
/
\
/
TTY
HARNESS
CONNECTOR
^
(
AMP
201298
-
1
)
N
o
V
/
LOAD
PROGRAMMER
CONNECTOR
(
AMP
201297
-
1
)
with
Ground
Fault
on
3
-
wire
load
.
Fig
.
14
.
Cabling
Diagram
-
SST
12
Courtesy of NationalSwitchgear.com
4
>
A
6
B
<
i
>
c
PROGRAMMER
UNIT
&
A
A
T
“
frt
.
.
FLUX
SHIFT
TRIP
DEVICE
BREAKER
BACK
FRAME
|
B
RED
I
(
48
V
.
dc
)
(
TO
SCR
ANODE
)
o
-
^
<
BLACK
o
-
-
<
I
E
I
LEFT
POLE
CURRENT
SENSOR
|
COM
WHITE
A
I
I
3
c
BLACK
NEUTRAL
I
TAP
WHITE
I
i
A
o
-
<
\
l h
D
I
3
F
BLACK
NEUTRAL
I
SENSOR
DISCONNECT
I
o
<
^
“
-
O
I
WHITE
B
o
-
<
I
H
-
-
I
3
I
K
BLACK
/
/
LINE
I
C
/
COM
WHITE
o
-
»
-
o
/
o
—
-
o
N
BLACK
o
^
C
<
-
-
o
TAP
IN
I
LOAD
|
\
/
\
/
\
/
TTT
T
HARNESS
CONNECTOR
(
AMP
201298
-
1
)
PROGRAMMER
CONNECTOR
(
AMP
201297
-
1
)
i
EQUIPMENT
—
MOUNTED
NEUTRAL
SENSOR
4
-
WIRE
LOAD
Fig
.
15
.
Cabling
Diagram
-
SST
with
Ground
Fault
on
4
-
wire
load
BREAKER
HARNESS
CONNECTOR
PROGRAMMER
UNIT
I
GROUND
FAULT
DEFEAT
CABLE
CAT
.
NO
.
TGFD
1
r
~
i
i
—
i
OH
<
<
—
i
r
B
i
o
7 7
CURRENT
SENSORS
V
A
£
<
t
>
B
£
<
t
>
cF
<
4
<
>
I
a
*
0
<<
—
|
—
0
—
I
—
•
<
<
—
I
—
o
—
l
—
<
<
—
!
—
o
—
I
—
<<
4
-
oJ
-
3
I
I I
Any
SST
Programmer
Unit
with
Ground
Fault
Element
C
c
o
—
j
—
<
<
n
D
°
o
<
4
o
3
a
F
!
H
O
—
j
—
<
<
0
-
|
—
<
<
:
<
<
:
o
3
I
K
I
r
“
»
o h
o
—
|
—
<
4
o
-
j
—
<
4
o
-
H
—
<
4
o
-
4
—
<
4
L
_
°
T
^
<
4
-
r
°
-
|
I
3
i
N
I
NEUTRAL
SENSOR
|
DISCONNECT
1
M
M
O
|
w
o
I
So
u
cF
—
<
<
-
4
-
o
I
J
L
.
L
_
J
I
MALE
FEMALE
END
END
Fig
.
16
.
Cabling
diagram
with
Ground
Fault
Defeat
Cable
inserted
be
-
tween
breaker
harness
and
SST
Programmer
Unit
—
for
use
during
single
-
phase
,
high
current
—
low
voltage
testing
.
i
;
Courtesy of NationalSwitchgear.com
TYPE
ECS
OVERCURRENT
TRIP
DEVICE
The
ECS
is
a
solid
-
state
,
direct
-
acting
,
self
-
pow
-
ered
trip
device
system
that
essentially
duplicates
SST
except
for
the
following
:
1
.
Programmer
units
(
Fig
.
17
)
are
limited
to
com
-
binations
of
Long
Time
,
Short
Time
and
In
-
stantaneous
trip
elements
only
.
The
Ground
Fault
element
is
not
available
.
2
.
Phase
sensors
(
Fig
.
18
)
are
not
tapped
.
As
listed
in
Table
2
,
each
sensor
has
only
a
single
ampere
rating
.
A
different
sensor
is
available
for
each
of
the
tabulated
ampere
rat
-
ings
,
which
span
the
same
range
as
SST
.
3
.
There
being
no
Ground
Fault
function
,
neutral
sensors
are
not
required
.
In
all
other
respects
the
ECS
trip
device
system
operates
and
can
be
treated
identically
to
SST
.
This
includes
circuitry
,
size
,
construction
,
component
lo
-
cation
,
programmer
unit
set
points
,
performance
characteristics
,
operating
range
,
quality
,
reliability
and
the
flux
shift
trip
device
.
Use
the
same
trouble
-
shooting
and
test
procedures
for
single
-
phase
,
high
current
-
low
voltage
tests
or
those
employing
the
TAK
-
TS
1
Test
Set
.
The
Ground
Fault
test
proce
-
dures
,
of
course
,
do
not
apply
.
Fig
.
17
.
ECS
Programmer
Unit
0
r
"
FLUX
SHIFT
SOLID
STATE
SWITCH
I
TRIP
I
COIL
I
OVERLOAD
TARGET
I
PROGRAMMER
UNIT
I
CURRENT
SENSOR
GJI
>
7
-
'
SSr
-
LONG
TIME
—
PICKUP
LONG
TIME
DELAY
*
I
SHORT
TIME
PICKUP
AND
DELAY
i
INSTANTANEOUS
PICKUP
.
SHORT
CIRCUIT
TARGET
REGULATED
48
VDC
POWER
SUPPLY
J
/
•
8
000
L
Fig
.
19
.
ECS
Block
diagram
.
Fig
.
18
.
ECS
phase
sensor
14
Courtesy of NationalSwitchgear.com
QA
4
>
B
<
J
>
C
PROGRAMMER
UNIT
AAA
FLUX
SHIFT
TRIP
DEVICE
BREAKER
_
£
BACK
FRAME
|
B
RED
(
48
V
.
dc
)
(
TO
SCR
ANODE
)
o
-
<
>
=
cr
>
=
d
BLACK
o
-
-
<
E
LEFT
POLE
CURRENT
SENSOR
'
I
v
WHITE
O
-
-
<
K
A
C
BLACK
o
-
K
I
WHITE
A
I
=
D
F
BLACK
o
-
-
<
I
WHITE
B
o
-
-
<
(
[
H
K
BLACK
i
I
I
\
l
_
_
_
N
/
\
/
\
/
TTT
HARNESS
CONNECTOR
(
AMP
201298
-
1
)
PROGRAMMER
CONNECTOR
(
AMP
201297
-
1
)
LOAD
Fig
.
20
.
Cabling
diagram
for
ECS
Trip
Device
TABLE
2
—
ECS
TRIP
CHARACTERISTICS
ECS
PROGRAMMER
ADJUSTMENT
RANGE
(
Set
Points
)
Sensor
Ampere
Rating
Long
Time
Short
Time
Frame
Size
(
Amperes
)
Breaker
Type
Instantaneous
Pickup
Pickup
(
=
L
)
Pickup
Time
Delay
Band
®
(
Seconds
)
Time
Delay
Band
®
(
Seconds
)
©
©
©
(
X
)
Multiple
of
X
Multiple Multiple
of
L
of
L
AK
-
75
3000
1200
,
1600
,
2000
,
3000
Maximum
3
,
4
,
5
,
6
,
8
,
10
(
L
)
-
or
-
1.75
,
2
,
2.25
,
2.5
,
3
,
4
(
L
)
Maximum
0.35
Intermed
.
0.21
Minimum
0.095
22
.
6
,
.
7
,
.
8
,
.
9
,
1.0
,
1.1
(
X
)
Intermed
.
4
,
5
,
6
,
8
,
10
,
12
(
L
)
10
AK
-
100
Minimum
4000
1600
,
2000
,
3000
,
4000
4
®
X
=
Sensor
rating
=
trip
rating
®
Pickup
tolerance
is
±
10
%
®
Time
delay
at
lower
limit
of
band
@
6
L
.
®
Time
delay
at
lower
limit
of
band
.
(
See
page
16
for
time
-
current
curves
)
15
Courtesy of NationalSwitchgear.com
H
MULTIPLES
OF
LONG
-
TIME
PICKUP
(
L
)
i
i
ii
m u
2
III
I
*
111
g
3
4
5
«
7
I
•
10
30
40
50 00
70
OOM
^
A
A
.
7
A
.
1000
II
700
700
iig
000
900
!
:
S
400
/
&
200
200
Long
-
time
Delay
Bands
100
100
*
00
oo
5
*
00
00
70
70
00
i
/
i
50
t
:
o
.
Maximum
Total
Clearing
Time
40
X
id
L
ut
30
%
z
&
&
U
4
Minimum
Total
,
Clearing
Time
i
"
20
S
vs
v
0
jfe
s
10
10
*
9
s
sS
0
7
%
V
S
*
s
S
5
A
s
in
-
V
4
7
v
z
*
s
3
7
s
3
LI
I
/
2
>
7
(
S
High
-
range
Short
-
time
Pickup
Points
,
Low
-
range
Short
-
time
Pickup
Points
s
m
7
m
IA
s
M
z
8
L
1
7
3
lot
]
.
0
0
7
.
7
.
0
N
7
n
A
o
-
-
-
o
V
*
•
Maximum
.
4
m
O
.
3
7
Short
-
time
Delay
Bands
p
Intermediate
S
?
J
M
-
2
s
/
M
Q
N
.
5
Minimum
s
S
v
-
J
u
\
ui
.
1
u
>
00
z
.
00
—
.
07
W
.
1
Instantaneous
Pickup
Points
.
00
m
-
41
j
.
00
I
7
>
oe
M
s
:
s
s
/
.
05
.
05
'
7
Z
7
7
N
,
4
Z
Z
z
/
/
.
04
Z
7
/
/
7
7
•
s
7
y
/
V
j
/
.
03
.
03
z
7
v
Application
Determines
End
of
Curve
7
7
7
/
s
.
02
.
02
7
Z
/
7
7
7
s
"
s
'
A
V
/
7
7
7
/
7
/
/
/
7
A
/
7
7
7
i
11
mil
§
1
I
1
2
sill
I
3
4
S
I
7
I
lit
40
50
00
70
SOOOg
20
30
A
.
0
.
7
.
0
.
9
1
MULTIPLES
OF
LONG
-
TIME
PICKUP
(
L
)
NOTE
:
Short
-
timo
delay
is
optional
.
Instantaneous
can
be
omitted
.
AK
/
AKR
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
GENERAL
*
^
ELECTRIC
GES
-
6032
A
ECS
”
SOLID
-
STATE
OVERCURRENT
-
TRIP
DEVICE
Programmer
Set
Points
X
=
Current
Sensor
Rating
(
Amperes
)
PICKUP
long
-
tint
*
:
6
,
.
7
.
8
..
9
.
1.0
I
1
I
multiples
d
current
sensor
rating
(
X
)
.
(
Settings
higher
thon
100
%
d
the
from
*
size
do
not
increase
the
continuous
current
roting
.
)
Short
-
time
•
1.75
.
2
.
2.25
.
2
.
S
,
3
4
4
er
3
.
4
.
5
.
6
.
B
«
10
multiples
d
Long
-
time
pickup
setting
(
l
)
.
Inilenteneous
:
4
.
5
.
6
.
8
.
«
0
8
12
multiples
d
long
-
time
pickup
setting
(
l
|
.
TIME
Of
LAV
SANDS
Long
-
time
-
delay
,
Short
-
time
-
delay
and
Instantaneous
Time
-
current
Curves
100
.
150
.
225
.
300
.
400
.
600
.
800
300
.
400
.
600
.
800
.
1200
,
1600
800
.
1200
.
1600
.
2000
1200
.
1600
.
2000
,
3000
1200
.
1600
.
2000
.
3000
.
3200
AKR
-
30
AKR
-
50
AKRT
-
50
AK
-
75
AKR
-
75
AK
/
AKR
-
100
1600.2000
.
3000.4000
Curves
apply
al
50
/
60
Hertz
From
—
20
C
to
+
70
C
Programmer
Ambient
i
-
time
end
Short
-
time
:
Mo
,
.
|
nt
.
I
Min
.
1
'
GENERAL
ELECTRIC
CO
.
,
CIRCUIT
PROTECTIVE
DEVICES
DEPT
.
,
PLAINVILLE
,
CONN
.
06062
8
-
78
(
1.2
M
)
16
Courtesy of NationalSwitchgear.com
>
MULTIPLES
OF
LONG
-
TIME
PICKUP
(
L
)
i
1 1
m u
i
i
1
I
Iil
|
g
g
.
5
.
•
.
7
J
.
1
1
3
4
5
*
7
1
9
10
20
30
40
50
M
70
*
090
=
1000
1000
*
00
000
»
00
MO
700
700
y
•
00
•
00
/
500
500
400
400
/
300
300
/
/
/
/
200 200
m
Long
-
time
Delay
Bands
5
»
o
•
0
MM
70
7
»
•
0
•
0
a
so
so
§
40
Maximum
Total
Clearing
Time
40
u
UJ
30
3
t
z
UJ
Minimum
Total
Clearing
Time
I
20
20
s
'
s
S
10
10
S
7
s
7
5
%
7
i
55
S
5
1
s
V
r
4
z
\
3
Z
<
N
0
!
,
/
7
2
S
1
!
z
m
Low
-
range
Short
-
time
Pickup
Points
ED
High
-
range
Short
-
time
Pickup
Points
/
m
i
z
.
9
.
9
TOLL
J
lli
?
II
-
J
/
.
7
7
;
Sep
*
1
Maximum
to
n
.
1
co
z
o
.
5
*
uo
/
UJ
.
4
O
/
J
7
Short
-
time
Delay
Bands
Intermediate
^
«
J
*
/
IA
Q
8
Minimum
S
/
s
I
u
s
ui
.
1
.
1
7
Instantaneous
Pickup
Points
oa
.
0
*
Z
.
OB
.
0
«
=
•
7
*
«
NOTES
:
1
.
Short
-
time
-
delay
element
is
optional
.
The
Instan
-
taneous
element
may
be
omitted
.
2
.
For
50
Hertz
operation
of
the
following
breakers
equipped
with
Ground
Trip
element
,
the
Short
-
time
and
Instontaneous
pickup
settings
should
not
ex
-
ceed
the
following
moximums
to
avoid
ground
error
signals
possible
due
to
sensor
saturation
.
.
07
I
.
OS
.
0
«
V
z
Ss
v
.
05
.
05
v
7
7
>
s
1
7
z
7
7
*
Z
.
04
.
04
1
z
77
7
7
r
3
Z
z
7
s
7
.
03
03
7
7
z
N
N
Application
Determines
End
of
Curve
/
Sensor
Tap
Setting
(
Amperes
)
Max
.
Pickup
Setting
(
Amperes
)
7 7
Z
7
S
N
Breaker
v
>
Typ
*
.
02
.
02
r
7
/
S
/
s
/
7
/
AK
/
AKR
-
50
1200
1600
14.000
18.000
s
/
7
7
7
s
>
/
s
/
/
/
s
Ns
s
7
AKT
/
AKRT
-
50
1600
16.000
20.000
z
7
s
2000
7
7
7
s
/
.
5
J
.
7
.
1
.
1
1
3
4
S
I
7
1110
20
40
50
M
70
8010
g
1
111
1
111
i
i
i
i
mill
MULTIPLES
OF
LONG
-
TIME
PICKUP
(
L
)
AK
/
AKR
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
GENERAL
ELECTRIC
GES
-
6033
B
SST
SOLID
-
STATE
OVERCURRENT
TRIP
DEVICE
X
=
Current
Sensor
Taps
(
Amperes
)
Programmer
Set
Points
HCKUF
Long
-
tim
*
:
.
6
.
,
7
.
,
8
.
.
9
.
1.0
I
1.1
multiples
o
»
current
sensor
fop
setting
(
X
)
.
(
Settings
higher
ftion
100
%
of
fhe
from
#
Sri
*
do
not
increase
the
continuous
current
rating
)
.
Short
-
Kme
:
1
75
.
2
.
2.25
.
2.5
.
3
I
4
or
3
.
4
.
S
.
6
.
8
*
10
mult
.
pl
*
*
of
Long
-
tim
*
pickup
setting
(
1
)
.
For
50
Hi
.
operation
,
se
*
Not
*
2
.
Ir
«
ionlon
*
out
:
4
.
5
.
6
.
8
,
10
4
12
multiples
of
Long
-
tim
*
pickvp
satting
(
l
)
.
For
50
Ht
op
*
rot
>
on
.
M
*
Not
*
2
.
TIME
DELAY
SANDS
tint
*
and
Sh
*
rl
-
tim
*
:
Max
.
.
Int
.
S
Min
70
.
100
.
150
.
225
70
.
100
.
150
.
225
or
200
.
300
.
400
.
600
100
.
150
.
225
.
300
or
300
.
400
.
600
.
800
300
.
400
.
600
.
800
or
600
.
800
.
1200
.
1600
AK
-
15
AK
-
25
AKR
-
30
AK
/
AKR
-
50
AKT
/
AKRT
-
50
800
,
1200
.
1600
.
2000
AK
-
75
AKR
-
75
AK
/
AKR
-
100
Long
-
time
-
delay
,
Short
-
time
-
delay
and
Instantaneous
Time
-
current
Curves
1200
.
1600
.
2000
.
3000
1200
.
1600
.
2000
.
3200
1600
.
2000
.
3000
.
4000
Curves
apply
at
50
/
60
Hertz
From
20
C
to
+
70
C
Programmer
Ambient
GENERAL
ELECTRIC
CO
.
,
CIRCUIT
PROTECTIVE
DEVICES
DEPT
.
,
PLAINVILLE
,
CONN
.
06062
8
-
78
(
1.2
M
)
17
Courtesy of NationalSwitchgear.com
MULTIPLES
OF
CURRENT
SENSOR
TAP
(
X
)
<
1
3
4
S
•
7
2
1
I
I
1
.
4
3
4
5
6
7
8
z
.
a
a
i
2
.
4
.
1
1600
1000
.
»
00
7
/
800
00
7
7
Ss
'
•
N
-
700
700
s
/
eoo
800
7
/
s
v
s
500
500
z
'
N
7
r
400
400
z
/
s
z
s
.
300
300
s
/
Ns
s
/
’
7
N
7
s
200
200
'
s
/
s
/
/
s
/
S
s
/
s
100
100
7
s
»
0
»
0
N
7
s
80
80
7
/
70
70
7
80
80
y
7
•
>
to
/
50
O
50
/
l
40
40
z
U
Ui
%
UI
/
-
/
30
30
7
z
I
.
5
X
/
7
/
s
Ground
Fault
Pickup
Points
AK
-
15
/
25
Ui
6
X
5
20 20
E
3
/
V
*
«
S
S
S
/
/
/
s
-
-
V
.
10
10
y
/
9
>
ox
[
/
8
7
>
/
7
7
7
s
8
5
7
7
4
z
7
N
7
/
3
3
7
s
N
5
7
4
X
2
SX
Ground
Fault
Pickup
Points
AKR
-
30
Ground
Fault
Pickup
Points
AK
-
50
AKR
-
50
2
7
/
r
«
i
s
/
s
/
0
s
.
5
S
i
—
.
9
I
-
2
X
mww
4
\
«
PI
a
si
1
^
?
Bk
'
R
/
7
n
s
o
V
.
5
%
z
7
.
4
Mi
z
Z
7
s
7
7
7
/
o
Maximum
7
/
/
Maximum
sS
7
z
7
/
7
z
FiU
“
IB
s
:
<
i
.
3
Ground
Fault
Delay
Bands
7
7
7
77
/
/
7
7
7
-
s
Intermediate
Intermediate
/
%
7
7
/
7
s
/
.
2
ssi
7
7
7
T
7
7
7
7
/
/
S
S
V
/
/
/
/
/
in
Q
9
IK
i
7
77
'
7
7
/
/
s
/
/
/
/
/
/
7
7
/
s
/
ife
/
/
/
s
/
/
u
/
\
s
S
7
7
/
/
N
Ui
/
s
/
/
1
u
»
.
1
7
7
T
/
z
z
/
Minimum
^
/
Minimum
.
09
.
08
z
7
7
Z
08
=
07
•
«
.
08
7
7
7
7
Z
7
/
/
/
y
.
07
5
.
08
.
08
—
»
.
05
.
05
.
04
.
03
.
03
.
02
.
02
.
01
.
01
5
6
7
8
|
Li
2
.
2
.
8
B
I
3
4
.
4
6
2
3
4
5
6
7
6
.
2
8
1
.
4
.
1
MULTIPLES
OF
CURRENT
SENSOR
TAP
(
X
)
NOTE
:
4
H
»
wire
Ground
Minor
tap
mutt
be
Ml
win
#
ot
pha
*
«
Minor
lop
.
TYPE
AKR
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
GENERAL
^
ELECTRIC
GES
-
6034
A
SST
“
SOLID
-
STATE
OVERCURRENT
TRIP
DEVICE
Programmer
Set
Points
Current
Sensor
Taps
(
Amperes
)
70
.
100
.
150
.
225
70
.
100
.
150
.
225
or
200
.
300
.
400
.
600
100
.
150
.
225
.
300
or
300
.
400
.
600
.
800
300
.
400
,
600
.
800
or
600
.
800
.
1200
,
1600
Ground
Fault
Pickup
;
AK
-
15
/
25
AKR
-
30
AK
/
AKR
-
50
Ground
Trip
Time
-
current
Curves
5
x
.
6
x
.
8
x
.
1
.
Ox
.
1.5
x
,
&
2
.
Ox
.
4
x
.
.
5
x
.
.
6
x
.
,
8
x
,
l
.
Ox
,
&
1.2
x
,
25
x
.
.
3
x
.
.
4
x
.
.
5
x
,
,
6
x
,
&
.
7
x
Where
X
=
sensor
tap
setting
AK
-
15
AK
-
25
AKR
-
30
AK
/
AKR
-
50
Ground
Fault
Delay
Bands
;
Maximum
.
Intermediate
&
Minimum
Curvet
apply
al
50
/
60
Hertz
From
—
20
C
lo
+
70
C
Programmer
Ambient
GENERAL
ELECTRIC
CO
.
,
CIRCUIT
PROTECTIVE
DEVICES
DEPT
.
.
PLAINVILLE
,
CONN
.
06062
8
-
78
(
1.2
M
)
18
Courtesy of NationalSwitchgear.com
MULTIPLES
OF
CURRENT
SENSOR
TAP
(
X
)
•
»
•
i
A
i
I
.
2
A
A
.
1
1
nr
.
2
.
4
l
Li
.
2
A
A
1
I
.
4
.
2
.
4
A
J
1000 1000
I
IP
llellB
•
00
»
00
•
00
•
00
.
*
700
700
-
•
>
•
00
•
00
N
X
s
*
X
900
900
x
<
•
400
400
*
s
X
»
x
x
,
300
300
*
s
"
2
v
>
S
*
*
x
,
200
200
»
A
s
*
*
X
'
S
s
s
S
•
*
S
.
.
'
S
s
S
s
'
100
100
Ground
Fault
Pickup
Point
*
AKR
-
75
Ground
Fault
Pickup
Points
AK
-
100
AKR
-
100
Ground
Fault
Pickup
Points
AK
-
75
•
o
»
o
Ground
Fault
Pickup
Points
AKT
-
50
AKRT
-
50
•
a
•
o
-
S
70 70
x
N
•
0
x
.
x
^
-
'
M
x
»
50
50
x
--
X
X
40 40
y
N
'
X
V
)
s
30
30
X
X
z
*
y
,
'
X
X
N
Sx
-
tu
*
X
«
*
X
l
”
20
X
X
-
C
*
<
1
*
-
-
X
xl
X
-
v
ex
/
x
ex
C
4
ex
X
x
.
*
“
X
_
|
XI
s
.
ex
r
Lt
•
*
10
10
kO
1
ex
x
X
e
]
E
s
7
m
*
ex
x
x
I f
i
a
'
v
9
9
>
s
X
4
s
o
-
X
.
*
3
S
s
»
*
)
s
S
s
S
*
•
s
2
s
-
'
X
-
-
-
X
-
s
s
s
VX
VH
r
-
'
"
s
\
<
x
x
1
ill
A
J
x
J
71
f
X
X
.
7
XJ
X
.
0
J
m
*
x
n
*
5
s
3
A
*
A
^
N
wn
<
A
Lia
.
4
-
Maximum
1
x
o
X
H
X
>
T
<
mZ
4
V
k
X
S
x
.
3
X
N
H
>
-
-
>
5
?
2
-
5
x
>
k
s
.
Intermodiate
X
»
HJKSs
?
.
2
>
x
A
K
trt
a
\
-
<
x
/
<
s
<
;
>
9
>
X
>
>
Ground
Fault
D
«
lay
Bands
S
s
>
<
:
<
>
<
s
>
<
X
^
Minimum
X
X
>
<
u
X
s
s
s
>
:
<
•
UJ
<
xi
.
1
.
1
U
>
y
5
<
w
.
09
~
z
h
i
;
i
08
—
.
07
U
*
<
X
c
<
<
>
<
*
<
X
.
.
07
I
.
08
.
08
.
09
.
05
.
04
.
04
.
03
.
03
.
02
.
02
.
01
.
«
»
i
T
L
T
2
A
.
1
.
1
.
8
«
2
.
4
.
1
.
4
.
6
.
8
1
Li
2
8
8
1
.
4
•
2
MULTIPLES
OF
CURRENT
SENSOR
TAP
(
X
)
NOT
*
:
4
th
wir
*
Ground
»
«
n
*
or
tap
must
be
*
et
same
at
phase
sensor
tap
.
AK
/
AKR
LOW
-
VOLTAGE
POWER
CIRCUIT
BREAKERS
GENERAL
ELECTRIC
GES
-
6035
B
SST
“
SOLID
-
STATE
OVERCURRENT
TRIP
DEVICE
Programmer
Set
Points
X
-
Current
Sensor
Taps
(
Amperes
)
800
.
1200
.
1600
.
2000
1200
.
1600
.
2000
.
3000
1200
.
1600
.
2000
.
3200
1600
.
2000
.
3000
.
4000
Ground
Fault
Pickup
:
AKT
.
AKRT
-
50
AK
-
75
AKR
-
75
AK
/
AKR
-
100
AKT
/
AKRT
-
50
.
2
x
.
.
25
x
.
.
3
x
,
.
4
x
,
,
5
x
,
&
.
6
x
,
2
x
,
22
x
.
25
x
.
3
x
.
35
x
.
8
.
.
Ax
.
2
x
,
22
x
,
,
25
x
,
,
3
x
,
.
35
x
&
.
37
x
18
x
.
,
2
x
,
,
22
x
.
25
x
.
27
x
&
3
x
Where
X
=
sensor
top
setting
Ground
Trip
Time
-
current
Curves
AK
-
75
AKR
-
75
AK
/
AKR
-
100
Curves
apply
ol
50
/
60
Hertz
From
—
20
C
to
+
70
C
Programmer
Ambient
Ground
Fault
Delay
Bands
Maximum
.
Intermediate
8
Minimum
GENERAL
ELECTRIC
CO
.
,
CIRCUIT
PROTECTIVE
DEVICES
DEPT
.
,
PLAINVILLE
,
CONN
.
06062
2
-
78
(
3
Mt
19
Courtesy of NationalSwitchgear.com
V
DISTRIBUTION
EQUIPMENT
DIVISION
PLAINVILLE
,
CONNECTICUT
GENERAL
ELECTRIC
Printed
in
U
.
S
.
A
.
Courtesy of NationalSwitchgear.com

This manual suits for next models

11

Other GE Circuit Breaker manuals

GE Power Break II User manual

GE

GE Power Break II User manual

GE AM-4.16-250-6C User manual

GE

GE AM-4.16-250-6C User manual

GE Gerapid 2607 User manual

GE

GE Gerapid 2607 User manual

GE AKR Series Configuration guide

GE

GE AKR Series Configuration guide

GE Spectra Series AMC3FGB User manual

GE

GE Spectra Series AMC3FGB User manual

GE AM-13.8-500-5C User manual

GE

GE AM-13.8-500-5C User manual

GE MicroVersaTripPlus AK-50 User manual

GE

GE MicroVersaTripPlus AK-50 User manual

GE AKR-3-50 User manual

GE

GE AKR-3-50 User manual

GE SPST012 User manual

GE

GE SPST012 User manual

GE AK-1-15 Series User manual

GE

GE AK-1-15 Series User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE AM-13.8-500-5C User manual

GE

GE AM-13.8-500-5C User manual

GE Pro-Stock SF250 User manual

GE

GE Pro-Stock SF250 User manual

GE WavePro 3200 A User manual

GE

GE WavePro 3200 A User manual

GE EntelliGuard GT-H User manual

GE

GE EntelliGuard GT-H User manual

GE EntelliGuard GBKRKR User manual

GE

GE EntelliGuard GBKRKR User manual

GE AM-4.16-250-6 User manual

GE

GE AM-4.16-250-6 User manual

GE ML-14-0 User manual

GE

GE ML-14-0 User manual

GE GE-200A User manual

GE

GE GE-200A User manual

GE Power-Break TSUV1 User manual

GE

GE Power-Break TSUV1 User manual

GE SF6 User manual

GE

GE SF6 User manual

GE EntelliGuard G User guide

GE

GE EntelliGuard G User guide

GE AK-50 Series Technical specifications

GE

GE AK-50 Series Technical specifications

Popular Circuit Breaker manuals by other brands

Siemens 3WX3647-5JE00 operating instructions

Siemens

Siemens 3WX3647-5JE00 operating instructions

TAVRIDA ELECTRIC ISM_LD Series Application guide

TAVRIDA ELECTRIC

TAVRIDA ELECTRIC ISM_LD Series Application guide

Moeller UVU-NZM Series installation instructions

Moeller

Moeller UVU-NZM Series installation instructions

Eaton Series NRX Installation and operating instructions

Eaton

Eaton Series NRX Installation and operating instructions

Moeller SVB-NZM 6 installation instructions

Moeller

Moeller SVB-NZM 6 installation instructions

Toshiba XVFN10 instruction manual

Toshiba

Toshiba XVFN10 instruction manual

Eaton FAZ-XHIN11 installation instructions

Eaton

Eaton FAZ-XHIN11 installation instructions

GenInterlock GE-200VL instructions

GenInterlock

GenInterlock GE-200VL instructions

Mitsubishi Electric AE-SW Series instruction manual

Mitsubishi Electric

Mitsubishi Electric AE-SW Series instruction manual

Siemens Sentron 3VA91 8-0VF30 Series operating instructions

Siemens

Siemens Sentron 3VA91 8-0VF30 Series operating instructions

ABB HD4/R Installation and operating instructions

ABB

ABB HD4/R Installation and operating instructions

Eaton CN13GN0 Instruction leaflet

Eaton

Eaton CN13GN0 Instruction leaflet

Coster XTE 602 manual

Coster

Coster XTE 602 manual

DINWAY BAM8 Series instruction manual

DINWAY

DINWAY BAM8 Series instruction manual

Eaton Z-ASA Instructions for installation

Eaton

Eaton Z-ASA Instructions for installation

Siemens AFCI Instructions for installation

Siemens

Siemens AFCI Instructions for installation

Siemens SENTRON 3WL10 manual

Siemens

Siemens SENTRON 3WL10 manual

Allen-Bradley 140G-R Series Installation

Allen-Bradley

Allen-Bradley 140G-R Series Installation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.