MSA fieldserver ProtoNode FPC-N54 User guide

Mestek ProtoNodeStart-up Guide 0
Start-up Guide
ProtoNode FPC-N54
For InterfacingMestekProducts
MSAsafety.com
Document Revision: 1.A
Auto-Discovery

Mestek ProtoNodeStart-up Guide 2
Technical Support
Thank you forpurchasing the ProtoNode for Mestek.
Please call Mestekfor technical support of the ProtoNode product.
MSA Safety does notprovide direct support. If Mestekneeds to escalate the concern,they willcontact
MSA Safety forassistance.
Support ContactInformation:
Mestek, Inc.
260 North Elm Street
Westfield, MA01085
CustomerService:
(413) 564-5572
Email: lhmorse@mestek.com
Website: mestek.com

Mestek ProtoNodeStart-up Guide 3
Quick Start Guide
1. Record the informationabout the unit. (Section 2.1)
2. Check that the ProtoNode and customer device COMsettingsmatch. (Section 2.3)
3. If connecting to a serial device:
Connect the ProtoNode 3 pin RS-485 R1 port to the RS-485 network connected to each of the
devices. (Section 3.1)
4. If using a serial field protocol:
Connect the ProtoNode 3 pin RS-485 R2 port to the field protocol cabling. (Section 3.2)
5. Connect power to ProtoNode 3 pin power port. (Section 3.5)
6. Connect a PCto the ProtoNode via Ethernet cable. (Section 4)
7. Setup Web Server Security and login via web browser. (Section 5)
8. Use a web browser to access the ProtoNode Web Configurator page to select the protocol of the
device attached to the ProtoNode and enter any necessary device information. Click the Discovery
Mode buttonat the bottomof the screen.It may take about3 minutesforall the devices to be
discovered and the configuration file to be built. (Section 6)
9. Ethernet Network: If using an Ethernet field protocol,use a web browser to access the ProtoNode Web
Configurator page to change the IP Address. (Section6.4)

Mestek ProtoNodeStart-up Guide 4
Table of Contents
1Introduction................................................................................................................... 7
1.1 ProtoNode Gateway................................................................................................. 7
2Setup for ProtoNode....................................................................................................... 8
2.1 Record IdentificationData......................................................................................... 8
2.2 Point Count Capacity................................................................................................ 8
2.3 Configuring Device Communications........................................................................... 9
2.3.1 Confirm theDevice and ProtoNode COM Settings Match............................................... 9
2.3.2 Set Node-IDfor AnyDeviceAttached to theProtoNode................................................. 9
3Interfacing ProtoNode to Devices...................................................................................10
3.1 Device Connections to ProtoNode.............................................................................10
3.2 Wiring Field Port to RS-485 Serial Network.................................................................10
3.3 Bias Resistors........................................................................................................11
3.4 Termination Resistor...............................................................................................12
3.5 Power-Up ProtoNode..............................................................................................13
4Connect the PC to theProtoNode...................................................................................14
4.1 Connecting to the Gateway via Ethernet.....................................................................14
4.1.1 Changing the Subnet of the Connected PC.................................................................14
5Setup WebServer Security.............................................................................................15
5.1 Login to the FieldServer...........................................................................................15
5.2 Select theSecurity Mode.........................................................................................17
5.2.1 HTTPS with Own Trusted TLS Certificate...................................................................18
5.2.2 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in Payload
Encryption.............................................................................................................18
6Configure the ProtoNode...............................................................................................19
6.1 Select Field Protocol and Set Configuration Parameters ...............................................19
6.2 Use Discovery Mode...............................................................................................20
6.3 Verify Device Communications..................................................................................20
6.4 Ethernet Network: Setting IP Address for the Field Network...........................................21
6.5 BACnet: Setting Node_Offset to Assign Specific Device Instances ................................23
6.6 How to Start the Installation Over: Clearing Profiles......................................................24
7Troubleshooting............................................................................................................25
7.1 Lostor Incorrect IPAddress.....................................................................................25
7.2 Viewing Diagnostic Information.................................................................................26
7.3 Checking Wiring and Settings...................................................................................27
7.4 LED Diagnostics for Communications Between ProtoNode and Devices .........................28
7.5 Taking a FieldServerDiagnostic Capture....................................................................29
7.6 Factory Reset Instructions........................................................................................30
7.7 Internet Browsers Not Supported...............................................................................30
8Additional Information...................................................................................................31
8.1 Update Firmware....................................................................................................31
8.2 BACnet: Setting Network_Numberfor More Than One ProtoNodeon the Subnet .............31
8.3 Mounting ...............................................................................................................32
8.4 Certification............................................................................................................32
8.4.1 BTL Mark –BACnet®Testing Laboratory....................................................................32
8.5 PhysicalDimension Drawing.....................................................................................33
8.6 Change Web ServerSecurity SettingsAfter Initial Setup...............................................34
8.6.1 Change Security Mode............................................................................................35
8.6.2 Editthe Certificate Loaded onto the FieldServer..........................................................36
8.7 Change User Management Settings ..........................................................................37

Mestek ProtoNodeStart-up Guide 5
8.7.1 Create Users .........................................................................................................38
8.7.2 Edit Users .............................................................................................................39
8.7.3 Delete Users..........................................................................................................40
8.7.4 Change FieldServer Password .................................................................................41
8.8 Routing Settings.....................................................................................................42
9Vendor Information –Mestek..........................................................................................43
9.1 Mngr Modbus RTU Mappings to BACnet &Metasys N2................................................43
9.2 Dep Modbus RTU Mappings to BACnet & Metasys N2.................................................43
10 Specifications...............................................................................................................45
10.1.1 Compliance with UL Regulations...............................................................................45
11 Limited 2 Year Warranty.................................................................................................46

Mestek ProtoNodeStart-up Guide 6
List of Figures
Figure 1: ProtoNode Part Numbers...................................................................................................................................8
Figure 2: Supported Point Count Capacity......................................................................................................................8
Figure 3: Points per Device................................................................................................................................................8
Figure 4: COM Settings......................................................................................................................................................9
Figure 5: RS-485 Connectionsfrom Devices to the ProtoNode.................................................................................10
Figure 6: Connection from ProtoNode to RS-485 Field Network................................................................................10
Figure 7: Bias Resistor DIP Switches.............................................................................................................................11
Figure 8: Termination Resistor DIP Switch....................................................................................................................12
Figure 9: Required Current Draw for the ProtoNode....................................................................................................13
Figure 10: Power Connections........................................................................................................................................13
Figure 11: Ethernet Port Location...................................................................................................................................14
Figure 12: Web Server Security Window.......................................................................................................................15
Figure 13: Connection Not Private Warning..................................................................................................................15
Figure 14: Warning Expanded Text................................................................................................................................16
Figure 15: FieldServer Login............................................................................................................................................16
Figure 16: Security Mode Selection Screen..................................................................................................................17
Figure 17: Security Mode Selection Screen –Certificate & Private Key...................................................................18
Figure 18: Web Configurator Showing Protocol Selector Parameter.........................................................................19
Figure 19: Web Configurator Showing Discovery Mode Button.................................................................................20
Figure 20: Web Configurator Showing Discovered Profiles........................................................................................20
Figure 21: Web Configurator Screen..............................................................................................................................21
Figure 22: Changing IP Address via FS-GUI.................................................................................................................22
Figure 23: Web Configurator Node Offset Field............................................................................................................23
Figure 24: Active Profiles..................................................................................................................................................23
Figure 25: Ethernet Port Location...................................................................................................................................25
Figure 26: Error Messages Screen.................................................................................................................................26
Figure 27: Diagnostic LEDs.............................................................................................................................................28
Figure 29: Web Configurator –NetworkNumber Field................................................................................................31
Figure 30: DIN Rail............................................................................................................................................................32
Figure 31: ProtoNode FPC-N54 Dimensions................................................................................................................33
Figure 32: FS-GUI Page...................................................................................................................................................34
Figure 33: FS-GUI Security Setup..................................................................................................................................35
Figure 34: FS-GUI Security Setup –Certificate Loaded..............................................................................................36
Figure 35: FS-GUI User Management............................................................................................................................37
Figure 36: Create User Window......................................................................................................................................38
Figure 37: Setup Users.....................................................................................................................................................39
Figure 38: Edit User Window...........................................................................................................................................39
Figure 39: Setup Users.....................................................................................................................................................40
Figure 40: User Delete Warning......................................................................................................................................40
Figure 41: FieldServer Password Update via FS-GUI.................................................................................................41
Figure 42: Routing Settings..............................................................................................................................................42
Figure 43: Specifications..................................................................................................................................................45

Description
Mestek ProtoNodeStart-up Guide 7
1 Introduction
1.1 ProtoNode Gateway
The ProtoNode is an external, high performance building automation multi-protocol gateway that is
preconfigured to automatically communicate between Mestek’sdevices (hereafter simply called “device”)
connectedto the ProtoNode and automaticallyconfiguresthem for BACnet/IP, BACnet MS/TP, Modbus
TCP/IP and Metasys®
1
N2 by JCI.
It is not necessary to download any configuration files to support the required applications. The ProtoNode
is pre-loaded with tested profiles/configurations for the supported devices.
FPC-N54 Connectivity Diagram:
The ProtoNode can connect with the MSA Grid –FieldServer Manager.The FieldServerManager allows
technicians,theOEM'ssupportteamandMSASafety'ssupportteamtoremotelyconnecttotheProtoNode.
The FieldServer Manager providesthe following capabilities for any registered devices in the field:
•Remotely monitor and control devices.
•Collect device data and view it on the Dashboard and the MSA Smart Phone App.
•Create user defined device notifications(alarm, trouble and warning) via SMS and/or Email.
•Generate diagnostic captures(as needed fortroubleshooting) without going to the site.
FormoreinformationontheFieldServerManager,seetheMSAGrid -FieldServerManagerStart-upGuide.
1
Metasys is a registered trademarkof Johnson ControlsInc.

Setupthe Gateway
Mestek ProtoNodeStart-up Guide 8
2 Setup for ProtoNode
2.1 Record Identificati on Data
Each ProtoNode has a uniquepartnumberlocated on the side or the back of the unit. This number should
be recorded,as it may be required for technical support. The numbersare as follows:
Model
Part Number
ProtoNode
FPC-N54-1778
Figure 1: ProtoNode Part Numbers
•FPC-N54 units have the following 3 ports: RS-485 +Ethernet + RS-485/RS-232
2.2 Poi nt Count Capacity
The total number of registers presented the device(s) attached to the ProtoNode cannotexceed:
Part number
Total Registers
FPC-N54-1778
1,500
Figure 2: Supported Point Count Capacity
Devices
Point Count Per Device
Mngr
41
Dep
25
Figure 3: Points per Device

Setupthe Gateway
Mestek ProtoNodeStart-up Guide 9
2.3 Configuring Device Communications
2.3.1 Confirm the Device and ProtoNode COM Settings Match
•Any connected serial device MUST have the same baud rate, data bits,stop bits, and
parity settings as the ProtoNode.
•Figure 4 specifies the device serial port settings required to communicate with the ProtoNode.
Port Setting
Device
Protocol
ModbusRTU
Baud Rate
9600
Parity
None
Data Bits
8
Stop Bits
2
Figure 4: COM Settings
2.3.2 Set Node-ID for Any Device Attached to the ProtoNode
•Set Node-ID for any device attached to ProtoNode.The Node-ID needs to be uniquely assigned
between 1 and 255.
•Document the Node-ID thatis assigned. The Node-ID assigned is used for deriving the Device
Instance for BACnet/IP and BACnetMS/TP.(Section 6.5)
NOTE: The Metasys N2 and Modbus TCP/IPfieldprotocol Node-ID is automatically setto be the
same value as the Node-ID of the device.

Installingthe Gateway
Mestek ProtoNodeStart-up Guide 10
3 Interfacing Pro toNode to Devices
3.1 Device Connections to ProtoNode
The ProtoNode has a 3-pin Phoenix connector for connecting RS-485 devices on the R1 port.
NOTE: Use standard groundingprinciples for RS-485 GND.
Device Pins
ProtoNode
Pin Label
Pin
Assignment
RS-485 +
TX +
RS-485 +
RS-485 -
RX -
RS-485 -
RS-485 GND
GND
RS-485 GND
3.2 Wiring Fi eld Port to RS -485 Seri al Network
•Connect the RS-485 network wires to the 3-pin RS-485 connector on the R2 port. (Figure 6)
oUse standard grounding principles for RS-485 GND
•See Section 4for information on connecting to an Ethernet network.
BMS
Wiring
ProtoNode
Pin Label
Pin
Assignment
RS-485 +
+
RS-485 +
RS-485 -
-
RS-485 -
-
GND
RS-485 GND
Figure 6: Connection from ProtoNode to RS-485 Field Network
G
-
+
Figure 5: RS-485 Connections from Devices to the ProtoNode
G
-
+

Installingthe Gateway
Mestek ProtoNodeStart-up Guide 11
3.3 Bias Resistors
To enable Bias Resistors, move both the BIAS- and BIAS+ dip switches to the right as shown in
Figure 7.
The ProtoNode biasresistors are used to keep the RS-485 bus to a known state, when there is no
transmission on the line (busis idling), to help preventfalse bits of data frombeing detected. The bias
resistors typically pull one line highand the other low - faraway from thedecision pointof the logic.
The bias resistor is 510 ohms which is in line with the BACnetspec. It should onlybe enabled at one
point onthe bus(forexample, on the field port were there are very weak biasresistors of 100k). Since
there are no jumpers, many gateways can be puton the networkwithout running into the bias resistor
limit which is < 500 ohms.
NOTE: See www.ni.com/support/serial/resinfo.htm for additional pictures and notes.
NOTE: The R1 and R2 DIP Switches apply settings to the respective serialport.
NOTE: If the gateway is already powered on, DIPswitch settings will not take effect unless the
unit is power cycled.
R1 Bias Resistor DIP
Switches (2 and 3)
Figure 7: Bias Resistor DIP Switches
R2 Bias Resistor DIP
Switches (2and 3)

Installingthe Gateway
Mestek ProtoNodeStart-up Guide 12
3.4 Term i nati on Resistor
If the ProtoNode is the last device on the serial trunk, then the End-Of-Line Termination Switch needsto
be enabled. To enable the Termination Resistor, move the TERM dip switch to the right as shown in
Figure 8.
Termination resistor is also used to reduce noise.It pulls the two lines of an idle bus together. However,
the resistor would override the effect of any bias resistors if connected.
NOTE: The R1 and R2 DIP Switches apply settings to the respective serialport.
NOTE: If the gateway is already powered on, DIPswitch settings will not take effect unless the
unit is power cycled.
R1 Termination
Resistor DIP Switch (1)
Figure 8: Termination Resistor DIP Switch
R2 Termination
Resistor DIP Switch (1)

Installingthe Gateway
Mestek ProtoNodeStart-up Guide 13
3.5 Power-Up ProtoNode
Check power requirements in the table below:
Power Requirement for ProtoNode External Gateway
Current Draw Type
ProtoNode Family
12VDC
24VDC/AC
FPC–N54 (Typical)
250mA
125mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of
the hostsystem. A safety margin of 25%is recommended.
Figure 9: Required Current Draw for the ProtoNode
Apply power to the ProtoNode as shown below in Figure 10. Ensure thatthe power supply used complies
with the specifications provided in Section 10.
•The ProtoNode accepts 9-30VDC or 24VAC on pins L+and N-.
•Frame GND should be connected.
Power to
ProtoNode
ProtoNode
Pin Label
Pin
Assignment
Power In (+)
L +
V +
Power In (-)
N -
V -
Frame Ground
FG
FRAME GND
Figure 10: Power Connections

SetupWeb Server Security
Mestek ProtoNodeStart-up Guide 14
4 Connect the PC to the Pro toNode
4.1 Connecting to the Gateway via Ethernet
Connect a Cat-5 Ethernet cable (straight through or cross-over) between the local PC and ProtoNode.
4.1.1 Changing the Subnet of the Connected PC
The defaultIP Addressforthe ProtoNode is 192.168.1.24,SubnetMaskis 255.255.255.0. If the PC and
ProtoNode are on different IP networks, assigna static IPAddress to the PC onthe 192.168.1.xxx network.
ForWindows10:
•Find the search field in the local computer’s taskbar (usually to the right of the windows icon )
and type in “Control Panel”.
•Click “Control Panel”, click “Network and Internet” and then click “Network and Sharing Center”.
•Click “Change adapter settings” on the left side of the window.
•Right-click on “Local Area Connection” and select “Properties” from the dropdown menu.
•Highlight and then click the Properties button.
•Select and enter a static IP Address on the same subnet. For example:
•Click the Okay button to close the Internet Protocol window and the Close button to close the
Ethernet Properties window.
Ethernet Port
Figure 11: Ethernet Port Location

SetupWeb Server Security
Mestek ProtoNodeStart-up Guide 15
5 Setup Web Server Security
Navigate to the IP Address of the ProtoNode on the local PC by opening a web browser and entering the
IP Addressof the ProtoNode; the defaultEthernetaddressis 192.168.1.24.
NOTE: If the IP Address ofthe ProtoNode has been changed,the assignedIP Address can be
discovered using the FSToolbox utility. See Section7.1 for instructions.
5.1 Logi n to the Fi eldServer
The first timethe FieldServer GUI is opened in a browser, the IP Address for the gatewaywill appear as
untrusted. This will cause the following pop-up windows to appear.
•When the Web Server Security Unconfigured windowappears,read the text and choose whether
to moveforward with HTTPS or HTTP.
•When the warning that “Your connection is not private” appears, click the advanced button on the
bottomleft corner of the screen.
Figure 13: Connection Not Private Warning
Figure 12: Web Server Security Window

SetupWeb Server Security
Mestek ProtoNodeStart-up Guide 16
•Additional text will expand belowthe warning, click the underlined text to go to the IP Address. In
the Figure 14 example this text is “Proceed to 10.40.50.94 (unsafe)”.
•When the login screen appears, put in the Username (default is “admin”) and the Password (found
on the label of the FieldServer).
NOTE: There is also a QR code in the top right corner of the FieldServer label that shows the
default unique passwordwhen scanned.
NOTE: A user has 5 attempts to login then there willbe a 10-minute lockout.There is no timeout
on the FieldServer to enter a password.
NOTE: To createindividualuser logins,go to Section 8.7.
Figure 15: FieldServer Login
Figure 14: Warning Expanded Text

SetupWeb Server Security
Mestek ProtoNodeStart-up Guide 17
5.2 Select the Security Mode
On the first login to the FieldServer,the following screen will appear that allows the user to select which
mode the FieldServer should use.
NOTE: Cookies are used for authentication.
NOTE: To change the web server security mode after initialsetup, goto Section 8.1.
The sections that follow include instructions forassigning the differentsecurity modes.
Figure 16: Security Mode Selection Screen

SetupWeb Server Security
Mestek ProtoNodeStart-up Guide 18
5.2.1 HTTPS with Own Trusted TLS Certificate
This is the recommended selection and the most secure. Please contact your IT department to find out
if you can obtain a TLScertificatefrom your company before proceeding with the OwnTrusted TLS
Certificate option.
•Once this option is selected,the Certificate, Private Key and Private Key Passphrase fieldswill
appear under the mode selection.
•Copy and paste the Certificate and Private Keytext into their respective fields. If the Private Key is
encrypted type in the associated Passphrase.
•Click Save.
•A “Redirecting” message will appear. After a short time, the FieldServerGUIwill open.
5.2.2 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in
Payload Encryption
•Select one of these optionsand click the Save button.
•A “Redirecting” message will appear. After a short time, the FieldServer GUI will open.
Figure 17: Security Mode Selection Screen –Certificate & Private Key

ConfiguringtheGateway
Mestek ProtoNodeStart-up Guide 19
6 Configure the ProtoNo de
6.1 Select Field Protocol and Set Configuration Parameters
•On the Web Configurator page, the firstconfiguration parameter is the ProtocolSelector.
•Select the field protocol by entering the appropriate number into the ProtocolSelectorValue. Click
the Submit button. Click the SystemRestart button to save the updated configuration.
NOTE: Protocol specific parameters are only visible when the associated protocol isselected.
•Ensurethat allparametersareentered forsuccessfuloperationof thegateway. Findthelegalvalue
options for each parameter underthe Parameter Description in parentheses.
NOTE: If multiple devices are connected to the ProtoNode, setthe BACnet VirtualServer Nodes
field to “Yes”; otherwise leave the field on the default “No” setting.
Figure 18: Web Configurator Showing Protocol Selector Parameter

ConfiguringtheGateway
Mestek ProtoNodeStart-up Guide 20
6.2 Use Discovery Mode
•Click the Discovery Mode button at the bottom of the screen.
•Click the OK button in the window that appears to discover devices and restart the device.
•Wait for the ProtoNode to restart and the Discovery in Progress window to disappear.
NOTE: It may take about 3 minutes for all the devices to be discovered and the configuration file
to be built.
•If the discovery is successful, the device profile should appear under the Active profilestitle.
NOTE: Scroll down the page if the Active profiles header is not visible.
6.3 Verify Devi ce Com m unicati ons
•If using a serial connection, check that the port R1 TX1 and RX1 LEDs are rapidly flashing.
See Section 7.4 for additional LED information and images.
•Confirm the software shows good communicationswithouterrors (Section7.2).
Figure 20: Web Configurator Showing Discovered Profiles
Figure 19: Web Configurator Showing Discovery Mode Button
Other manuals for fieldserver ProtoNode FPC-N54
2
Table of contents
Other MSA Safety Equipment manuals

MSA
MSA M1 User manual

MSA
MSA V-GARD 900 Series User manual

MSA
MSA Gallet F2XR User manual

MSA
MSA Gravity Sure-Line Operation instructions

MSA
MSA 415865 User manual

MSA
MSA SavOx TR User manual

MSA
MSA Rail Slider User manual

MSA
MSA Workman SRL-R User manual

MSA
MSA FieldServer FS-8700-153 User manual

MSA
MSA V-EDGE PFL User manual

MSA
MSA AUER 3S-Basis Plus User manual

MSA
MSA SavOx User manual

MSA
MSA 10016511 User manual

MSA
MSA PrimaX IR User manual

MSA
MSA Latchways PushLock Eyebolt User manual

MSA
MSA V-TEC PFL User manual

MSA
MSA SingleLine SCOUT User manual

MSA
MSA BD mini User manual

MSA
MSA V-FLEX Operation instructions

MSA
MSA OptimAir 3000 User manual