Satel ACU-120 User manual

ABAX WIRELESS SYSTEM CONTROLLER
ACU-120
Firmware version 5.03 acu-120_en 10/17
SATEL sp. z o.o.
ul. Budowlanych 66
80-298 Gdańsk
POLAND
tel. + 48 58 320 94 00
www.satel.eu

WARNINGS
The device should be installed by qualified personnel.
Prior to installation, please read carefully this manual in order to avoid mistakes that can lead
to malfunction or even damage to the equipment.
Disconnect power before making any electrical connections.
Changes, modifications or repairs not authorized by the manufacturer shall void your rights
under the warranty.
SATEL's goal is to continually upgrade the quality of its products, which may result in some
changes of their technical specifications and firmware. The current information on
the introduced modifications is available on our website.
Please visit us:
http://www.satel.eu
Hereby, SATEL sp. z o.o., declares that this device is in compliance with the essential
requirements and other relevant provisions of Directive 2014/53/EU. The declaration of
conformity may be consulted at www.satel.eu/ce
The following symbols may be used in this manual:
- note;
- caution.

Changes made to the firmware version 5.03
Support for the INT-KWRL wireless keypad.
Possibility to define whether the AMD-101 detector is to occupy one or two positions on
the list of wireless devices.

2 ACU-120 SATEL
CONTENTS
1. Introduction .......................................................................................................................3
2. Features............................................................................................................................3
3. Specifications....................................................................................................................3
4. Electronics board ..............................................................................................................4
4.1 Terminals...................................................................................................................5
4.2 DIP-switches..............................................................................................................5
4.2.1 Controller connected to the INTEGRA / INTEGRA Plus control panel ...............5
4.2.2 Controller connected to the VERSA / VERSA Plus / VERSA IP control panel....5
5. Installation of the controller ...............................................................................................5
6. Programming the controller...............................................................................................7
6.1 Parameters, options and functions ............................................................................8
7. Wireless devices ...............................................................................................................9
7.1 Wireless devices supported by the controller ............................................................9
7.2 Installation of wireless devices.................................................................................10
7.2.1 Work with the INTEGRA / INTEGRA Plus control panels.................................11
7.2.2 Work with the VERSA / VERSA Plus / VERSA IP control panels .....................14
7.3 Programming the wireless devices ..........................................................................14
7.3.1 Parameters and options....................................................................................14
7.3.2 Programming in the INTEGRA / INTEGRA Plus system ..................................16
7.3.3 Programming in the VERSA / VERSA Plus / VERSA IP system ......................18
7.4 Specific character of the operation of wireless devices ...........................................19
7.4.1 Wireless detectors ............................................................................................19
7.4.2 Wireless sirens .................................................................................................19
7.4.3 Wireless expanders of hardwired zones and outputs .......................................20
7.4.4 230 V AC wireless controllers...........................................................................21
7.4.5 Radio signal repeater .......................................................................................21
8. Wireless keypads............................................................................................................22
8.1 Wireless keypads supported by the controller .........................................................22
9. APT-100 keyfobs ............................................................................................................22
9.1 Keyfobs in the INTEGRA / INTEGRA Plus system ..................................................22
9.1.1 Adding the APT-100 keyfob by means of the DLOADX program .....................24
9.1.2 Removing the APT-100 keyfob by means of the DLOADX program ................24
9.2 Keyfobs in the VERSA / VERSA Plus / VERSA IP system ......................................24
10. Manual update history.....................................................................................................26

SATEL ACU-120 3
1. Introduction
The ACU-120 controller works with the INTEGRA, INTEGRA Plus, VERSA, VERSA Plus and
VERSA IP control panels. It enables expansion of the security alarm system by adding the
ABAX wireless devices and keypads. The ABAX system is based on two-way
communication. All transmissions are acknowledged, which ensures that the information has
been received and makes it possible to check the presence of devices in the system in real
time. Configuration of parameters and testing of the ABAX system wireless devices is
performed by radio, so dismounting of their enclosures is unnecessary. Additionally, the
controller allows to operate the alarm system, using the ABAX system two-way keyfobs.
The name plate of the controller is located on the enclosure base. After installation of the
device, the name plate is not visible to the user.
2. Features
Support for up to 48 ABAX system wireless devices (the number of supported devices
depends on the control panel).
Support for up to 8 ABAX system wireless keypads (the number of supported keypads
depends on the control panel).
Support for up to 248 APT-100 keyfobs (the number of supported keyfobs depends on the
control panel).
Two-way encrypted radio communication in the 868 MHz frequency band.
Antenna diversification – automatic selection of the antenna that will be used for receiving
transmission, depending on the level of received radio signal.
Controller firmware update capability.
Tamper switch responding to opening of the enclosure.
Tamper input.
3. Specifications
Supply voltage ................................................................................................... 12 V DC ±15%
Standby current consumption ..........................................................................................50 mA
Maximum current consumption........................................................................................75 mA
Operating frequency band ...................................................................868.0 MHz ÷ 868.6 MHz
Radio communication range (in open area) ............................................................ up to 500 m
Security grade according to EN50131-3 ....................................................................... Grade 2
Complied with standards..EN 50130-4, EN 50130-5, EN 50131-1, EN 50131-3, EN 50131-5-3
Environmental class according to EN50130-5 ......................................................................... II
Operating temperature range...............................................................................-10°C...+55°C
Maximum humidity..........................................................................................................93±3%
Electronics board dimensions ............................................................................. 103 x 139 mm
Enclosure dimensions..................................................................................126 x 158 x 32 mm
Weight............................................................................................................................... 202 g

4 ACU-120 SATEL
4. Electronics board
Fig. 1. Controller electronics board.
Explanations to Fig. 1:
antenna 2 (printed on the electronics board and designated as AN2).
LED indicating the status of communication with the control panel:
ON – no communication with the control panel,
blinking – communication with the control panel OK.
tamper switch.
DIP-switches.
terminals.
antenna 1 (printed on the electronics board and designated as AN1).

SATEL ACU-120 5
RS-232 port (TTL standard) to enable updating the controller firmware. The controller can
be connected to the computer using the USB-RS converter offered by SATEL.
4.1 Terminals
+12V - power input.
COM - common ground.
CKM - keypad bus clock.
DTM - keypad bus data.
CKE - expander bus clock.
DTE - expander bus data.
A RS485 B - terminals provided for future applications (RS-485).
TMP - tamper input (NC). Connected in parallel with the tamper switch.
If the controller is installed in the enclosure in which tamper switch is open, and the
enclosure tamper switch is not to be connected to the tamper input, connect the TMP
terminal to the COM terminal of the controller.
4.2 DIP-switches
The switch 7 defines which of the antennas is to be used for transmitting:
OFF position – antenna 1 (AN1),
ON position – antenna 2 (AN2).
Thus you can select the antenna whose polarization is consistent with that of the antennas in
wireless devices installed in the system. This contributes to the quality of the radio signal.
Functions of the other switches depend on which control panel the controller is connected to.
4.2.1 Controller connected to the INTEGRA / INTEGRA Plus control panel
The DIP-switches 1-5 are used for address setting. A numerical value is assigned to each
switch. In OFF position, the value is 0. Numerical values assigned to individual switches in
ON position are shown in Table 1. The sum of numerical values assigned to switches 1-5
means the address set on the device. The address must be different from that on the other
devices connected to the expander bus of the control panel.
DIP-switch number 1 2 3 4 5
Numerical value 1 2 4 8 16
Table 1.
Set the DIP-switch 8 to OFF position.
When connecting the controller to the control panel to which the ABAX system
controller is already connected, it is recommended that a higher address be set in the
new controller than that in the controller already connected to the control panel.
4.2.2 Controller connected to the VERSA / VERSA Plus / VERSA IP control
panel
Set the switch 8 in ON position. Status of the switches 1-6 is irrelevant.
5. Installation of the controller
Disconnect power before making any electrical connections.

6 ACU-120 SATEL
The alarm system installation to which the controller is to be connected should
be provided with:
2-pole disconnector,
short-circuit protection with a 16 A time delay circuit breaker.
The controller should be installed indoors, in spaces with normal air humidity. Prior to
installation you should plan the arrangement of all ABAX system wireless devices which are
to be operated by the controller. Select the installation place so that these devices are
located within the controller operating range. Remember that thick walls, metal partitions, etc.
will reduce the range of the radio signal. It is recommended that the controller be mounted
high above the floor. This will allow you to get a better range of radio communication and
avoid the risk of the controller being accidentally covered by people moving around the
premises. Mounting the controller near electrical installations is not advisable, as this may
cause malfunction of the device.
Several ABAX wireless system controllers can work within each other's range. Automatic
synchronization with the wireless systems already in use is always performed when the
controller is switched on, and after each operation of addition/removal of supported devices.
The number of wireless devices working within each other's range depends on the R
ESPONSE
PERIOD
(see “Parameters, options and functions” p. 8) and can vary from 150 to 450. The
higher the response frequency, the lower the number of devices that can work within each
other's range.
1. Loosen the cover locking screws and remove the enclosure cover.
2. Remove the fastening screws of electronics board and remove the electronics board.
3. Place the enclosure base against the wall and mark location of the mounting holes. Set
the enclosure so that the cable entry opening is situated at the bottom of the enclosure or
at the base.
4. Drill the holes in the wall for wall plugs (screw anchors).
5. Make the cable entry opening at the base. The opening diameter should not exceed
10 mm. The finished opening must not have sharp edges.
6. Using wall plugs (screw anchors) and screws, secure the enclosure base to the wall
When installed, the device must withstand a pull-off force of at least 50 N.
7. Using screws, install the electronics board in the enclosure.
8. Set the DIP-switches as required (see: “DIP-switches”).
9. Depending on the control panel to which the controller is to be connected:
INTEGRA / INTEGRA Plus: connect the CKM, DTM, CKE, DTE and COM terminals to the
corresponding terminals of the control panel communication buses (refer to the control
panel installer manual). If the controller is not to support the wireless keypads, the CKM
and DTM terminals do not need to be connected.
VERSA / VERSA Plus / VERSA IP: connect the CKE, DTE and COM terminals to the
corresponding terminals of the control panel communication bus (refer to the control
panel installer manual).
It is recommended that an unshielded non-twisted cable be used to make the connection.
If you use the twisted-pair type of cable, remember that the DTM and CKM / CKE and
DTE (clock and data) signals must not be sent through one pair of twisted conductors.
The conductors must be run in one cable. Prevent the cables from coming into contact
with sharp edges to avoid damage to the cables.

SATEL ACU-120 7
Fig. 2. Method of connecting the controller to the control panel.
10.Connect the power cables to the 12V and COM terminals. Use conductors with a cross-
section of 1 – 2.5 mm
2
. The controller may be powered directly from the control panel,
from an expander with power supply, or from a power supply unit with current limitation up
to 3 A.
11.Replace the cover and then lock it with the screw.
12.Power on the alarm system.
13.Start the identification function in the control panel (see the control panel installer
manual). The module will be identified as “ACU-100”.
6. Programming the controller
Programming of the controller is carried out by means of the control panel, using:
the LCD keypad in service mode:
– INTEGRA / INTEGRA Plus – the controller programming functions are available in the
S
ETTINGS
submenu (S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
). Upon
entering the submenu, a list of devices will be displayed. Using the and keys, find
the controller name and press the key to get access to the list of functions. To
program the controller name, use the N
AMES
submenu (S
TRUCTURE
H
ARDWARE
E
XPANDERS
N
AMES
).
– VERSA / VERSA Plus / VERSA IP – most of the controller parameters can be
programmed in the 2. S
ETTINGS
submenu (2. H
ARDWARE
1. K
PDS
&
EXPS
.
2. S
ETTINGS
). Upon entering the submenu, a list of devices will be displayed. Using
the and keys, find the controller name and press the key to start the “step by

8 ACU-120 SATEL
step” programming. The functions to start synchronization and to enter / exit the test
mode are available in the 3. W
IRELESS MOD
. submenu (2. H
ARDWARE
1. K
PDS
&
EXPS
.
3. W
IRELESS MOD
.).
the
DLOADX program:
– INTEGRA / INTEGRA Plus – in the “Structure” window, “Hardware” tab, after clicking on
the controller name in the list of devices (Fig. 3);
– VERSA / VERSA Plus / VERSA IP – in the “Versa – Structure” window, “Hardware” tab,
after clicking on the controller name.
6.1 Parameters, options and functions
Fig. 3. DLOADX
program: parameters and options of the controller connected to INTEGRA /
INTEGRA Plus control panel.
Name – individual name of device (up to 16 characters).
Tamper signaled in partition – the partition in which tamper alarm will be triggered in the
event of module tamper.
No auto-reset after three module tamper alarms – if this option is enabled, the feature
reducing the number of tamper alarms from the module to three is disabled (the feature
prevents multiple logging of the same events and applies to successive uncleared alarms).
Response period – communication with wireless devices takes place in specified intervals.
The controller is then gathering information on the status of wireless devices and, if
necessary, sending commands to the devices, e.g. switching the detectors to their
active/passive state, switching on/off the test mode and/or changing configuration of the
devices. The response period can be 12, 24 or 36 seconds. The less often communication
between the controller and the wireless devices takes place, the more wireless devices
can work within each other's operating range (12 seconds – up to 150, 24 seconds – up to
300, 36 seconds – up to 450). Beyond the response period, information about tampers of

SATEL ACU-120 9
devices and violations of detectors operating in active mode are sent to the controller. The
response period has an effect on the level of energy consumption by the wireless devices.
The less often communication between the controller and the wireless devices takes
place, the lower energy consumption and the longer battery life are.
In the case of the AMD-103 detector and ASP-100 siren, no communication takes
place during polling.
Higher sensitivity for jamming detection – if this option is enabled, the sensitivity of
detection of radio communication jamming is boosted.
Synchronize – this function starts the procedure of synchronization, i.e. checking for
presence of other ABAX wireless system controllers working within the controller operating
range. The controller will synchronize the response period so that the radio transmissions
of some controllers should not be mutually jammed. Synchronization is performed
automatically upon starting the controller and after each operation of adding/removing
devices supported by it.
Test mode – in the ABAX system the test mode can be started, in which:
– LED indicators are enabled in the wireless devices (the LEDs are disabled during
normal operation) – information provided by means of the LEDs depends on the device;
– signaling is blocked in the ASP-105 and ASP-205 sirens.
The test mode is started/ended during polling, which results in a delay, its duration
depending on the programmed response period. The test mode will be turned off
automatically after 30 minutes of:
– starting the test mode from the DLOADX program (the 30-minute period is running from
the moment of exiting the controller settings),
– exiting the service mode in the control panel.
According to requirements of the EN50131 standard, the level of radio signals sent by
wireless devices is reduced during the test mode operation.
For the AMD-103 detector, entering the test mode remotely is not possible.
7. Wireless devices
The wireless keypads constitute a special category of devices and therefore they are
discussed in a separate section.
7.1 Wireless devices supported by the controller
Detectors
AFD-100 – wireless water flood detector.
AGD-100 – wireless glass-break detector.
AMD-100 – wireless magnetic contact.
AMD-101 – dual channel wireless magnetic contact.
AMD-102 – wireless magnetic contact with input for roller shutter detector.
AMD-103 – wireless magnetic contact.
AOCD-250 – wireless outdoor dual technology curtain detector.
AOD-200 – wireless outdoor dual technology motion detector.
APD-100 – wireless passive infrared detector.
APMD-150 – wireless dual technology motion detector.

10 ACU-120 SATEL
ARD-100 – wireless reorientation detector.
ASD-110 – wireless smoke and heat detector.
ASD-150 – wireless smoke detector.
ATD-100 – wireless temperature detector [supported, if the controller works with the
INTEGRA or INTEGRA Plus control panel].
AVD-100 – wireless vibration detector and magnetic contact.
Sirens
ASP-100 – wireless outdoor siren.
ASP-105 – wirelessly triggered outdoor siren.
ASP-205 – wireless indoor siren.
Other
ACX-200 – hardwired zone / output expander.
ACX-201 – hardwired zone / output expander with power supply.
ARF-100 – radio signal level tester.
ARU-100 – radio signal repeater [supported, if the controller works with the INTEGRA or
INTEGRA Plus control panel].
ASW-100 E / ASW-100 F – 230 V AC wireless controller.
7.2 Installation of wireless devices
After the control panel has identified the controller, you can begin installation of the ABAX
system wireless devices. Before installing a wireless device, check the level of radio signal
received by the device from controller and by the controller from device at the planned
installation place. The ARF-100 tester is a useful tool to check the signal level. The level of
signal received by device/controller may not be lower than 40%. If the radio signal level at the
planned installation place is too low, select another installation location. Sometimes it is
sufficient to move the device ten or twenty centimeters to obtain a significant improvement of
signal quality. You can install the device permanently only after reaching the optimum level of
radio signal.
The wireless devices must be registered to the alarm system. This can be done using the
LCD keypad or DLOADX program. The controller can support up to 48 wireless devices, but
some devices take up more than one position on the list. For example, after adding to the
system the ACX-200 expander module, which takes up 4 positions on the list of devices, the
controller will still be able to handle 44 more wireless devices. The number of positions on the
list is at the same time the number of zones and, in case of some devices, also outputs which
will be taken by the device in the system.
The data relating to wireless devices are stored in the controller. If the controller with
registered wireless devices is connected to the control panel, the wireless devices will
be automatically assigned to the system zones/outputs during identification procedure.
For some wireless devices, you can select whether the device will take up one or two
positions (channels) on the list of devices. Depending on the device, if one position is
selected:
AMD-101 – only additional NC input will be supported,
AMD-102 – only additional inputs (roller shutter and NC) will be supported,
AOD-200 – only the motion detector will be supported,
ATD-100 – you will be able to program only one temperature threshold,
AVD-100 – only the vibration detector will be supported.

SATEL ACU-120 11
7.2.1 Work with the INTEGRA / INTEGRA Plus control panels
The number of supported wireless devices depends on the control panel.
When adding and removing the wireless devices, remember that the identification function
registers zones and outputs by groups of 8. Already after adding one wireless device which
takes up 1 zone, the control panel will reserve 8 zones in the system for wireless devices.
The LCD keypad makes it possible to select the zone to which that device will be assigned.
Observe continuity, i.e. avoid leaving any gaps in the list, which will later reduce the number
of available zones in the system. Remember to preserve continuity also when removing
wireless devices. For example, if the devices registered in the controller occupy 9 positions
on the list, then 16 zones (2x8) are reserved in the system. After removal of the device which
occupied position 7 on the list, there will still be 16 zones (2x8) reserved in the system for
wireless devices, although 8 positions are actually taken up on the list of wireless devices
(see: Table 2). In such a case, it is recommended that the last devices be removed from the
list and then added to the system again, so as to fill up the gap in the list and reduce the
number of zones reserved for wireless devices.
INTEGRA / INTEGRA Plus
ACU-120 zones outputs
It.. list of devices No device No device
1 APD-100 detector 17 APD-100 detector 17 unused/unavailable
2 APD-100 detector 18 APD-100 detector 18 unused/unavailable
3 AMD-100 detector 19 AMD-100 detector 19 unused/unavailable
4 AMD-100 detector 20 AMD-100 detector 20 unused/unavailable
5 AMD-101 detector 21 AMD-101 detector 21 unused/unavailable
6 ^ 22 AMD-101 detector 22
unused/unavailable
7 23 unused/unavailable 23
unused/unavailable
8 ASP-105 siren
8
24 ASP-105 siren 24 ASP-105 siren
9 ^ 25 ASP-105 siren 25 ASP-105 siren
10 26 unused/unavailable 26
unused/unavailable
11 27 unused/unavailable 27
unused/unavailable
12 28 unused/unavailable 28
unused/unavailable
13 29 unused/unavailable 29
unused/unavailable
14 30 unused/unavailable 30
unused/unavailable
15 31 unused/unavailable 31
unused/unavailable
16
8
32 unused/unavailable 32
unused/unavailable
Table 2. An example of how the wireless devices should not be registered. For devices taking
up 8 positions, the system must reserve 16 zones and 16 outputs, as well as 2 addresses.
INTEGRA / INTEGRA Plus
ACU-120 zones outputs
It. list of devices No device No device
1 ASP-105 siren 17 ASP-105 siren 17 ASP-105 siren
2 ^ 18 ASP-105 siren 18 ASP-105 siren
3 APD-100 detector 19 APD-100 detector 19 unused/unavailable
4 APD-100 detector 20 APD-100 detector 20 unused/unavailable
5 AMD-100 detector 21 AMD-100 detector 21 unused/unavailable
6 AMD-100 detector 22 AMD-100 detector 22 unused/unavailable
7 AMD-101 detector 23 AMD-101 detector 23 unused/unavailable
8 ^
8
24 AMD-101 detector 24 unused/unavailable
Table 3. An example of how to correctly register the wireless devices (compare also Fig. 4).
For 8 devices, the system has reserved 8 zones and 8 outputs, as well as 1 address.

12 ACU-120 SATEL
In case of devices which, in addition to zones, also take up outputs, it is recommended that
you add them to the system first. This will allow you to maintain the continuity of use of not
the zones alone, but the outputs as well. Table 2shows a situation in which the siren first
output occupies position 8, and the second output – position 9. As a result, 16 outputs have
been reserved for wireless devices in the system, though actually 2 outputs are used (the
eighth output in the first group of 8 outputs and the first output in the second group of 8
outputs).
In some cases, the gaps in the list of zones/outputs cannot be avoided. It applies to situation
when the number of zones/outputs, which is used by the devices, is not a multiple of 8.
Fig. 4. DLOADX
program: the list of wireless devices registered in the controller connected to
INTEGRA / INTEGRA Plus control panel.
For each group of 8 zones /outputs, one address on the expander bus is reserved. The
controller can occupy from 1 to 6 addresses. This must be taken into account at the system
design stage and sufficient number of free addresses must be left for the controller. If, when
new wireless devices have been added to the controller, it turns out that next addresses are
needed, and these are taken up by other devices, successful completion of the expander
identification procedure will be impossible. It will be necessary to change addresses of the
devices connected to the bus.
Adding new wireless devices
DLOADX program
You can add wireless devices in the “Structure” window, “Hardware” tab, after clicking on the
controller name in the list of devices.
1. Click on the “Read” button. The data related to wireless devices will be read from the
controller (these data are not read after clicking on the button in the main menu).
2. Click on the “New device” button. The “New wireless dev.” window will open.

SATEL ACU-120 13
3. Enter the 7-digit serial number of the added device. The serial number can be found on
the electronics board or on the enclosure. Each ARF-100 radio signal level tester has
serial number 0000500.
4. Depending on the device type:
ACX-200 / ACX-201: power-up the expander,
ARF-100: turn on the device,
ASW-100 E / ASW-100 F: insert the controller into 230 V AC socket,
other devices: open the tamper contact.
If an invalid serial number is entered, it will be indicated by a suitable message. In such
a case, enter the correct serial number and repeat the above mentioned step.
5. The message will confirm that a new device has been added. It will be assigned to the
first free zone from the pool reserved for the controller. A suggested name for that zone
will appear (the name is editable). The name will be also assigned to the output, if the
device is to be assigned to the output. For some devices, you can also select whether the
device will take up one or two positions on the list of devices.
6. Click on the “OK” button. You can cancel adding the new device by pressing the “Cancel”
button. You can also press the “Next” button to immediately begin adding another
wireless device.
7. Click on the “Write” button. The data related to the new wireless device will be written to
the controller (these data will not be written after clicking on the or button in
the main menu).
Having added new wireless devices, start the expansion module identification function.
LCD Keypad
You can add wireless devices in service mode, using the N
EW DEVICE
function (S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
[controller name] N
EW DEVICE
).
1. Start the N
EW DEVICE
function.
2. Enter the device 7-digit serial number and press the key. The serial number can be
found on the electronics board or on the enclosure. Each ARF-100 radio signal level
tester has serial number 0000500.
3. When the “Open device tamper” command is displayed, depending on the device type:
ACX-200 / ACX-201: power-up the expander,
ARF-100: turn on the device,
ASW-100 E / ASW-100 F: insert the controller into 230 V AC socket,
other devices: open the tamper contact.
If you have entered a wrong serial number or the device has already been registered,
a suitable message with relevant information will be displayed (press to return to the
submenu).
4. Information about the device to be added will be displayed (type and serial number).
Press the key 1 to confirm your intention to add a device.
5. If there is an option whether the device will occupy one or two positions (channels) on the
device list, a suitable message with relevant information will be displayed. Press the key
1, if the device is to take up 1 position. Press the key 2, if the device is to occupy 2
positions.
6. Using the and keys, select the zone to which you want the device to be assigned,
and then press . If the device occupies more than one position on the list of devices,
additional zones, following the selected one, will be assigned to it automatically.

14 ACU-120 SATEL
7. A message will be displayed to inform you that the expander identification function has
been started.
8. After the devices have been identified, a new name of the zone will be displayed. You can
change it. The same name will also be given to an output, if the device is to be assigned
to the output. Press to save the name. If the device occupies two or more zones, the
procedure of giving them a name will be repeated for each of them.
Removing wireless devices
DLOADX program
You can remove wireless devices in the “Structure” window, “Hardware” tab, after clicking on
the controller name in the list of devices.
1. Click on the “Read” button. The data related to wireless devices will be read from the
controller (these data are not read after clicking on the button in the main menu).
2. Click on the device you want to remove (if the device occupies two or more positions on
the list, you can click on any of them).
3. Click on the “Delete”
button. The “Confirm” window will open.
4. Click on the “Yes” button. The “Confirm” window will close.
5. Click on the “Write” button. The device will be removed from the controller.
Having removed a wireless device, start the expansion module identification function.
LCD keypad
You can remove a wireless device in the service mode, using the R
EMOVE DEVICE
function
(S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
[controller name] R
EMOVE DEVICE
).
1. Start the R
EMOVE DEVICE
function.
2. Using the and keys, select the zone to which the device you want to remove is
assigned, and then press .
3. A prompt will appear on the display asking you whether the device is to be removed (the
device type and serial number will be shown). Press the key 1. The device will be deleted.
4. A message on the display will inform you that the expander identification function has
been started. After identification of the devices, return to the R
EMOVE DEVICE
function will
follow.
7.2.2 Work with the VERSA / VERSA Plus / VERSA IP control panels
The VERSA / VERSA Plus / VERSA IP control panels can support up to 30 wireless devices.
For information about operation of the ABAX system controller with the control panels, as
well as adding and removing wireless devices, please refer to the installer manual of
respective control panels.
7.3 Programming the wireless devices
7.3.1 Parameters and options
Filter – the number of consecutive response periods, during which communication with the
device failed to be established, for the loss of communication with the device to be
reported. Values from the 0 to 50 range can be entered. Entering the digit 0 will disable
control of the device presence in the system.
In the case of the AMD-103 magnetic contact and ASP-100 siren, the presence check
is performed in a different way than for the other ABAX system devices. If the value
programmed for the F
ILTER
parameter differs from 0, the lack of presence will be

SATEL ACU-120 15
reported if no transmission from the AMD-103 magnetic contact / ASP-100 siren is
received within one hour.
ARU – parameter available for a wireless device, if the ARU-100 repeater is registered in the
controller (the controller is connected to the INTEGRA or INTEGRA Plus control panel). It
allows you to define whether the device is to communicate to the controller directly, or via
the selected ARU-100 repeater (several ARU-100 repeaters can be registered in the
controller). The programming procedure is described in section “Programming in the
INTEGRA / INTEGRA Plus system”
(p. 16).
Always active – the option is available for the most of wireless detectors. If enabled, the
detector is permanently switched over to the active mode (see “Wireless detectors”
p. 19).
The AMD-103 detector and the wireless detectors assigned to 24-h zones are always
in the active mode, therefore the A
LWAYS ACTIVE
option does not have to be enabled
for them.
Configuration – some of the wireless devices provide additional parameters and options,
which can be configured by radio (shown in square brackets is information on the zone for
which additional parameters can be programmed, if the device takes up more than 1
zone):
AGD-100 – wireless glass-break detector. Sensitivity is to be programmed.
AMD-100 / AMD-101 – wireless magnetic contact. The active reed switch is to be
selected.
AMD-102 – wireless magnetic contact with input for roller shutter detector. The following is
to be programmed:
active reed switch [first zone];
number of pulses after which alarm will be triggered by the roller shutter input
[second zone];
time during which the specified number of pulses must occur for the roller shutter
input to trigger alarm [second zone].
AOCD-250 – wireless outdoor dual technology curtain detector. The following is to be
programmed:
sensitivity of PIR sensor;
sensitivity of microwave sensor.
AOD-200 – wireless outdoor dual technology motion detector. The following is to be
programmed:
sensitivity of PIR sensor;
sensitivity of microwave sensor;
sensitivity of dusk sensor (detection threshold).
APMD-150 – wireless dual technology detector. The following is to be programmed:
sensitivity of PIR sensor;
sensitivity of microwave sensor;
the way of operation in test mode.
APD-100 – wireless passive infrared detector. The following is to be programmed:
sensitivity,
option of immunity to pets up to 15 kg.
ARD-100 – wireless reorientation detector. Sensitivity is to be programmed.
ASD-150 – wireless smoke detector. The following is to be programmed:
option to signal alarm from other ASD-150 detectors;

16 ACU-120 SATEL
option to send out alarm to other ASD-150 detectors.
ATD-100 – wireless temperature detector. For both positions occupied by detector, the
temperature threshold parameters can be programmed (thus two different temperature
threshold can be programmed):
threshold type: high (when the temperature rises above the defined temperature
value, alarm will be triggered) or low (when the temperature drops below the defined
temperature value, alarm will be triggered);
temperature;
tolerance.
AVD-100 – wireless vibration detector and magnetic contact. The following is to be
programmed:
active reed switch [first zone];
sensitivity of vibration detector (registering a single vibration meeting the sensitivity
criterion will cause alarm) [second zone];
the number of pulses which, if registered by vibration detector will cause alarm (the
pulses need not meet the sensitivity criterion) [second zone].
Working parameters of the vibration detector are independently analyzed. The
detector can trigger alarm after registering a single, strong vibration caused by
a powerful impact, and also on registering several slight vibrations caused by a series
of weak strikes.
ASP-100 – wireless outdoor siren. The following is to be programmed:
type of acoustic signaling;
maximum duration of signaling.
ASP-105 – wirelessly triggered outdoor siren. The following is to be programmed:
type of acoustic signaling;
maximum duration of acoustic signaling.
ASP-205 – wireless indoor siren. Signaling parameters can be programmed for both
positions occupied by the siren (thus allows to program two different signaling types):
maximum duration of signaling;
type of acoustic signaling;
optical signaling option.
ASW-100 E / ASW-100 F – 230 V AC wireless controller. Operating mode can be
programmed.
7.3.2 Programming in the INTEGRA / INTEGRA Plus system
DLOADX program
You can program the wireless devices in the “Structure” window, “Hardware” tab, after
clicking on the controller name in the list of devices (Fig. 3). Before making any changes,
click on the “Read” button, and after making the changes – on the “Write” button (the data
relating to wireless devices are not read and saved after clicking on the button in the
DLOADX program main menu).
ARU
In the “ARU” column:
– leave the field blank, if the device is to communicate directly to the controller;

SATEL ACU-120 17
– enter the ARU-100 repeater number in the list of wireless devices, if the device is to
communicate to the controller via the repeater (the ARU-100 repeater takes up two
positions on the list of devices – enter the number of the first of them).
Configuration
Described below is how the additional parameters and options should be programmed in the
“Configuration” column.
AGD-100 – enter a digit from the 1 to 3 range to set the sensitivity (1 – low , 2 – medium,
3 - high).
AMD-100 / AMD-101 – enter the digit 0 (bottom reed switch) or 1 (side reed switch) to
determine which of the two reed switches is to be active.
AMD-102 – for the magnetic contact, enter the digit 0 (bottom reed switch) or 1 (side reed
switch) to determine which of the two reed switches is to be active. For the roller shutter
input, enter 2 digits:
1
st
digit – number of pulses: from 1 to 8.
2
nd
digit – pulse validity: 0 (30 seconds), 1 (120 seconds), 2 (240 seconds) or 3 (unlimited
duration).
AOCD-250 – enter 2 digits:
1
st
digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2
nd
digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).
AOD-200 – for the first position taken by the detector, enter 3 digits:
1
st
digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2
nd
digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).
3
rd
digit – sensitivity of dusk sensor: from 1 to 4 (1 – minimum; 4 – maximum).
APMD-150 – enter 3 digits:
1
st
digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2
nd
digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).
3
rd
digit – the way of operation in the test mode: 0 (alarm triggered after motion is sensed
by both detectors), 1 (alarm triggered after motion is sensed by infrared detector) or 2
(alarm triggered after motion is sensed by microwave detector).
APD-100 – enter 2 digits:
1
st
digit – sensitivity: 1 (low), 2 (medium) or 3 (high),
2
nd
digit – pet immunity option: 0 (disabled) or 1 (enabled).
ARD-100 – enter a number from the 1 to 16 range to determine sensitivity (1 – minimum;
16 – maximum).
ASD-150 – enter 2 digits:
1
st
digit – option to signal alarm from other ASD-150 detectors: 0 (disabled) or 1 (enabled).
2
nd
digit – option to send out alarm to other ASD-150 detectors: 0 (disabled) or 1
(enabled).
ATD-100 – for each position taken by the detector, enter in turn:
letter H (high temperature threshold) or L (low temperature threshold);
numerical value corresponding to a temperature from the -30°C to +70°C range (with up
to 0.5° accuracy),
numerical value corresponding to a tolerance from the 0.5°C to 10°C range (with up to
0.5° accuracy).

18 ACU-120 SATEL
AVD-100 – for the magnetic contact, enter the digit 0 (bottom reed switch) or 1 (side reed
switch) to determine which of the two reed switches is to be active. For the vibration
detector, enter 2 digits:
1
st
digit – sensitivity: from 1 to 8 (1 – minimum ; 8 – maximum).
2
nd
digit – number of pulses: from 0 to 7. For the value 0, pulses are not counted.
ASP-100 – enter 2 digits:
1
st
digit – type of acoustic signaling: from 1 to 4.
2
nd
digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4 (9
minutes).
ASP-105 – enter 2 digits:
1
st
digit – type of acoustic signaling: from 1 to 4.
2
nd
digit – maximum duration of acoustic signaling: 1 (1 minute), 2 (3 minutes), 3 (6
minutes) or 4 (9 minutes).
ASP-205 – for both positions taken on the list by the siren, enter 3 digits:
1
st
digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4
(9 minutes).
2
nd
digit – type of acoustic signaling: 0 (disabled), 1 (sound type 1), 2 (sound type 2) or 3
(sound type 3).
3
rd
digit – optical signaling: 0 (disabled) or 1 (enabled).
ASW-100 E / ASW-100 F – enter 0 (only remote control of the electric circuit); 1 (remote or
manual control of the electric circuit) or 2 (remote or manual control of the electric circuit,
but with option to manually block the remote control).
LCD keypad
You can configure the wireless devices in service mode, using the following functions: U
SE
ARU-100, A
CTIVE MODE
, C
ONFIGURATION
and F
ILTER
(S
TRUCTURE
H
ARDWARE
E
XPANDERS
S
ETTINGS
[controller name]). Having started the function, use the and keys to select
the zone to which the wireless device is assigned and press the key.
Use ARU-100
Using the and keys select whether the wireless device is to communicate to the
controller directly, or via a selected repeater (the name of the zone to which the repeater is
assigned is displayed on the list).
Configuration
Use the arrow keys for programming additional parameters and options. The values which
can be programmed for individual parameters of wireless devices are presented in the
section describing configuration of the devices by means of the DLOADX
program.
7.3.3 Programming in the VERSA / VERSA Plus / VERSA IP system
DLOADX program
You can configure wireless devices in the “Versa – Structure” window, “Hardware” tab, after
clicking on the controller name in the list of devices. Proceed in the same way as when
programming in the INTEGRA / INTEGRA Plus system. Before making any changes, click on
the “Read” button, and after making the changes – on the “Write” button (the data relating to
the wireless devices are not read after clicking on the button or saved after clicking on
the button in the DLOADX program main menu).
Table of contents
Other Satel Controllers manuals

Satel
Satel ABAX 2 ACU-220 User manual

Satel
Satel MTX-300 User manual

Satel
Satel ACU-280 User manual

Satel
Satel INT-CR User manual

Satel
Satel RX-2K User manual

Satel
Satel ABAX 2 ACU-280 User manual

Satel
Satel KNX-BSA12L User manual

Satel
Satel KNX-DIM21 User manual

Satel
Satel Abax ACU-100 User manual

Satel
Satel VERSA-MCU User manual

Satel
Satel RXH-1K User manual

Satel
Satel ACU-280 User manual

Satel
Satel ACU-270 User manual

Satel
Satel ASW-100 E User manual

Satel
Satel KNX-BSA12H User manual

Satel
Satel KNX-SA41 User manual

Satel
Satel KNX-SA41 User manual

Satel
Satel MICRA VERSA-MCU User manual

Satel
Satel KNX-DIM21 User manual

Satel
Satel ACU-250 User guide