Activate referencing with end position determination StartRef
Factory setting: left reference end position "Ref"
–HMI: activate "Reference" menu, parameterise reference end position "Ref" and initiate refer-
encing movement è 9.4 Display and operating components (HMI)
–IO-Link, process data: parameterise reference end position "Ref" 0x0103.0, false (factory set-
ting) or true and initiate referencing movement 0x0104.0 = true
–IO-Link, system parameters: 0x0002, value = 0xCE (Execute "Reference" Movement (False),
factory setting) or value = 0xCF (Execute "Reference" Movement (True))
Sequence
The diagram shows the referencing movements with end position determination
–MovRef: force-controlled movement against mechanical stop "MechIn"
–MovOut: position-controlled movement to the reference end position "Ref"
–MovRef: force-controlled movement against the mechanical stop "MechOut"
–MovOut: position-controlled movement to the end position LimOut
Tab. 10: Initialise referencing sequence with reference end position "Ref" and
end position determination
9.6 Point-to-point operating modes
Automatic saving of device data
If automatic storage is activated (0x0109.0 = true, default), parameter changes
in the device data (= data storage parameters è "Integrated drive EMCS"
instruction manual è www.festo.com/sp) are made automatically and perma-
nently saved in the flash memory. Exceeding the maximum permissible 100,000
write cycles results in irreparable damage to the flash memory and the device,
e.g. when using the device for positioning tasks via IO-Link.
If automatic saving is deactivated (0x0109.0 = false), parameter changes are
only temporarily stored in the RAM. The RAM permits an unlimited number of
parameter changes, e.g. for positioning tasks via IO-Link.
For single point-to-point operation the drive can be traversed to the target posi-
tions "end positions "LimIn/LimOut and intermediate positions PosImp" (IO-Link
only).
Point-to-point operation
Parameterise point-to-point operation
HMI:
–Speed Out, Speed In, Force and Start Press è 9.4 Display and operating components (HMI)
IO-Link (acyclic device data):
–Velocity Speed Out: 0x0101.0, Speed Out1)
–Velocity Speed In: 0x0100.0, Speed In1)
–Force/Torque: 0x0102.0, Force1)2)
–Start Press Position PosStart Press: 0x0105.0, Position Start Press [mm]2)3)4)
–End position LimOut: 0x0106.0, end position Out [mm]4)
–Intermediate position PosImp: 0x0108.0, Intermediate Position [mm]3)4)
Control point-to-point operation via digital inputs
Positioning task Control signals
MovIn
DI1 [Logic, Pin 5]
MovOut
DI2 [Logic, Pin 6]
StartIn/MovIn 1 0
StartOut/MovOut 0 1
Stop5) 0 0
Switch off power
stage6)
1 1
Control point-to-point operation via IO-Link
Positioning task Process parameters System parameters
Move "In" Move
"Out"
Move
"Inter-
mediate"
System commands
0x0029.1 0x0029.2 0x0029.5 0x0002
StartIn/MovIn true false false = 0xC8, Execute "MoveIn"
StartOut/MovOut false true false = = 0xC9, Execute "MoveOut"
StartImp/MovImp false false true = 0xD0, Execute "MoveIntermediate"
Stop5) false false false = 0xCA, stop motion
Switch off power
stage6)
³ 2 x true = 0xCB, disable power stage
Point-to-point operation
Sequence
The diagrams show the movements in point-to-point operation
–MovOut: position-controlled movement to the end position "LimOut"
–MovIn: position-controlled movement to the end position "LimIn"
–MovImp: position-controlled movement to the intermediate position "PosImp"
–Point-to-point operation with press function, from Start Press Position "PosStart Press"
–MovOut: force-controlled movement until the parameterised force or torque setpoint
value "Force" is reached or to the end position "LimOut"
–MovImp: force-controlled movement to the intermediate position "PosImp" (IO-Link only)
Simple point-to-point operation
Simple point-to-point operation with intermediate position (IO-Link only)
Point-to-point operation with press function
Point-to-point operation with press function and intermediate position (IO-Link only)
1) 10, 20, ..., 100% of maximum value
2) Only required for point-to-point operation with press function
3) Reset at every referencing
4) Reference point: reference end position "Ref"
5) The output stage remains active, the drive decelerates to standstill and remains stationary position-con-
trolled.
6) In error-free status the power stage is switched off after 3 s, the drive coasts to a standstill and remains
stationary unregulated.
Tab. 11: Parameterise and control point-to-point operation