manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Circuit Breaker
  8. •
  9. GE MicroVersaTrip AKR-75 User manual

GE MicroVersaTrip AKR-75 User manual

Other manuals for MicroVersaTrip AKR-75

2

This manual suits for next models

2

Other GE Circuit Breaker manuals

GE AM-13.8-500-5A User manual

GE

GE AM-13.8-500-5A User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE AKR-30 Series User manual

GE

GE AKR-30 Series User manual

GE GL 310 F3/4031 P/VR User manual

GE

GE GL 310 F3/4031 P/VR User manual

GE Power Break II SPUV012DC User manual

GE

GE Power Break II SPUV012DC User manual

GE MicroVersaTrip Plus User manual

GE

GE MicroVersaTrip Plus User manual

GE Power Break II User manual

GE

GE Power Break II User manual

GE GL 310 F1/4031 P/VR User manual

GE

GE GL 310 F1/4031 P/VR User manual

GE MicroVersa Trip Plus User manual

GE

GE MicroVersa Trip Plus User manual

GE Shunt Trip User manual

GE

GE Shunt Trip User manual

GE FD 63 User manual

GE

GE FD 63 User manual

GE EntelliGuard GT-H User manual

GE

GE EntelliGuard GT-H User manual

GE PowerVac GEK-86132G User manual

GE

GE PowerVac GEK-86132G User manual

GE CB Watch 3 User manual

GE

GE CB Watch 3 User manual

GE AK-1-15 Series User manual

GE

GE AK-1-15 Series User manual

GE MicroVersaTrip Plus Series User manual

GE

GE MicroVersaTrip Plus Series User manual

GE POWER/VAC GEK 86132A User manual

GE

GE POWER/VAC GEK 86132A User manual

GE AKR-3-50 User manual

GE

GE AKR-3-50 User manual

GE AKR-75 Series Programming manual

GE

GE AKR-75 Series Programming manual

GE AM-13.8-500-5C User manual

GE

GE AM-13.8-500-5C User manual

GE Spectra Series AMCB6FGB User manual

GE

GE Spectra Series AMCB6FGB User manual

GE AK-1-50 User manual

GE

GE AK-1-50 User manual

GE AK-2-50 User manual

GE

GE AK-2-50 User manual

GE Spectra Series User manual

GE

GE Spectra Series User manual

Popular Circuit Breaker manuals by other brands

Siemens 3VT9524-4TG30 quick start guide

Siemens

Siemens 3VT9524-4TG30 quick start guide

Acrel ASCB1 Series Installation and operation manual

Acrel

Acrel ASCB1 Series Installation and operation manual

ABB SACE Emax 2 E2.2 manual

ABB

ABB SACE Emax 2 E2.2 manual

Eaton NOVA LBS 15 Installation and operation instructions

Eaton

Eaton NOVA LBS 15 Installation and operation instructions

ABB SACE Emax E1 quick start guide

ABB

ABB SACE Emax E1 quick start guide

Siemens SIRIUS 3RV1742 Original operating instructions

Siemens

Siemens SIRIUS 3RV1742 Original operating instructions

WEG FHU ACW125 installation instructions

WEG

WEG FHU ACW125 installation instructions

TERASAKI NHP TemBreak PRO P160 Series installation instructions

TERASAKI

TERASAKI NHP TemBreak PRO P160 Series installation instructions

Siemens Sentron 3VA9157-0PK1 Series operating instructions

Siemens

Siemens Sentron 3VA9157-0PK1 Series operating instructions

hager TS 303 User instruction

hager

hager TS 303 User instruction

ETI EFI-4B Instructions for mounting

ETI

ETI EFI-4B Instructions for mounting

Gladiator GCB150 Installation instruction

Gladiator

Gladiator GCB150 Installation instruction

nader NDM3EU-225 operating instructions

nader

nader NDM3EU-225 operating instructions

Eaton 50DHP-VR Instruction handbook

Eaton

Eaton 50DHP-VR Instruction handbook

ABB SACE Emax 2 E6.2 Instruction handbook

ABB

ABB SACE Emax 2 E6.2 Instruction handbook

Gewiss 90 RCD Installation

Gewiss

Gewiss 90 RCD Installation

OEZ LFN Instructions for use

OEZ

OEZ LFN Instructions for use

Eaton Power Defense PDG2 Instruction leaflet

Eaton

Eaton Power Defense PDG2 Instruction leaflet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

GEI
-
86151
D
Installation
Instructions
i
Low
Voltage
Power
Circuit
Breakers
Types
AKR
-
75
/
100
»
»
Courtesy of NationalSwitchgear.com
»
Installation
and
Operation
of
Type
AKR
-
75
and
AKR
-
100
Low
-
Voltage
Power
Circuit
Breakers
CONTENTS
SECTION
6
6.0
FUSE
ROLLOUT
ELEMENTS
SECTION
7
7.0
CONNECTIONS
7.1
Primary
Power
7.2
Secondary
Control
SECTION
1
1.0
INTRODUCTION
3
13
14
SECTION
2
2.0
RECEIVING
,
HANDLING
AND
STORAGE
14
14
4
SECTION
8
8.0
OPERATION
8.1
General
8.2
Manual
Closing
8.3
Electrical
Closing
8.4
Tripping
8.5
Current
Rating
For
Auxiliary
Devices
SECTION
3
3.0
INSTALLATION
3.1
Class
1
E
Application
3.2
Location
3.3
Mounting
Types
15
»
4
15
4
15
4
15
4
16
SECTION
4
4.0
STATIONARY
BREAKERS
16
5
SECTION
9
9.0
MAINTENANCE
9.1
Inspection
9.2
Lubrication
9.3
Reference
Publications
17
SECTION
5
5.0
DRAWOUT
BREAKERS
5.1
General
5.2
No
Code
Letter
-
AKD
Switchgear
5.2
.
1
Breaker
Insertion
5.2
.
2
Breaker
Removal
5.3
Code
A
-
AKD
5
/
6
Switchgear
5.3
.
1
Breaker
Insertion
5.3
.
2
Breaker
Removal
5.4
Code
B
-
AKR
Substructure
5.4
.
1
Breaker
Insertion
5.4
.
2
Breaker
Removal
5.5
Code
C
-
AKD
6
Switchgear
5.6
Code
D
-
AKD
8
Switchgear
5.7
Code
F
-
AKR
Substructure
17
5
17
6
17
6
SECTION
10
10.0
INTERCHANGEABILITY
OF
DRAWOUT
BREAKERS
10.1
General
10.2
No
Letter
AKD
Types
10.3
Code
A
Types
10.4
Code
B
Types
10.5
CodeC
Types
10.6
Code
D
Types
10.7
Code
F
Types
10.88
E
-
Type
Rejection
6
7
18
8
19
8
19
8
19
8
19
10
19
11
19
11
19
»
11
19
11
2
Courtesy of NationalSwitchgear.com
SECTION
1
Introduction
i
These
instructions
describe
the
installation
and
operation
of
the
AKR
-
75
and
AKR
-
100
frame
size
Low
Voltage
Power
Circuit
Breakers
.
They
cover
a
variety
of
models
which
may
differ
in
rating
,
trip
device
and
/
or
mounting
type
as
indicated
in
Table
1
.
Table
1
MOUNTING
TYPE
FRAME
SIZE
(
Amperes
)
BREAKER
WIDTH
(
Inches
)
PRIMARY
STUD
TYPE
DEEP
ESCUTCHEON
BREAKER
DESIGNATION
DRAWOUT
Stationary
Sub
*
Structure
600
V
.
Ac
50
/
60
Hz
.
AKD
-
8
AKD
-
5
AKD
-
6
AKD
250
V
.
DC
Bar
X
AKR
-
O
-
75
3000
Tube
X
25
Tube
X
X
AKR
-
(
*
)
A
-
75
4000
Fingers
X
X
AKR
-
HB
-
75
Fingers
AKR
-
(
»
)
C
-
75
X
3200
Fingers
X
X
AKR
-
nD
-
75
Fingers
X
X
AKR
-
(
*
)
F
-
75
Bar
X
AKR
-
(
*
)
S
-
75
Tube
AKR
-
n
-
100
X
33
Tube
AKR
-
(
*
)
A
-
10
Q
X
X
Fingers
X
X
AKR
-
(
*
)
B
-
100
25
Fingers
X
AKR
-
(
*
)
Q
100
6000
4000
Fingers
X
X
AKR
-
nD
-
100
Fingers
X
X
AKR
-
(
*
)
F
’
10
Q
Bar
X
AKR
-
HS
-
100
Bar
33
i
X
AKR
-
OW
-
100
SPECIAL
DC
BREAKERS
FOR
FIELD
SWITCHING
Tube
ARK
-
N
-
75
F
X
Fingers
X
X
AKR
-
NB
-
75
F
25
Fingers
X
AKR
-
ND
-
75
F
X
4000
Fingers
X
X
AKR
-
NF
-
75
F
Bar
X
AKR
-
NS
-
75
F
33
Tube
AKR
-
N
-
100
F
X
Fingers
X
X
AKR
-
NB
-
100
F
Fingers
X
X
6000
AKR
-
ND
-
100
F
Fingers
X
X
AKR
-
NF
-
100
F
25
Bar
X
AKR
-
NS
-
100
F
33
Bar
X
AKR
-
NW
-
100
F
Example
:
AKR
-
5
B
-
75
identifies
a
drawout
,
substructure
-
mounted
breaker
equipped
with
the
SST
trip
device
.
The
EC
trip
devices
are
electro
-
mechanical
,
refer
to
GEI
86157
for
detailed
information
.
BREAKER
MODELS
(
*
)
This
digit
identifies
the
trip
device
:
2
=
EC
-
1
or
E
02
A
.
Dc
only
.
4
=
ECS
5
-
SST
50
/
60
Hertz
only
.
6
=
MicroVersaTrip
50
/
60
Hertz
only
.
7
=
MicroVersaTrip
RMS
-
9
50
/
60
Hertz
only
.
8
=
EPIC
MicroVersaTrip
.
9
=
MicroVersaTrip
Plus
and
PM
50
/
60
Hertz
only
.
For
detailed
information
on
these
trip
devices
refer
to
the
following
publication
:
GEI
-
86157
N
=
Non
-
automatic
.
In
addition
,
all
non
-
automatic
250
V
.
Dc
breaker
types
carry
the
suffix
letter
D
after
the
frame
number
,
e
.
g
.
,
AKR
-
N
B
-
75
D
.
i
Courtesy of NationalSwitchgear.com
SECTION
3
SECTION
2
Installation
Receiving
,
Handling
,
and
Storage
3.1
CLASS
1
E
APPLICATION
NOTE
:
Before
installing
in
a
Nuclear
Class
1
E
application
,
verify
that
this
product
is
intended
for
such
use
by
checking
the
procurement
records
.
Breakers
with
MicroVersaTrip
Plus
or
MicroVersaTrip
PM
trip
units
are
not
intended
for
use
in
Class
IE
applications
.
Before
installing
or
operating
these
circuit
breakers
,
care
-
fully
read
these
instructions
.
Upon
receipt
of
a
circuit
breaker
,
immediately
examine
for
any
damage
or
loss
sustained
in
shipment
.
If
injury
,
loss
or
rough
handling
is
evident
,
file
a
damage
claim
at
once
with
the
transportation
company
and
notify
the
nearest
General
Electric
Sales
Office
.
Unpack
the
circuit
breaker
as
soon
as
possible
after
it
has
been
received
.
Exercise
care
in
unpacking
to
avoid
damage
to
the
breaker
parts
.
Be
sure
that
no
loose
parts
are
missing
or
left
in
the
packaging
material
.
Blow
out
any
dirt
or
loose
particles
of
packaging
material
remaining
on
or
in
the
breaker
.
If
the
circuit
breaker
is
not
to
be
placed
in
service
at
once
,
store
it
in
a
clean
,
dry
location
in
an
upright
position
.
Support
it
to
prevent
bending
of
the
studs
or
damage
to
any
of
the
breaker
parts
.
Do
not
cover
the
breaker
with
packing
or
other
material
which
absorbs
moisture
that
may
cause
corrosion
of
breaker
parts
.
A
covering
of
kraft
or
other
non
-
absorbent
paper
will
prevent
dust
from
settling
oh
the
breaker
.
3.2
LOCATION
In
choosing
a
location
for
the
installation
of
these
breakers
there
are
two
factors
to
be
considered
.
The
first
is
the
location
'
s
environmental
impact
on
the
breaker
.
Much
better
performance
and
longer
life
can
be
expected
if
the
area
is
clean
,
dry
,
dust
-
free
and
well
ventilated
.
The
second
is
con
-
venience
for
operation
and
maintenance
.
The
breaker
should
be
easily
accessible
to
the
operator
and
there
should
be
sufficient
space
available
for
maintenance
work
.
3.3
MOUNTING
TYPES
AKR
-
75
and
-
100
breakers
are
furnished
in
both
drawout
and
stationary
construction
.
The
mounting
type
is
identified
by
the
second
middle
digit
in
the
breaker
'
s
nameplate
desig
-
nation
as
follows
:
AKR
-
4
(
f
)
-
75
,
where
(
t
)
=
mounting
type
code
letter
per
Table
2
TABLE
2
MOUNTING
TYPE
CODES
Breaker
Type
Code
Letter
Drawout
Stationary
None
AKD
A
AKD
-
5
,
6
B
Substructure
C
AKD
-
6
Only
AKD
-
8
D
F
Substructure
AKR
-
75
/
100
(
25
"
wide
)
S
AKR
-
100
(
33
"
wide
)
W
4
Courtesy of NationalSwitchgear.com
SECTION
5
SECTION
4
Stationary
Breakers
Drawout
Breakers
5.1
General
5.2
No
Code
Letter
-
AKD
Switchgear
5.2
.
1
Breaker
Insertion
5.2
.
2
Breaker
Removal
5.3
Code
A
-
AKD
5
/
6
Switchgear
5.3
.
1
Breaker
Insertion
5.3
.
2
Breaker
Removal
5.4
Code
B
-
AKR
Substructure
5.4
.
1
Breaker
Insertion
5.4
.
2
Breaker
Removal
5.5
Code
C
-
AKD
6
Switchgear
5.6
Code
D
-
AKD
8
Switchgear
5.7
Code
F
-
AKR
Substructure
6
6
These
breakers
are
designed
lor
mounting
in
a
switch
-
board
or
enclosure
designed
and
constructed
by
others
.
Mounting
consists
of
bolting
the
breaker
frame
to
a
support
-
ing
structure
within
the
switchboard
or
enclosure
,
connecting
the
power
buses
or
cables
,
and
making
any
necessary
con
-
trol
connections
.
The
front
cover
of
the
breaker
enclosure
may
be
a
hinged
door
or
a
plate
bolted
to
the
panel
,
including
a
cut
-
out
opening
through
which
the
front
escutcheon
of
the
breaker
can
protrude
.
6
7
8
8
9
9
10
The
surface
on
which
the
breaker
is
mounted
must
be
flat
to
avoid
internal
distortion
of
the
breaker
.
The
supporting
structure
must
be
rigid
enough
to
avoid
any
possibility
of
the
breaker
studs
supporting
the
weight
of
the
breaker
.
Minimum
cutout
dimensions
as
given
by
the
appropriate
outline
draw
-
ing
must
be
maintained
to
provide
adequate
electrical
clear
-
ance
.
Connecting
bus
and
cables
must
be
rigidly
supported
to
prevent
undue
stress
on
the
breaker
terminals
.
11
11
11
11
Outline
drawing
numbers
giving
dimensions
for
designing
a
suitable
enclosure
for
the
stationary
AKR
-
75
and
AKR
-
100
types
are
given
below
.
TABLE
3
Outline
Drawing
Stationary
Breaker
Type
Breaker
Width
Manually
Operated
Electrically
Operated
AKR
-
(
)
S
-
75
25
"
139
C
4560
139
C
4561
AKR
-
(
)
S
-
100
25
"
AKR
-
(
)
W
-
100
139
C
4562
33
"
139
C
4563
e
5
Courtesy of NationalSwitchgear.com
|
Drawout
Breakers
1
.
There
are
three
(
3
)
distinct
drawout
positions
—
CON
-
NECTED
,
TEST
and
WITHDRAWN
.
2
.
Racking
travel
occurs
only
between
the
CONNECTED
position
and
a
point
just
short
of
reaching
the
TEST
position
.
3
.
The
compartment
door
must
be
open
during
racking
.
5.1
GENERAL
Drawout
breakers
are
manufactured
in
six
different
styles
,
identified
in
Table
2
by
the
mounting
code
letters
None
,
A
,
B
,
C
,
D
&
F
.
The
“
no
-
letter
”
models
are
used
in
General
Electric
'
s
AKD
Switchgear
.
Code
A
breakers
were
later
introduced
with
AKD
-
5
Switchgear
and
feature
dosed
-
door
drawout
opera
-
tion
.
Code
Band
F
breakers
provide
an
alternate
dosed
-
door
drawout
arrangement
with
the
stationary
element
furnished
as
a
preassembied
“
substructure
/
1
Code
C
breakers
are
exclusively
for
AKD
-
6
Switchgear
;
they
employ
the
Code
A
drawout
mechanism
but
have
finger
-
type
primary
studs
in
-
stead
of
tubular
.
Code
D
breakers
were
introduced
with
the
AKD
-
8
Switchgear
and
feature
the
Code
B
dosed
-
door
drawout
mechanism
.
The
construction
and
operation
of
each
of
these
drawout
styles
is
covered
under
respective
headings
in
the
following
text
.
NOTE
:
The
Code
B
and
Code
F
drawout
types
are
mutually
interchangeable
.
The
“
no
-
letter
,
”
Code
A
,
Code
C
and
Code
D
drawout
types
are
mutually
noninterchangeable
.
Before
attempting
to
insert
a
breaker
,
verify
that
the
breaker
model
matches
the
compartment
.
The
Code
B
,
D
,
and
F
breakers
are
identical
except
for
the
following
:
a
.
Position
indication
label
.
This
label
is
mounted
on
the
sides
of
the
breaker
’
s
deep
escutcheon
and
indicates
the
DISCONNECTED
,
TEST
,
and
CONNECTED
posi
-
tions
.
The
Code
D
breaker
label
indicates
the
proper
position
only
in
AKD
8
switchgear
.
The
Code
B
and
F
breaker
labels
indicate
properly
only
in
AKR
Substruc
-
tures
.
b
.
Trip
device
.
Code
D
and
F
breakers
are
factory
sup
-
plied
with
MicroVersaTrip
or
PM
trip
units
.
5.2
.
1
BREAKER
INSERTION
1
.
Prior
to
lifting
a
breaker
to
its
intended
compartment
location
,
observe
the
following
precautions
:
a
.
Check
the
compartment
to
insure
that
it
is
free
of
foreign
objects
.
b
.
Verify
that
the
breaker
is
the
correct
type
for
that
compartment
.
c
.
Insure
that
the
breaker
is
OPEN
.
d
.
Apply
a
thin
,
fresh
coat
of
D
50
HD
38
lubricant
to
the
breaker
'
s
primary
disconnects
.
e
.
Insure
that
the
racking
cams
on
the
breaker
are
correctly
positioned
for
initial
engagement
with
the
pins
in
the
compartment
.
To
do
this
,
insert
the
rack
-
ing
handle
and
rotate
it
fully
clockwise
.
f
.
If
a
compartment
contains
a
keylock
,
it
will
not
ac
-
cept
the
AKR
-
75
/
100
replacement
breakers
as
re
-
ceived
.
The
AKR
drawout
mechanism
differs
from
that
of
its
predecessor
AK
model
,
causing
the
AKR
breaker
to
mechanically
interfere
with
the
keylock
during
breaker
insertion
.
To
remedy
this
it
will
be
necessary
to
relocate
the
keylock
using
new
mount
-
ing
hardware
included
as
a
modification
kit
.
So
al
-
tered
,
the
compartment
accepts
both
AK
and
AKR
types
.
2
.
Using
a
suitable
lifting
mechanism
and
spreader
rig
,
position
lifting
hooks
at
the
cutout
notches
in
the
top
wrap
-
around
frames
of
the
breaker
.
Exercise
care
to
avoid
damage
to
the
control
wiring
.
3
.
Open
the
compartment
door
.
Keeping
the
rollout
tray
positioned
inside
the
compartment
,
raise
the
breaker
above
the
elevation
of
the
tray
.
4
.
Depress
the
test
position
stop
lever
and
pull
the
tray
all
the
way
out
to
its
WITHDRAWN
position
.
5
.
Lower
the
breaker
over
the
tray
until
it
is
about
one
-
half
inch
above
the
two
dowel
pins
on
the
tray
.
Push
the
breaker
back
into
the
compartment
until
the
rear
bottom
flange
of
the
breaker
rests
against
the
guides
behind
the
dowel
pins
.
6
.
Slowly
lower
and
guide
the
breaker
onto
the
tray
so
the
holes
in
the
rear
flange
fit
over
the
two
dowel
pins
.
When
correctly
positioned
on
the
dowel
pins
,
the
breaker
'
s
rear
and
side
bottom
flanges
will
rest
firmly
on
the
tray
.
7
.
Secure
the
breaker
to
the
tray
by
inserting
and
tighten
-
ing
two
-
%
inch
hex
-
head
screws
into
the
front
holes
of
its
side
flanges
.
8
.
If
the
breaker
is
a
manually
operated
type
,
push
it
into
the
compartment
until
the
TEST
position
stop
engages
,
preventing
further
travel
.
The
breaker
is
now
in
the
TEST
position
.
i
c
.
Appearance
.
Code
D
and
F
breakers
use
a
different
color
scheme
on
their
deep
escutcheons
and
labels
.
Also
,
they
have
a
differently
shaped
manual
operating
handle
.
5.2
NO
CODE
LETTER
(
AKD
SWITCHGEAR
)
(
Fig
.
1
)
These
“
no
-
letter
”
AKR
-
75
/
100
models
are
replacements
for
their
AK
-
75
and
AK
-
100
predecessors
in
AKD
switchgear
.
The
racking
mechanism
is
breaker
-
mounted
and
the
breakers
are
bolted
to
a
roller
-
mounted
tray
in
an
arrange
-
ment
similar
to
the
BType
(
see
Section
5.4
)
.
In
addition
to
the
characteristics
listed
in
Table
1
,
the
AKD
drawout
has
the
following
unique
aspects
:
i
6
Courtesy of NationalSwitchgear.com
If
the
breaker
is
electrically
operated
,
push
it
into
the
compartment
until
the
spring
discharge
stop
is
encountered
.
Release
this
by
depressing
the
“
spring
discharge
”
lever
on
the
bottom
of
the
breaker
(
see
fig
.
1
)
,
then
continue
pushing
the
breaker
into
the
compartment
until
the
TEST
position
stop
engages
.
4
.
To
withdraw
a
manually
operated
breaker
from
TEST
,
depress
the
test
position
stop
lever
and
pull
the
breaker
out
of
its
compartment
until
the
tray
stops
.
At
this
position
the
tray
will
be
fully
withdrawn
against
its
limit
stop
.
The
withdrawal
movement
for
electrically
operated
breakers
differs
from
the
above
in
that
the
tray
is
stopped
short
of
its
WITHDRAWN
limit
by
the
compartment
-
mounted
spring
discharge
stop
.
In
order
to
complete
the
withdrawal
,
the
closing
springs
first
must
be
discharged
by
depressing
the
spring
discharge
lever
on
the
breaker
.
Next
,
keeping
this
lever
depressed
,
pull
the
breaker
completely
out
against
the
tray
limit
stop
.
A
ramp
cam
mounted
on
the
compartment
wall
keeps
the
breaker
trip
-
free
during
the
outward
travel
from
the
TEST
position
.
5
.
Before
proceeding
with
subsequent
operations
to
re
-
move
the
breaker
from
the
tray
,
visually
check
the
breaker
’
s
CHARGED
-
DISCHARGED
and
OPEN
-
CLOSED
indicators
to
verify
that
the
breaker
is
open
and
the
springs
are
discharged
.
This
precaution
is
particularly
important
at
locations
where
AKR
-
75
and
-
100
breakers
are
being
deployed
in
AKD
equipments
as
replacements
for
AK
-
75
and
-
100
non
-
quick
-
close
electrical
models
;
these
compartments
did
not
need
and
were
not
equipped
with
a
spring
discharge
stop
.
i
NOTE
:
A
spring
discharge
stop
will
not
be
present
in
some
AKD
-
type
compartments
originally
furnished
for
electrically
operated
AK
-
75
and
AK
-
100
breakers
of
the
non
-
quick
-
close
type
.
9
.
Depress
the
TEST
position
stop
lever
and
push
the
breaker
farther
into
the
compartment
until
the
outer
surfaces
of
the
racking
cams
butt
against
the
racking
pins
in
the
housing
.
10
.
Insert
the
racking
handle
(
673
D
0500
-
636
-
05
)
on
the
jackscrew
shaft
at
the
upper
right
side
of
the
breaker
.
Rotate
it
clockwise
until
the
jackscrew
comes
to
a
solid
stop
.
The
breaker
is
now
in
the
CONNECTED
position
.
5.2
.
2
BREAKER
REMOVAL
1
.
With
the
door
closed
and
latched
,
trip
the
breaker
.
6
.
Remove
the
two
-
%
inch
hex
-
head
screws
which
fasten
the
breaker
to
the
compartment
tray
.
2
.
Open
the
door
and
insert
the
racking
handle
on
the
jackscrew
shaft
.
Rotate
it
counterclockwise
until
the
jack
-
screw
comes
to
a
solid
stop
.
At
this
point
the
primary
discon
-
nects
are
disengaged
.
3
.
Now
pull
the
breaker
out
of
its
compartment
until
the
test
position
stop
engages
,
thereby
holding
the
breaker
in
the
TEST
position
.
7
.
Using
care
to
prevent
damage
to
the
wiring
,
attach
the
lifting
device
to
the
cutout
notches
in
the
top
wraparound
frame
of
the
breaker
.
i
i
Fig
.
1
AKR
-
2
-
75
electrically
operated
,
2
-
pole
Dc
(
AKD
type
)
7
Courtesy of NationalSwitchgear.com
8
.
Lift
the
breaker
approximately
one
-
half
inch
off
the
dowel
pins
.
Push
the
tray
back
into
the
compartment
.
With
the
door
open
,
the
breaker
is
manually
pulled
out
from
the
DISCONNECTED
to
the
WITHDRAWN
position
;
here
the
breaker
is
completely
out
of
its
compartment
,
ready
for
moval
.
re
-
i
9
.
Swing
the
breaker
forward
until
the
primary
discon
-
nects
clear
the
compartment
.
Lower
the
breaker
onto
a
flat
surface
free
of
protrusions
that
could
damage
the
breaker
’
s
internal
parts
.
NOTE
:
All
electrically
operated
AKR
-
751100
breakers
employ
a
spring
discharge
interlock
which
prevents
removal
of
the
breaker
with
its
clos
-
ing
springs
in
the
charged
state
.
Before
the
breaker
can
be
moved
away
from
the
DISCON
-
NECTED
position
toward
the
WITHDRAWN
posi
-
tion
,
it
is
necessary
to
depress
and
hold
the
breaker
-
mounted
spring
discharge
lever
(
Fig
.
2
)
.
This
discharges
the
closing
springs
and
releases
the
breaker
.
Manually
operated
breakers
do
not
require
this
interlock
because
their
closing
springs
are
never
propped
in
the
fully
charged
position
.
Refer
to
the
“
Manual
Closing
”
text
in
section
8.2
.
5.3
.
1
BREAKER
INSERTION
(
CODE
A
)
1
.
Prior
to
lifting
a
breaker
to
its
intended
compartment
location
,
observe
the
following
precautions
:
a
.
Check
the
compartment
to
insure
that
it
is
free
of
foreign
objects
.
b
.
Verify
that
the
breaker
is
the
correct
type
for
that
compartment
.
c
.
Insure
that
the
breaker
is
OPEN
.
d
.
Apply
a
thin
,
fresh
coat
of
D
50
HD
3
Q
lubricant
to
the
breaker
’
s
primary
disconnects
.
5.3
CODE
A
(
AKD
SWITCHGEAR
)
The
drawout
mechanism
is
equipment
mounted
and
is
externally
operated
by
a
removable
racking
handle
.
The
breaker
is
supported
by
two
pins
protruding
from
each
side
of
its
frame
,
these
engaging
slots
in
telescoping
rails
fastened
to
the
compartment
walls
.
The
drawout
operation
features
four
positions
—
CON
-
NECTED
,
TEST
,
DISCONNECTED
and
WITHDRAWN
.
In
the
CONNECTED
position
the
primary
and
secondary
dis
-
connects
are
fully
engaged
.
The
breaker
must
be
tripped
before
it
can
be
racked
into
or
out
of
this
position
.
In
the
TEST
position
the
primary
contacts
are
disconnected
but
the
sec
-
ondary
contacts
remain
engaged
.
This
allows
complete
breaker
operation
without
energizing
the
primary
circuit
.
In
the
DISCONNECTED
position
neither
primary
nor
second
-
ary
contacts
are
made
.
Breakers
can
be
racked
between
these
three
positions
with
the
compartment
door
closed
.
Each
position
is
clearly
identified
by
a
rotary
indicator
visible
through
an
opening
in
the
door
.
i
ft
Fig
.
2
AKR
-
5
A
-
75
electrically
operated
(
AKD
-
5
,
6
type
)
8
Courtesy of NationalSwitchgear.com
5
.
Attach
lifting
hooks
at
the
cutouts
in
the
top
wrap
-
around
frame
and
raise
the
breaker
until
its
mounting
pins
clear
the
track
slots
.
6
.
Push
the
tracks
into
the
compartment
so
that
the
breaker
can
be
lowered
to
a
smooth
surface
free
of
protru
-
sions
that
could
damage
the
internal
parts
of
the
breaker
.
2
.
With
the
movable
inner
housing
of
the
compartment
in
the
CONNECTED
position
,
insert
the
racking
handle
(
part
no
.
673
D
0500
-
636
-
05
)
on
the
jackscrew
shaft
located
at
the
left
side
of
the
compartment
just
above
the
position
indicator
.
3
.
Rotate
the
handle
counterclockwise
until
the
jack
-
screw
stops
—
the
indicator
should
read
DISC
.
4
.
Remove
the
racking
handle
and
open
the
compart
-
ment
door
.
5
.
Rotate
the
two
track
-
lock
links
and
pull
the
right
track
to
the
limit
of
its
travel
.
6
.
Using
a
lifting
device
,
raise
the
breaker
until
the
breaker
mounting
pins
are
approximately
one
-
inch
above
the
tracks
.
Use
care
to
avoid
damage
to
the
breaker
wiring
.
7
.
Pull
the
left
track
out
to
the
limit
of
its
travel
and
lower
the
breaker
so
its
mounting
pins
drop
into
the
slots
in
the
track
.
Remove
the
lifting
device
.
8
.
Push
the
breaker
in
against
the
track
stops
.
On
electri
-
cally
operated
breakers
,
be
sure
to
depress
the
spring
dis
-
charge
lever
while
doing
so
.
Rotate
the
two
track
-
lock
links
to
lock
the
breaker
in
place
.
Close
the
compartment
door
.
9
.
Insert
the
racking
handle
on
the
jackscrew
shaft
and
rotate
it
clockwise
to
move
breaker
into
the
compartment
.
Breaker
is
in
CONNECTED
position
when
jackscrew
stops
.
The
indicator
should
read
CONN
.
10
.
Orient
the
jackscrew
so
that
its
slotted
sleeve
is
free
to
move
outward
,
otherwise
the
breaker
will
remain
trip
-
free
.
<
5.4
CODE
B
(
AKR
SUBSTRUCTURE
)
(
Figs
.
3
,
4
)
The
AKR
substructure
is
a
self
-
contained
,
open
-
type
framework
serving
as
the
stationary
receptacle
for
a
drawout
breaker
.
Featuring
closed
-
door
type
drawout
operation
,
it
is
designed
for
convenient
mounting
in
individual
breaker
com
-
partments
of
drawout
switchgear
equipments
.
It
provides
means
for
making
the
primary
and
secondary
connections
to
the
removable
breaker
element
and
is
factory
aligned
.
The
breakers
are
bolted
to
a
roller
-
mounted
tray
which
is
part
of
the
substructure
.
The
racking
mechanism
is
breaker
-
mounted
.
The
racking
handle
is
inserted
through
the
com
-
partment
door
and
acts
to
rotate
slotted
racking
cams
on
each
side
of
the
breaker
frame
.
The
cams
engage
fixed
pins
mounted
on
both
side
plates
of
the
substructure
,
moving
the
breaker
in
and
out
through
the
same
four
positions
described
for
the
Code
A
Types
—
CONNECTED
,
TEST
,
DISCON
-
NECTED
,
WITHDRAWN
.
Breaker
position
is
registered
di
-
rectly
by
markings
on
the
right
side
of
the
escutcheon
which
appear
as
*
it
emerges
through
the
door
cutout
.
All
AKR
B
breakers
for
use
in
substructures
are
equipped
with
a
"
deep
”
escutcheon
instead
of
the
standard
escut
-
cheon
employed
on
all
other
models
.
This
configuration
al
-
lows
the
breaker
to
be
racked
between
the
CONNECTED
and
DISCONNECTED
positions
with
the
door
closed
.
The
door
does
not
move
with
the
breaker
as
it
does
in
the
AKD
-
5
and
AKD
-
6
models
.
5.3
.
2
BREAKER
REMOVAL
(
CODE
A
)
1
.
Trip
the
breaker
.
Insert
the
racking
handle
into
the
jack
-
screw
shaft
.
2
.
Rotate
the
handle
counterclockwise
until
the
jackscrew
stops
.
Indicator
should
read
DISC
.
3
.
Remove
the
racking
handle
and
open
the
compartment
door
.
4
.
Rotate
the
two
track
-
lock
links
and
pull
the
breaker
out
to
the
track
travel
limit
.
This
is
the
WITHDRAWN
position
.
If
the
breaker
is
electrically
operated
,
the
breaker
-
mounted
Spring
Discharge
lever
must
be
depressed
to
permit
with
-
drawal
.
<
NOTE
:
Spring
discharge
interlocks
were
not
re
-
quired
and
are
not
present
in
existing
compart
-
ments
originally
furnished
for
non
-
quick
-
close
type
electrically
operated
AK
-
75
/
100
breakers
.
Regard
-
less
of
whether
this
interlocking
hardware
is
present
in
a
compartment
,
ALWAYS
verify
that
the
closing
springs
are
discharged
and
the
breaker
is
tripped
OPEN
before
removal
is
attempted
.
Fig
.
3
AKR
drawout
substructure
Cat
.
No
.
TAK
8
SS
02
3200
amperes
i
9
Courtesy of NationalSwitchgear.com
I
5.4
.
1
BREAKER
INSERTION
(
CODE
B
)
5
.
Lower
the
breaker
over
the
tray
until
it
is
about
one
-
half
inch
above
the
two
dowel
pins
on
the
tray
.
Push
the
breaker
back
into
the
compartment
until
the
rear
bottom
flange
of
the
breaker
rests
against
the
guides
behind
the
dowel
pins
.
6
.
Slowly
lower
and
guide
the
breaker
onto
the
tray
so
the
holes
in
the
rear
flange
fit
over
the
two
dowel
pins
.
When
correctly
positioned
on
the
dowel
pins
,
the
breaker
’
s
rear
and
side
bottom
flanges
will
rest
firmly
on
the
tray
.
7
.
Secure
the
breaker
to
the
tray
by
inserting
and
tighten
-
ing
two
-
%
inch
hex
head
screws
into
the
front
holes
of
its
side
flanges
.
8
.
Push
the
breaker
into
the
compartment
until
the
spring
discharge
stop
engages
,
preventing
further
movement
.
This
is
the
DISCONNECTED
position
.
At
this
point
the
racking
cams
are
positioned
to
engage
the
fixed
racking
pins
in
the
compartment
,
ready
to
begin
the
racking
motion
.
It
is
to
be
noted
that
manually
operated
breaker
models
do
not
employ
a
spring
discharge
interlock
.
It
is
unnecessary
because
their
operating
mechanism
never
statically
posi
-
tions
the
springs
in
a
fully
-
charged
state
.
However
,
to
provide
necessary
means
for
mechanically
securing
the
breaker
in
the
DISCONNECTED
position
,
a
position
stop
is
employed
.
It
has
a
release
lever
marked
“
Push
to
Withdraw
”
and
is
located
in
the
same
place
as
the
spring
discharge
release
lever
on
electrically
operated
breakers
—
see
Fig
.
4
.
1
.
Prior
to
lifting
a
breaker
to
its
intended
compartment
location
,
observe
the
following
precautions
:
a
.
Check
the
compartment
to
insure
that
it
is
free
of
foreign
objects
.
b
.
Verify
that
the
breaker
is
the
correct
type
for
that
compartment
.
c
.
Insure
that
the
breaker
is
OPEN
.
d
.
Apply
a
thin
,
fresh
coat
of
D
50
HD
38
lubricant
to
the
breaker
’
s
primary
disconnects
.
e
.
Insure
that
the
racking
cams
on
the
breaker
are
correctly
positioned
for
initial
engagement
with
the
pins
in
the
compartment
.
To
do
this
,
insert
the
rack
-
ing
handle
and
rotate
it
fully
counterclockwise
.
2
.
Using
a
suitable
lifting
mechanism
and
spreader
rig
,
position
lifting
hooks
at
the
cutout
notches
in
the
top
wrap
-
around
frames
of
the
breaker
.
Exercise
care
to
avoid
damage
to
the
control
wiring
.
3
.
Open
the
compartment
door
.
Keeping
the
rollout
tray
positioned
inside
the
compartment
,
raise
the
breaker
above
the
elevation
of
the
tray
.
4
.
Pull
the
tray
all
the
way
out
to
its
WITHDRAWN
limit
.
i
FINGER
-
TYPE
PRIMARY
DISCONNECTS
“
PUSH
TO
WITHDRAW
”
RELEASE
LEVER
I
Fig
.
4
AKR
-
9
F
-
75
manually
operated
(
substructure
type
)
10
Courtesy of NationalSwitchgear.com