Nibe S Series User manual

IHB 2109-1
631179
Extra climate system
ECS 40/ECS 41
LEK
LEK
LEK

Important information
SAFETY INFORMATION
This manual describes installation and service proced-
ures for implementation by specialists.
The manual must be left with the customer.
This appliance can be used by children
aged from 8 years and above and persons
with reduced physical, sensory or mental
capabilities or lack of experience and
knowledge if they have been given super-
vision or instruction concerning use of the
appliance in a safe way and understand
the hazards involved. Children shall not
play with the appliance. Cleaning and user
maintenance shall not be made by children
without supervision.
This is an original manual. It may not be
translated without the approval of NIBE.
Rights to make any design or technical
modifications are reserved.
©NIBE 2021.
System pres-
sure
Defined by
main
product
MPaMax. system
pressure, heat-
ing medium
Defined by
main
product
l/sMax flow
35°CMax. permitted
ambient temper-
ature
ECS 40/ECS 41 must be installed via an isol-
ator switch. The cable area has to be dimen-
sioned based on the fuse rating used.
If the supply cable is damaged, only NIBE,
its service representative or similar author-
ised person may replace it to prevent any
danger and damage.
SYMBOLS
NOTE
This symbol indicates danger to person or ma-
chine .
Caution
This symbol indicates important information
about what you should consider when installing
or servicing the installation.
TIP
This symbol indicates tips on how to facilitate
using the product.
MARKING
The CE mark is obligatory for most products
sold in the EU, regardless of where they are
made.
CE
Classification of enclosure of electro-technical
equipment.
IP 21
Danger to person or machine.
!
Read the Installer Manual.
ECS 40/ECS 41 S-series | GB4
S
S-series

General
This accessory is used when your climate unit is installed
in buildings with several climate systems1that require
different supply temperatures, for example in cases
where the building has both a radiator system and an
underfloor heating system. See “Compatible products”
below to see which climate units ECS 40/ECS 41 can
be connected to.
The total water flow in the climate systems should not
exceed 1,700 l/h.
Caution
With underfloor heating systems, maximum
supply temperature for heating is normally be
set between 35 and 45°C.
Check the max temperature for your floor with
your floor supplier.
Caution
If the room sensor is used in a room with un-
derfloor heating, it should only have an indicat-
ory function, not control of the room temperat-
ure.
COMPATIBLE PRODUCTS
• S1155
• S1255
• VVM S320
• VVM S325
• SMO S40
CONTENTS
AXC module1 x
Cable ties4 x
Circulation pump1 x
Contact1 x
Shunt motor1 x
Shunt valve1 x
Heating pipe paste2 x
Aluminium tape2 x
Insulation tape1 x
Replacement gasket2 x
Temperature sensor2 x
Room sensor1 x
Pipe with straight coupling2
1 x
COMPONENT LOCATION, AXC MODULE
(AA25)
AA5-X4 AA5-S2
AA5-X2
AA5
AA25-X1
AA5-X9
AA25-FC1
ELECTRICAL COMPONENTS
Accessory cardAA5
DIP switchAA5-S2
Terminal block, inputsAA5-X2
Terminal block, communicationAA5-X4
Terminal block, outputsAA5-X9
AXC moduleAA25
Miniature circuit-breakerAA25-FC1
Terminal block, power supplyAA25-X1
Designations according to standard EN 81346-2.
1. The number of climate systems that can be installed varies depending on the product and software version. To check which software version is
available for your product, visit nibeuplink.com.
2. This is only used when connecting to NIBE F370 or F470.
5ECS 40/ECS 41 S-series | GB
S

Pipe connections
INSTALLATION PRINCIPLE
CIRCULATION PUMP
The circulation pump’s permitted positions.
SHUNT
The shunt’s permitted positions.
GENERAL
When connecting extra climate systems, they must be
connected so that they have a lower working temperat-
ure than the climate system 1.
CIRCULATION PUMP
The extra circulation pump (EP21-GP10) is positioned in
the extra climate system according to the outline dia-
gram.
SHUNT VALVE
The shunt valve (EP21-QN25) is located on the supply
line after the heat pump/indoor module, before the first
radiator in the climate system 1. The return line from
the extra climate system is connected to the shunt valve
and to the return line from the climate system 1, see
image and outline diagram.
B
A
AB
• Connect the supply line to the climate
system from the heat pump to port A on
the shunt valve (opens on increase signal)
• Connect the return line from the climate
system to port B on the shunt valve via
the T-pipe (closes on reduce signal).
• Connect the supply line to the climate system to the
common port AB on the shunt valve (always open).
ECS 40/ECS 41 S-series | GB6
S

INSTALLING THE SHUNT
When installing the shunt, the flat side of the shaft must
be in the southwest position, see image. Then, install
the shunt motor with the knob in the middle position.
Shunt valve, (QN25)
Connection DN20 1 1/4" (22 mm)
LEK
LEK
LEK
LEK
Return
Heat
pump/indoor
module
Flow pipe
TEMPERATURE SENSOR
• The supply line sensor (EP21-BT2) is installed on the
pipe between the circulation pump (EP21-GP10) and
shunt valve (EP21-QN25).
• The return line sensor (EP21-BT3) is installed on the
pipe from the extra climate system.
LEK
LEK
E
Install the temperature sensors using cable ties, together
with the heat conducting paste and aluminium tape.
Then insulate with the enclosed insulation tape.
NOTE
To prevent interference, sensor cables to ex-
ternal connections must not be laid close to
high voltage cables.
7ECS 40/ECS 41 S-series | GB
S

SETTING THE CIRCULATION PUMP
LEK
GP10-SF4
LEDs
I II III
The circulation pump (GP10) is equipped
with five LEDs. In normal mode, the
LEDs show the pump’s setting by light-
ing up in green and/or yellow. The LEDs can also indicate
an alarm, in which case they light up in red and yellow.
The circulation pump’s (GP10) various settings are se-
lected by pressing the switch (GP10-SF4).
Choose between 5 different settings on the circulation
pump.
• proportional pressure auto adapt (PPAA)
• constant pressure auto adapt (CPAA)
• proportional pressure (PP)
• constant pressure (CP)
• constant curve (CC).
The circulation pump’s factory setting is PP, speed 2.
PROPORTIONAL PRESSURE AUTO ADAPT
(PPAA)
The circulation pump continually regulates the flow
through the system with a great deal of freedom, to
ensure minimum pump power consumption.
The setting is intended for radiator systems. Due to
optimisation to low pumping capacity, the flow may be
insufficient in certain systems.
Capacity, circulation pump (PPAA)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
80
50
40
70
60
30
Tryck
(kPa)
Fl de
(l/s)
Pressure
Flow
Power, circulation pump (PPAA)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
60
50
40
30
Effekt
(W)
Fl de
(l/s)
Output
Flow
LED indicationSetting
PPAA
ECS 40/ECS 41 S-series | GB8
S

CONSTANT PRESSURE AUTO ADAPT (CPAA)
The circulation pump continually regulates the flow
through the system with a great deal of freedom, to
ensure minimum pump power consumption.
The setting is intended for underfloor heating systems.
Due to optimisation to low pumping capacity, the flow
may be insufficient in certain systems.
Capacity, circulation pump (CPAA)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
80
50
40
70
60
30
Tryck
(kPa)
Fl de
(l/s)
Pressure
Flow
Power, circulation pump (CPAA)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
60
50
40
30
Effekt
(W)
Fl de
(l/s)
Output
Flow
LED indicationSetting
CPAA
PROPORTIONAL PRESSURE (PP)
Within a limited range, the circulation pump is permitted
to regulate its speed to an optimum system pressure.
Speed 1, 2 or 3 is selected based on maximum flow
requirement.
The setting is intended for radiator systems.
Capacity, circulation pump (PP)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
80
50
40
70
60
30
Tryck
(kPa)
Flöde
(l/s)
3
2
1
Pressure
Flow
Output, circulation pump (PP)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
60
50
40
30
Effekt
(W)
Flöde
(l/s)
3 2 1
Output
Flow
LED indicationPump speed
PP
1
2
3
9ECS 40/ECS 41 S-series | GB
S

CONSTANT PRESSURE (CP)
Within a limited range, the circulation pump is permitted
to regulate its speed to a constant system pressure.
Speed 1, 2 or 3 is selected based on maximum flow
requirement.
The setting is intended for underfloor heating systems.
Capacity, circulation pump (CP)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
80
50
40
70
60
30
Tryck
(kPa)
Fl de
(l/s)
3
2
1
Pressure
Flow
Output, circulation pump (CP)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
60
50
40
30
Effekt
(W)
Flöde
(l/s)
32 1
Output
Flow
LED indicationPump speed
CP
1
2
3
CONSTANT CURVE (CC)
The circulation pump’s speed is fixed and no regulation
takes place. Speed is selected based on maximum flow
requirement.
The setting can be used when very high flows are re-
quired.
Capacity, circulation pump (CC)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
80
50
40
70
60
30
Tryck
(kPa)
Fl de
(l/s)
3
2
1
Pressure
Flow
Output, circulation pump (CC)
00 0,2 0,4 0,6 0,8 1,0 1,2
10
20
60
50
40
30
Effekt
(W)
Fl de
(l/s)
3
2
1
Output
Flow
LED indicationPump speed
CC
1
2
3
ECS 40/ECS 41 S-series | GB10
S

ALARM
If an alarm occurs, LED shines red.
When one or more alarms are active, this is indicated
according to the following table. If more than one alarm
is active, the one with the highest priority is displayed.
LED indicationCause / Action
The rotor is blocked. Wait or
release the rotor shaft.
Supply voltage too low.
Check the supply voltage.
Electrical fault. Check the
supply voltage or replace
the circulation pump.
11ECS 40/ECS 41 S-series | GB
S

Outline diagrams
Caution
These are outline diagrams.
Real installations must be planned according
to applicable standards.
EXPLANATION
Heat pumpEB100
SMO S40AA35
Heat pumpEB101
Climate system 2 (ECS 40/ECS 41)EP21
Climate system 3 (ECS 40/ECS 41)EP22
AXC moduleAA25
Flow temperature sensor, extra climate
system
BT2
Return line sensor, extra climate systemBT3
Circulation pump, extra climate systemGP10
Shunt valveQN25
Non-return valveRM1
Designations according to standard EN 81346-2.
Outline diagram S1155 / S1255 / VVM S320 / VVM S325
with ECS 40/ECS 41
-EB100
-EP22-RM1
-EP22-GP10-EP22-BT2
-EP22-AA25
-EP22-QN25
-EP22-BT3
-EP22
-EP21-RM1
-EP21-GP10-EP21-BT2
-EP21-AA25
-EP21-BT3
-EP21-QN25
-EP21
Outline diagram SMO S40 with ECS 40/ECS 41
-AA35
-EB101
-EP22-RM1
-EP22-GP10-EP22-BT2
-EP22-AA25
-EP22-QN25
-EP22-BT3
-EP22
-EP21-RM1
-EP21-GP10-EP21-BT2
-EP21-AA25
-EP21-BT3
-EP21-QN25
-EP21
ECS 40/ECS 41 S-series | GB12
S

Electrical connection
NOTE
All electrical connections must be carried out
by an authorised electrician.
Electrical installation and wiring must be carried
out in accordance with the stipulations in force.
The climate unit must not be powered when
installing ECS 40/ECS 41.
• To prevent interference, sensor cables to external
connections must not be laid close to high voltage
cables.
• The minimum area of communication and sensor
cables to external connections must be 0.5 mm² up
to 50 m, for example EKKX, LiYY or equivalent.
• ECS 40/ECS 41 must be installed via an isolator
switch. The cable area has to be dimensioned based
on the fuse rating used.
• Mark the relevant electrical cabinet with a warning
about external voltage, in those cases where a com-
ponent in the cabinet has a separate supply.
• ECS 40/ECS 41 restarts after a power failure.
The electrical circuit diagram is at the end of this Installer
handbook.
CABLE LOCK
Use a suitable tool to release/lock cables in terminal
blocks.
LEK
1
1
2
2
3
3
1
2
3
3
4
1
2
LEK
1
1
2
2
3
3
1
2
3
3
4
1
2
1
2
MOUNTING
The AXC module (AA25) is a separate, electric control
module and must be mounted on a wall.
Caution
The screw type must be adapted to the surface
on which installation is taking place.
Installation is not permitted using glue or tape.
UN
Use all mounting points and mount the module upright,
flat against the wall.
Leave at least 100 mm of free space around the module
to allow access and make cable routing easier during
installation and servicing.
NOTE
The installation must be carried out in such a
way that IP21 is satisfied.
OVERVIEW ACCESSORY BOARD (AA5)
ON
12345678
-X9
-X2
24 20212223 1516171819 1011121314 56789 1
1
N
L
PE
PE
1
2
3
4
5
6
7
8
2
3
4
5
6
7
8
9
234
-X8
-X4
-X10
-X1
AA5-X2 AA5-X9AA5-S2
AA5-X4
13ECS 40/ECS 41 S-series | GB
S

CONNECTING COMMUNICATION
CONNECTING TO HEAT PUMP OR INDOOR
MODULE
ECS 40/ECS 41 contains an accessory board (AA5) that
connects directly to the main product’s PCB (terminal
block AA2-X30).
If more accessories are to be connected, or are already
installed, the boards are connected in series.
Because there can be different connections for accessor-
ies with accessory board (AA5), you should always read
the instructions in the manual for the accessory that is
to be installed.
B
A
GND
+12V
AA2-X30
1234
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
Main product
Accessory 1
Accessory 2
CONNECTING TO CONTROL MODULE
ECS 40/ECS 41 contains an accessory board (AA5) that
connects directly to the control module on its joint board
(terminal block AA100-X9).
If more accessories are to be connected, or are already
installed, the boards are connected in series.
Because there can be different connections for accessor-
ies with accessory board (AA5), you should always read
the instructions in the manual for the accessory that is
to be installed.
+12V
GND
B
A
AA100-X9
7
8
9
10
11
12
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
Accessory 1
Accessory 2
SMO S40
POWER CONNECTION
Connect the power supply cable to terminal block AA25-
X1 as illustrated.
Tightening torque for earth cable: 0.5–0.6 Nm.
AA25-X1
N
L
ExterntProduktNamn
2
1
AA25 External
ECS 40/ECS 41 S-series | GB14
S

CONNECTION OF SENSORS AND EXTERNAL
ADJUSTMENT
For the location of the terminal blocks, see Component
location, AXC module (AA25) page 5.
SUPPLY TEMPERATURE SENSOR, EXTRA
CLIMATE SYSTEM (BT2)
Connect the supply temperature sensor to AA5-X2:23-
24.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
BT2
AA5-X2
RETURN LINE SENSOR, EXTRA CLIMATE
SYSTEM (BT3)
Connect the return line sensor to AA5-X2:21-22.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
BT3
AA5-X2
ROOM SENSOR, EXTRA CLIMATE SYSTEM
(BT50) (OPTIONAL)
Connect the room sensor to AA5-X2:19-20.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
BT50
AA5-X2
EXTERNAL ADJUSTMENT (OPTIONAL)
A potential-free switch can be connected to AA5-X2:17-
18 for external adjustment of the climate system.
24 23 22 21 20 19 18 17 16 15 14 13
AA25
External
AA5-X2
External adjustment
Caution
The relay outputs on the accessory board can
have a max load of 2 A (230 V) in total.
CONNECTION OF THE CIRCULATION PUMP
(GP10)
Connect the external heating medium pump (GP10) to
AA5-X9:7 (N), AA5-X9:8 (230 V) and X1:PE.
1
2
3
4
5
6
7
8
9
AA5-X9
2
1
1
M
AA25-X1
ExternalAA25
GP10
CONNECTION OF THE SHUNT VALVE
MOTOR (QN25)
Connect the shunt motor (QN25) to AA5-X9:6 (230V,
open), AA5-X9:5 (N) and AA5-X9:4 (230V, close).
1
2
3
4
5
6
7
8
9
AA25 External
AA5-X9
QN25
Open SH +
N
SH -
Close
15ECS 40/ECS 41 S-series | GB
S

DIP SWITCH
The DIP switch (S2) on the accessory board (AA5) is set
as follows, with each climate system having a unique
setting.
Climate system
5432
ON
12345678
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
876
ON
12345678
ON
12345678
ON
12345678
ECS 40/ECS 41 S-series | GB16
S

Program settings
Program setting of ECS 40/ECS 41 can be performed
via the start guide or directly in the menu system.
START GUIDE
The start guide appears at first start-up after installation
of the heat pump/indoor module, but is also found in
menu .7.7.
MENU SYSTEM
MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Add or remove accessories here.
Select: "Climate system 2-8".
MENU 1.1 - TEMPERATURE
You make temperature settings for your installation here.
MENU 1.3 - ROOM SENSOR SETTINGS
Here, you make your settings for room sensors and
zones. The room sensors are grouped by zone.
Here, you select the zone to which a sensor will belong.
It is possible to connect multiple room sensors to each
zone. Each room sensor can be given a unique name.
The control of heating, cooling, humidity and ventilation
are activated by ticking each option. Which options are
shown depends on which type of sensor is installed. If
control is not activated, the sensor will be the displaying
sensor.
Caution
A slow heating system such as underfloor
heating may be inappropriate for controlling
with room sensors.
MENU 1.30.1 - CURVE, HEATING
Curve, heating
Setting range: 0 – 15,0
In menu "Curve, heating" you can view the heating curve
for your house. The task of the heating curve is to
provide an even indoor temperature, regardless of the
outdoor temperature. It is from this heating curve that
ECS 40/ECS 41 determines the temperature of the water
to the climate system, the supply temperature, and
therefore the indoor temperature. Here, you can select
heating curve and read off how the supply temperature
changes at different outdoor temperatures.
TIP
It is also possible to create your own curve.
This is done in menu 1.30.7.
Caution
With underfloor heating systems, the maxim-
um supply temperature is normally set
between 35 and 45 °C.
Check the max floor temperature with your
floor supplier.
TIP
Wait 24 hours before making a new setting,
so that the room temperature has time to sta-
bilise.
If it is cold outdoors and the room temperature
is too low, increase the curve slope by one in-
crement.
If it is cold outdoors and the room temperature
is too high, lower the curve slope by one incre-
ment.
If it is warm outdoors and the room temperat-
ure is too low, increase the curve offset by one
increment.
If it is warm outdoors and the room temperat-
ure is too high, lower the curve offset by one
increment.
MENU 1.30.3 - EXTERNAL ADJUSTMENT
Climate system
Setting range: -10 – 10
Setting range (if room sensor is installed): 5 – 30 °C
Connecting an external contact, for example, a room
thermostat or a timer allows you to temporarily or peri-
odically raise or lower the room temperature. When the
contact is on, the heat curve offset is changed by the
number of steps selected in the menu. If a room sensor
is installed and activated the desired room temperature
(°C) is set.
MENU 1.30.4 - LOWEST SUPPLY HEATING
heating
Setting range: 5 – 80 °C
Set the minimum temperature on the supply temperat-
ure to the climate system. This means that
ECS 40/ECS 41 never calculates a temperature lower
than that set here.
17ECS 40/ECS 41 S-series | GB
S

MENU 1.30.5 - LOWEST SUPPLY COOLING
cooling
Depending on which cooling accessory is used, the
setting range can vary.
Setting range 7 – 30 °C
Alarm, room sensor during cooling operation
Setting range: on/off
Set the minimum temperature on the supply temperat-
ure to the climate system. This means that
ECS 40/ECS 41 never calculates a temperature lower
than that set here.
Here, you can receive alarms during cooling operation,
for example if a room sensor malfunctions.
NOTE
Cooling flow line must be set with regard to
which climate system is connected. For ex-
ample, floor cooling with too low cooling flow
line can cause condensation precipitation,
which in the worst instance could lead to
moisture damage.
MENU 1.30.6 - HIGHEST SUPPLY HEAT
climate system
Setting range: 5 – 80 °C
Here, you set the highest supply temperature for the
climate system. This means that ECS 40/ECS 41 never
calculates a temperature higher than the one set here.
Caution
With underfloor heating systems, "Maximum
supply temperature for heating" should nor-
mally be set between 35 and 45°C.
Check the max floor temperature with your
floor supplier.
MENU 1.30.7 - OWN CURVE
Own curve, heat
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own heating curve here, if there
are special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: 5 – 80 °C
Own curve, cooling
Caution
Curve 0 must be selected for own curve to
apply.
You can create your own cooling curve here, if there are
special requirements, by setting the desired supply
temperatures for different outdoor temperatures.
Supply temp
Setting range: -5 – 40 °C
MENU 7.2.4 - EXTRA CLIMATE SYSTEM (ECS)
Use in cooling mode
Setting range: on/off
Shunt amplification
Setting range: 0.1 – 10.0
Shunt waiting time
Setting range: 10 – 300 s
Contr. pump GP10
Setting range: on/off
Control signal
Setting range: PWM / 0-10V*
Manual speed
Setting range: 0 – 100%
Factory setting: 70%
*Factory setting
The shunt amplification and shunt waiting time for the
different extra climate systems that are installed are
also set here.
MENU 7.5.3 - FORCED CONTROL
Here you can force control the various components in
the installation. The most important safety functions
remain active however.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
Caution
Also see the Installer Manual for the relevant
heat pump.
ECS 40/ECS 41 S-series | GB18
S

Technical data
TECHNICAL SPECIFICATIONS
AXC module
Electrical data
230 V ~ 50 HzRated voltage
IP 21Enclosure class
4kVRated value for impulse voltage
2Pollution degree
10AMin fuse rating
Miscellaneous
Type 1Operation mode according to EN 60 730-1
-25 – 70°CArea of operation
5 – 35°CAmbient temperature
1, 24Program cycles, hours
1, 2, 5, 7Program cycles, days
1min.Resolution, program
75°CTemperature, ball pressure test
175x250x100mmDimensions LxWxH
1.47kgWeight
Lead in brass
components
Substances according to Directive (EG) no. 1907/2006, article 33 (Reach)
ESC 41ECS 40
6.34.0cwsvalue
22mmConnection valve Ø
230V~ 50HzRated voltage
067 288067 287Part No.
19ECS 40/ECS 41 S-series | GB
S

ELECTRICAL CIRCUIT DIAGRAM
Part Specification Sheet 051057-11
Page 2/2 Created:2020-02-13 10:24
JOV 2020-02-13
Production ASN 2012-04-02
0.001
WIRING DIAGRAM ECS
ELSCHEMA ECS
051057 11
ECS 40/ECS 41 S-series | GB20
S
Other manuals for S Series
4
This manual suits for next models
3
Table of contents
Other Nibe Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

DOTECH
DOTECH TX3 Series operating instructions

Ropex
Ropex RESISTRON RES-5027 operating instructions

Gemo
Gemo LT102HT quick start guide

Carbolite
Carbolite 201 operating instructions

REGLOPLAS
REGLOPLAS 300L operating instructions

Viessmann
Viessmann VITOSOLIC 100 Installation and service instructions for contractors