7.4 Process data setting
In the following section, the process data, which is required for the application and is described under chapter 6.1,
can be set.
Table 15: Process data
ISDU
Name Data
type
Data
repo
sitor
y
Length Acce
ss
Defa
ult
valu
e
Value/range
Index Sub-
inde
x
DEC HEX
120 78
-
Process data select UInt
yes
8 bits
rw
0
0 = System status, Q status, and run length code
1 = System status, Q status, and beam status (for value 1 max. no. of beams = 240)
2 = User-defined process data
67 43 Process data user def‐
inition Record 16 byt
es
User-defined output
function 1
Offset
120 bi
ts 20 0 = No function
1 = RLC 1 – 1st value of the run length code
2 = RLC 2 – 2nd value of the run length code
3 = RLC 3 – 3rd value of the run length code
4 = RLC 4 – 4th value of the run length code
5 = RLC 5 – 5th value of the run length code
6 = RLC 6 – 6th value of the run length code
7 = RLC 7 – 7th value of the run length code
8 = RLC 8 – 8th value of the run length code
9 = RLC 9 – 9th value of the run length code
10 = RLC 10 – 10th value of the run length code
11 = RLC 11 – 11th value of the run length code
12 = RLC 12 – 12th value of the run length code
13 = RLC 13 – 13th value of the run length code
14 = RLC 14 – 14th value of the run length code
15 = RLC 15 – 15th value of the run length code
16 = RLC 16 – 16th value of the run length code
17 = System status (high byte) and Q status (low
byte)
18 = Number of beams blocked
19 = Number of beams made
20 = First beam blocked
21 = First beam made
22 = Last beam blocked
23 = Last beam made
24 = Number of consecutive beams blocked
25 = Number of consecutive beams made
26 = Central beam blocked
27 = Central beam made
28 = Outside dimension
29 = Inside dimension
30 = Virtual outputs (VQs)
31 = Teach quality
32 = Process quality
33 = Data update counter
Selection of beam functions, zone 1
34 = NBB Z1 – Number of beams blocked,
zone 1
35 = FBB Z1 – First beam blocked, zone 1
36 = LBB Z1 – Last beam blocked, zone 1
37 = NCBB Z1 – Number of consecutive
beams blocked, zone 1
38 = CBB Z1 – Central beam blocked, zone 1
Selection of beam functions, zone 2
39 = NBB Z2 – Number of beams blocked,
zone 2
40 = FBB Z2 – First beam blocked, zone 2
41 = LBB Z2 – Last beam blocked, zone 2
42 = NCBB Z2 – Number of consecutive
beams blocked, zone 2
43 = CBB Z2 – Central beam blocked, zone 2
Selection of beam functions, zone 3
44 = NBB Z3 – Number of beams blocked,
zone 3
45 = FBB Z3 – First beam blocked, zone 3
46 = LBB Z3 – Last beam blocked, zone 3
47 = NCBB Z3 – Number of consecutive
beams blocked, zone 3
48 = CBB Z3 – Central beam blocked, zone 3
Selection of beam functions, zone 4
49 = NBB Z4 – Number of beams blocked,
zone 4
50 = FBB Z4 – First beam blocked, zone 4
51 = LBB Z4 – Last beam blocked, zone 4
52 = NCBB Z4 – Number of consecutive
beams blocked, zone 4
53 = CBB Z4 – Central beam blocked, zone 4
User-defined output
function 2
112 bi
ts 18
User-defined output
function 3
104 bi
ts 22
User-defined output
function 4 96 bits 20
User-defined output
function 5 88 bits 28
User-defined output
function 6 80 bits 29
User-defined output
function 7 72 bits 0
User-defined output
function 8 64 bits 0
User-defined output
function 9 56 bits 0
User-defined output
function 10 48 bits 0
User-defined output
function 11 40 bits 0
User-defined output
function 12 32 bits 0
User-defined output
function 13 24 bits 0
User-defined output
function 14 16 bits 0
User-defined output
function 15 8 bits 0
User-defined output
function 16 0 bits 0
SERVICE DATA 7
8022573/2018-01-19 | SICK T E C H N I C A L I N F O R M A T I O N | MLG-2 17