6 INSTALLATION PLACE
1) Recommended installation height is 2.3-2.5
mand at a distance not more than 6m from the
most distant spot of protected glass.
2) The detector cannot be used in premises
with high level of acoustic interference.
3) Alarm loop and power supply wires should
be located far from power cables.
To eliminate false alarm hazards
1) It is recommended to close all doors, air-
vents, switch off possible sourses of intense air
flows (fans, air-conditioners) and acoustic inter-
ferences (loudspeakers, etc.) in the room during
protection period.
2) The detector's location should provide di-
rect visibility of all secured glass parts; masking
the detector with decorative curtains is not al-
lowed, as sensitivity may be lost.
Not recommended installation places
7 INSTALLATION PROCEDURE
3b) Mounting in the
corner
Detector base should be positioned strictly
as per figure!
There is a possibility to install detector using a
bracket (delivered separately).
4) Install PCB and perform wiring (see sec.8)
5) Perform GB- / PIR-channel tests (see sec.9)
8 WIRING
Perform wiring to detector`s terminals in
accordance with control panel operating manual.
TMP –detector tampering control terminals;
RELAY-PIR, RELAY-GB –terminals for detector
connection to alarm loop;
+12V, GND –power supply terminals.
9 TEST
GB-channel test:
1) Remove jumpers from Mem and GB plugs,
install jumper on Ind plug.
2) Power detector ON. LED starts flash during
60 sec.
3) During this time close shortly Тst plug using
screwdriver. AC-channel TEST mode switches
for 8 min.
4) Assemble the detector.
5) Apply non-
destructive strike to the
most distant part of the
protected glass.
6) At the detection
moment LED should
light up for 4s and relay
shouldopen (check with
control panel) or LED
should double-flash one
time.
PIR-channel test:
Perform TEST-pass.
To detect sensitive zones
pass through detection
zone with the speed of
0.3-3 m/s. Make sure the
"Alarm - IR" notification is
issued with each pass.