INSTRUCTION
i
Read this instruction before installation
and wiring of the product
HTDT10(-420) 1
HTDT10(-420)
Duct mounted humidity/temperature
transmitter
HTDT10 is a duct mounted humidity and temperature transmitter for
measuring relative humidity and temperature in air handling systems.
Available with 0...10 V DC or 4...20 mA output signal.
85
90
35
220
20-200
Ø12
100
Installation
Mount the transmitter in the duct using either the screw pockets in the en-
closure or the mounting ange provided. When mounted in contaminated
environments the transmitter’s membrane lter should be exchanged for a
sintered stainless steel lter (HA010103).
Wiring
Connect supply voltage and output signals according to the diagram for
the unit being installed.
V+
0
RH 0...10 V DC
Temp. 0...10 V DC
HTDT10
1
2
3
V+
Temp. 4...20 mA
HTDT10-420
RH 4...20 mA
1
2
3
4
Supply voltage:
HTDT10: 15...29 V AC or 15...35 V DC
HTDT10-420: 20...30 V DC
Output signals:
Humidity: 0...10 V DC (4...20 mA) corresponding to 0...100 % RH
Accuracy: ±2 % RH (0...90 % RH), ±3 % RH (90...100 % RH)
Temperature: 0...10 V DC (4...20 mA) corresponding to -20...+80°C
Accuracy at 20°C: ±0.2 K
External load impedance:
HTDT10: Min. 10 kΩ
HTDT10-420: Max. 500 Ω
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]e
i
Läs denna instruktion innan produkten
monteras och ansluts
INSTRUKTION
HTDT10(-420)
SV
Fukt-/temperaturtransmitter för kanalmontage
HTDT10 är en kanalmonterad fukt- och temperaturtransmitter för
mätning av relativ luftfuktighet och temperatur i klimat- och luftbehan-
dlingsanläggningar.
Kan erhållas för 0...10 V DC eller 4...20 mA utsignal.
85
90
35
220
20-200
Ø12
100
Installation
Transmittern monteras i kanal antingen med hjälp av skruvckorna i
apparathuset eller med hjälp av den bifogade fästänsen. Vid applika-
tioner i starkt förorenade miljöer bör känselkroppens membranlter
bytas mot ett sintrat lter av rostfritt stål (HA010103).
Inkoppling
Koppla in matningsspänning och signalkablage i enlighet med den
kopplingsbild som gäller för den installerade enheten.
V+
0
RH 0...10 V DC
Temp. 0...10 V DC
HTDT10
1
2
3
V+
Temp. 4...20 mA
HTDT10-420
RH 4...20 mA
1
2
3
4
11772E
JUL 18
EN
CE
This product carries the CE mark. More information is available
at www.regincontrols.com
HTDT10(-420)
ANLEITUNG
i
Diese Anleitung vor Installation und Verdrahtung
des Produktes bitte durchlesen
2
Matningsspänning:
HTDT10: 15...29 V AC eller 15...35 V DC
HTDT10-420: 20...30 V DC
Utsignaler:
Fukt: 0...10 V DC (4...20 mA) vilket motsvarar 0...100 % RH
Noggrannhet: ±2 % RH (0...90 % RH), ±3 % RH (90...100 % RH)
Temperatur: 0...10 V DC (4...20 mA) vilket motsvarar -20...+80°C
Noggrannhet vid 20°C: ±0,2 K
Belastningsimpedans:
HTDT10: Min.10 kΩ
HTDT10-420: Max. 500 Ω
Teknisk support
Teknisk hjälp och råd på telefon: 031 720 02 30
Kontakt
AB Regin, Box 116, 428 22 Kållered
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regin.se, [email protected]
Feuchte-/Temperatur-Transmitter für
Kanalmontage
Der HTDT10 ist ein Feuchte- und Temperatur-Transmitter für die Ka-
nalmontage, der zum Messen von relativer Feuchte und Temperatur in
Lüftungsanlagen geeignet ist.
Er ist mit einem Ausgangssignal von 0...10 V DC oder 4...20 mA erhältlich.
85
90
35
220
20 – 200
Ø 12
100
Montage
Montieren Sie den Transmitter entweder mit den Einschraubhülsen im
Gehäuse oder mit dem mitgelieferten Montageansch im Kanal. Bei einer
Montage in kontaminierten Umgebungen sollte der Membranlter des
Transmitters gegen einen Sinteredelstahllter (HA010103) ausgetauscht
werden.
Verdrahtung
Schließen Sie die Versorgungsspannung und die Verbindung zu den
Ausgangssignalen entsprechend dem Schaltplan für das zu installierende
Gerät an.
V+
0
rF 0...10 V DC
Temp. 0...10 V DC
HTDT10
1
2
3
V+
Temp. 4...20 mA
HTDT10-420
rF 4...20 mA
1
2
3
4
Versorgungsspannung:
HTDT10: 15...29 V AC oder 15...35 V DC
HTDT10-420: 20...30 V DC
Ausgangssignale:
Feuchtigkeit: 0...10 V DC (4...20 mA) entsprechend 0...100 % rF
Genauigkeit: ± 2 % rF (0...90 % rF), ± 3 % rF (90...100 % rF)
Temperatur: 0...10 V DC (4...20 mA) entsprechend -20...+80 °C
Genauigkeit bei 20 °C: ± 0,2 K
Externe Lastimpedanz:
HTDT10: Min. 10 kΩ
HTDT10-420: Max. 500 Ω
Kontakt
Regin Controls Deutschland GmbH
Telefon: +49 30 77 99 40
Internet: www.regincontrols.de
E-Mail: [email protected]
HTDT10(-420)
DE
CE
Denna produkt är CE-märkt. Mer information nns
på www.regincontrols.com
CE
Dieses Produkt trägt das CE-Zeichen. Mehr Information können
Sie auf www.regincontrols.com nden.

This manual suits for next models

1

Other Regin Transmitter manuals

Regin HTRT10A-420 User manual

Regin

Regin HTRT10A-420 User manual

Regin DMD-C User manual

Regin

Regin DMD-C User manual

Regin PDTX C Series User manual

Regin

Regin PDTX C Series User manual

Regin HTDT2500 User manual

Regin

Regin HTDT2500 User manual

Regin HTRT10A-420 User manual

Regin

Regin HTRT10A-420 User manual

Regin DMD User manual

Regin

Regin DMD User manual

Regin CTHRA User manual

Regin

Regin CTHRA User manual

Regin TRT5-420 User manual

Regin

Regin TRT5-420 User manual

Regin CTRTA User manual

Regin

Regin CTRTA User manual

Regin DMD-C User manual

Regin

Regin DMD-C User manual

Regin DMD User manual

Regin

Regin DMD User manual

Regin Presigo PDT C Series User manual

Regin

Regin Presigo PDT C Series User manual

Regin TRTN User manual

Regin

Regin TRTN User manual

Regin HTRT2500 User manual

Regin

Regin HTRT2500 User manual

Regin COF User manual

Regin

Regin COF User manual

Regin DTT4-420 User manual

Regin

Regin DTT4-420 User manual

Regin NO2F User manual

Regin

Regin NO2F User manual

Regin AVDT25 User manual

Regin

Regin AVDT25 User manual

Regin DMD-C User manual

Regin

Regin DMD-C User manual

Regin DMD User manual

Regin

Regin DMD User manual

Regin TDT200 User manual

Regin

Regin TDT200 User manual

Regin HTWT10 User manual

Regin

Regin HTWT10 User manual

Regin CO2DT-R User manual

Regin

Regin CO2DT-R User manual

Popular Transmitter manuals by other brands

Emerson Rosemount 5081 quick start guide

Emerson

Emerson Rosemount 5081 quick start guide

Adtech TCT-327-MOD instruction manual

Adtech

Adtech TCT-327-MOD instruction manual

GRAUPNER Kingpad mc-edition mc-28 user manual

GRAUPNER

GRAUPNER Kingpad mc-edition mc-28 user manual

evertz 7700 Series manual

evertz

evertz 7700 Series manual

Kimo CA 310 user manual

Kimo

Kimo CA 310 user manual

Zamel RNK-04 instruction manual

Zamel

Zamel RNK-04 instruction manual

Jamara CCX Pro Instruction

Jamara

Jamara CCX Pro Instruction

Dwyer Instruments CDTV Series Specifications-installation and operating instructions

Dwyer Instruments

Dwyer Instruments CDTV Series Specifications-installation and operating instructions

Analytical Technology Q45 manual

Analytical Technology

Analytical Technology Q45 manual

AMIMON CONNEX ProSight Installation and operation guide

AMIMON

AMIMON CONNEX ProSight Installation and operation guide

Mantracourt T24-ACMm user manual

Mantracourt

Mantracourt T24-ACMm user manual

Gonnheimer Elektronic D122.T user manual

Gonnheimer Elektronic

Gonnheimer Elektronic D122.T user manual

Multiplex Profi MC 3030 manual

Multiplex

Multiplex Profi MC 3030 manual

HaiKe DAB-005B user manual

HaiKe

HaiKe DAB-005B user manual

Monarch Transmitter Solutions 418ELPW2K manual

Monarch

Monarch Transmitter Solutions 418ELPW2K manual

Danfoss AKS 41 Technical leaflet

Danfoss

Danfoss AKS 41 Technical leaflet

Nuomm NEWSCASTER VT2 user manual

Nuomm

Nuomm NEWSCASTER VT2 user manual

GE AquaTrans AT868 user manual

GE

GE AquaTrans AT868 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.