V2 ZARISS-M User manual

Zariss
IL n. 341-1
EDIZ. 27/04/2011
V2 S.p.A.
Corso Principi di Piemonte, 65/67
12035 ACCONIGI (CN) ITALY
tel. +39 01 72 81 24 11 - fax +39 01 72 84 050
ATTUATORE ELETTROMECCANICO IRREVERSIBILE
A BRACCIO SNODATO PER CANCELLI A BATTENTE
IRREVERSIBLE ELECTROMECHANICAL PIVOTING
ARM ACTUATOR FOR SWING GATES
ACTIONNEUR ÉLECTROMÉCANI UE IRRÉVERSIBLE
AVEC BRAS ARTICULÉ POUR PORTAILS BATTANTS
ACTUADOR ELECTROMECÁNICO IRREVERSIBLE
DE BRAZO ARTICULADO PARA CANCELAS BATIENTES
I
GB
F
E


ENGLISH
41
INDEX
1 - GENERAL SAFETY INFORMATION....................................................................................................................................42
1.1 - P ELIMINA Y CHECKS and IDENTIFICATION OF THE TYPE TO BE USED ..................................................................42
1.2 - TECHNICAL ASSISTANCE SE VICE ..........................................................................................................................43
1.3 - EC DECLA ATION OF INCO PO ATION FO PA TLY COMPLETED MACHINE Y ......................................................43
2 - TECHNICAL DATA..............................................................................................................................................................44
3 - INSTALLATION OF THE MOTOR ......................................................................................................................................44
3.1 - INSTALLATION LAYOUT ..........................................................................................................................................44
3.2 - INSTALLATION MEASU ES ......................................................................................................................................45
3.3 - INSTALLATION OF THE MOTO ................................................................................................................................46
3.4 - MOTO UNBLOCKING ............................................................................................................................................47
3.5 - FIXING THE OPENING MECHANICAL STOP ..............................................................................................................47
4 - CONTROL UNIT ................................................................................................................................................................48
4.1 - ENE GY SAVING FUNCTION....................................................................................................................................48
4.2 - INSTALLATION ........................................................................................................................................................48
4.3 - CONNECTION OF THE MOTO ................................................................................................................................48
4.4 - EXTE NAL PHOTOCELL CONNECTION ....................................................................................................................49
4.5 - INTE NAL PHOTOCELL CONNECTION ....................................................................................................................49
4.6 - CONNECTING SAFETY IBBONS ..............................................................................................................................49
4.7 - ACTIVATION INPUTS................................................................................................................................................50
4.8 - STOP ......................................................................................................................................................................50
4.9 - LOW VOLTAGE LIGHT OUTPUT................................................................................................................................50
4.10 - COU TESY LIGHTS................................................................................................................................................50
4.11 - LOCK ....................................................................................................................................................................51
4.12 - EXTE NAL AE IAL ................................................................................................................................................51
4.13 - PLUG IN ECEIVE ................................................................................................................................................51
4.14 - ADI INTE FACE ....................................................................................................................................................51
4.15 - POWE SUPPLY ....................................................................................................................................................51
4.16 - BATTE Y POWE ..................................................................................................................................................51
4.17 - ELECT ICAL CONNECTION SUMMA Y..................................................................................................................52
5 - CONTROL PANEL ..............................................................................................................................................................53
5.1 - DISPLAY ..................................................................................................................................................................53
5.2 - USE OF THE KEYS FO P OG AMMING..................................................................................................................54
6 - INITIALISING THE CONTROL UNIT....................................................................................................................................54
7 - ACCESSING THE CONTROL UNIT SETTINGS ....................................................................................................................56
8 - RAPID CONFIGURATION ..................................................................................................................................................56
8.1 - POWE ADJUSTMENT ............................................................................................................................................57
8.2 - OBSTACLE SENSO ADJUSTMENT ..........................................................................................................................57
8.3 - OPE ATIONAL LOGIC ..............................................................................................................................................58
8.4 - EXITING APID CONFIGU ATION ............................................................................................................................58
9 - LOADING THE DEFAULT PARAMETERS............................................................................................................................59
10 - WORKING TIME SELF-TRAINING....................................................................................................................................60
11 - READING OF CYCLE COUNTER ......................................................................................................................................61
12 - PROGRAMMING THE CONTROL UNIT ..........................................................................................................................62
12.1 - SUMMA Y OF FUNCTIONS ..................................................................................................................................74
13 - OPERATION DEFECTS......................................................................................................................................................76
14 - TESTING AND START-UP ................................................................................................................................................78
15 - MAINTENANCE ..............................................................................................................................................................78
16 - DISPOSAL ........................................................................................................................................................................79

ENGLISH
42
1 - GENERAL SAFETY INFORMATION
Prior to proceeding with installation, it is essential the instructions be read in full, since they contain important information
regarding safety, installation, use and maintenance.
• Anything not expressly described in these instructions is prohibited; unforeseen uses may be a source of danger to people and property.
• Do not install the product in explosive environments and atmospheres: the presence of inflammable gases or fumes is a serious safety
hazard.
• Do not make any modifications to any part of the automation device, or the accessories connected to it, unless described in this manual.
• Any other modifications will void the warranty on the product.
• The installation steps should be conducted so as to avoid rainy weather, which can expose electronic circuits to dangerous water
seepage.
• All operations requiring the casing of the device to opened should be performed with the control unit disconnected from the electricity
supply and with a warning notice displayed, for example: ”CAUTION, MAINTENANCE IN P OG ESS”.
• Avoid exposing the device close to sources of heat and flame.
• In the event of interventions on automatic or differential breakers or fuses, it is essential that faults be identified and resolved prior to
resetting. In the case of faults that cannot be resolved using the information to be found in this manual, consult the V2 customer
assistance service.
• V2 declines all responsibility for failure to comply with good construction practice standards in addition to structural deformation of the
gate that might occur during use.
• V2 reserves the right to make modifications to the product without prior warning.
• Installation/maintenance personnel should wear individual protection devices (IPDs), such as overalls, safety helmets, boots and gloves.
• The ambient operating temperature should be that indicated in the technical characteristics table.
• The automation device should be shut down immediately in the event of any anomalous or hazardous situation; the fault or malfunction
should be immediately reported to the person responsible.
• All safety and hazard warnings on the machinery and equipment should be complied with.
• Electromechanical actuators for gates are not intended to be used by people (including children) with diminished physical, sensory or
mental capacity, or lacking in experience or knowledge, unless they are under supervision or have been instructed in use of the actuator
by a person responsible for safety.
• DO NOT introduce objects of any kind into the compartment below the motor cover.
The compartment should remain free in order to aid with motor cooling.
1.1 - PRELIMINARY CHECKS AND IDENTIFICATION OF THE TYPE TO BE USED
The automation device should not be used until installation, as specified in “Testing and start-up”, has been performed.
It should be remembered that the device does not compensate for defects caused by improper installation, or poor maintenance, thus,
prior to proceeding with installation, ensure that the structure is suitable and meets current standards and, if necessary, perform any
structural modifications aimed at the implementation of safety gaps and the protection or segregation of all crushing, shearing and transit
zones, and verify that:
• The gate has no friction points, either during closing or opening.
• The gate is well balanced, i.e. there is no tendency to move spontaneously when stopped in any position.
• The position identified for fixing the motor reducer allows easy and safe manual manoeuvring, compatible with the size of the motor
reducer itself.
• The support on which the automation device will be fixed is solid and durable.
• The mains power supply to which the automation device is connected has a dedicated safety earthing system and differential breaker
with tripping current less than or equal to 30 mA (the breaker gap distance should be greater than or equal to 3 mm).
Warning: The minimum safety level depends on the type of use; please refer to the following outline:
Closure use type
Type of activation commands
Group 1
Informed people
(use in private area)
Group 2
Informed people
(use in public area)
Group 3
Informed people
(unlimited use)
Man-present command A B Not possible
emote control and closure in view
(e.g. infrared) Cor E C or E C and Dor E
emote control and closure not in view
(e.g. radio) Cor E C and Dor E C and Dor E
Automatic control
(e.g. timed closure control) Cand Dor E C and Dor E C and Dor E

ENGLISH
43
Group 2 - Only a limited number of people are authorised for use, but in this case, closure is in a public area. An example of this may be a
company gate that accesses onto a public street, and which is only used by employees.
Group 3 - Anyone can use the automated closure, which is thus located on public land. For example the access gate to a supermarket or an
office, or a hospital.
Protection A - Closure is activated by means of a control button with the person present, i.e. with maintained action.
Protection B - With the person present, closure is activated by a command controlled by means of a key-switch or the like, in order to
prevent use by unauthorised persons.
Protection C - estricts the force of the leaf of the door or gate. I.e., in the case of the gate striking an obstacle, the impact force must fall
within a curve established by the regulations.
Protection D - Devices, such as photocells, capable of detecting the presence of people or obstacles. They may be active on just one side or
on both sides of the door or gate.
Protection E - Sensitive devices, such as footboards or immaterial barriers, capable of detecting the presence of a person, and installed in
such a way that the latter cannot be struck in any way by a moving leaf or panel. These devices should be active within the entire “danger
zone” of the gate. The Machinery Directive defines “Danger Zone” as any zone surrounding and/or near machinery where the presence of
an exposed person constitutes a risk to the health and safety of that person.
The risk analysis should take into consideration all danger zones for the automation device, which should be appropriately
protected and marked.
In a clearly visible area, apply a sign with information identifying the motorised door or gate.
The installer should provide the user with all the information relating to automatic operation, emergency opening and
maintenance of the motorised door or gate.
1.2 - TECHNICAL ASSISTANCE SERVICE
For any installation problem please contact our Customer Service at the number +39-0172.812411 operating Monday to Friday
from 8:30 to 12:30 and from 14:00 to 18:00.
1.3 - EC DECLARATION OF INCORPORATION FOR PARTLY COMPLETED MACHINERY
(DIRECTIVE 2006/42/EC, ANNEX II-B)
The manufacturer V2 S.p.A., headquarters in Corso Principi di Piemonte 65, 12035, acconigi (CN), Italy
Under its sole responsibility hereby declares that:
the partly completed machinery model(s):
ZA ISS-M-230V
ZA ISS-S-230V
Identification number and year of manufacturing: typed on nameplate
Description: electromechanical actuator for gates
• is intended to be installed on gates, to create a machine according to the provisions of the Directive 2006/42/EC.
The machinery must not be put into service until the final machinery into which it has to be incorporated has been declared in conformity
with the provisions of the Directive 2006/42/EC (annex II-A).
• is compliant with the applicable essential safety requirements of the following Directives:
Machinery Directive 2006/42/EC (annex I, chapter 1)
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive 2004/108/EC
adio Directive 99/05/EC
The relevant technical documentation is available at the national authorities’ request after justifiable request to:
V2 S.p.A., Corso Principi di Piemonte 65, 12035, acconigi (CN), Italy
The person empowered to draw up the declaration and to provide the technical documentation:
Cosimo De Falco
Legal representative of V2 S.p.A.
acconigi, 11th April 2010

ENGLISH
44
ZARISS-M ZARISS-S
Max. leaf length and weight m x Kg 2,2 x 200
1,2 x 250
Power supply Vac / Hz 230 - 50 24 Vdc
Maximum power (2 motors) W 180
Full load current A 0,4 3,5
Speed pm 1,1 ÷ 1,65
Torque N m 180
Working temperature °C -20 ÷ +55
Working cycle % 30
Motor weight Kg 10 8
Protection IP 44
3 - INSTALLATION OF THE MOTOR
3.1 - INSTALLATION LAYOUT
ZA ISS-M actuator cable 3 x 1 mm2
ZA ISS-S actuator cable 3 x 1,5 mm2
Flashing light
(LUMOS-24V, with built-in
antenna)
cable 2 x 1,5 mm2
cable G174 (antenna)
Key switch cable 2 x 0,5 mm2
emote control -
Digital radio switch -
External photocells cable 4 x 0,5 mm2( X)
cable 2 x 0,5 mm2(TX)
Internal photocells cable 4 x 0,5 mm2( X)
cable 2 x 0,5 mm2(TX)

ENGLISH
45
To carry out a proper installation of the operator parts as well as
to ensure the best automation performance, the measurement
levels shown in the following table shall be complied with.
Change the gate structure to adapt it to one of the cases in the
table, if necessary.
1. Depending on the opening angle of the leaves or panels,
make sure it is possible to respect the dimensions reported in
the table
2. Measure the value of Bon-site
3. Based on the value for dimension Band the opening angle of
the leaves or panels, the value of Amay be deduced from the
table
PLEASE NOTE: the maximum permitted value for
dimension C is 650 mm. A greater value might result in
malfunctioning and consequent damage to the motor
B A
90°
0 ÷ 60 120
60 ÷ 150 130
150 ÷ 180 140
180 ÷ 210 150
210 ÷ 230 160
230 ÷ 250 170
B A
110°
0 ÷ 20 210
20 ÷ 30 220
30 ÷ 40 230
50 ÷ 60 240
60 ÷ 70 250
70 ÷ 80 260
80 ÷ 90 270
90 ÷ 110 280
B A
100°
0 ÷ 50 150
50 ÷ 100 160
100 ÷ 130 170
130 ÷ 150 180
150 ÷ 170 190
170 ÷ 200 200
PLEASE NOTE: ensure there are no
obstacles near the motor that might
interfere with the arm, both during
movement and with the gate open.

ENGLISH
46
To install the ZA ISS motor, follow the following steps closely:
1. Fix bracket Ato the pillar using rawplugs suited to the pillar
material
PLEASE NOTE: the bracket should be perfectly horizontal.
Use a spirit level to accurately position the bracket
2. Position the straight arm Con the motor shaft
3. Tighten screw E, after having inserted the washer
PLEASE NOTE: the casing Dshould be fitted later, after
having fixed the opening mechanical stop
4. Fix the motor reducer onto bracket Ausing the two screws F
and the relevant nuts and washers
5. Fit the curved arm Gonto the straight arm Cusing the
pivot-pin I and snap-ring L
6. Fit the bracket Bonto the curved arm Gusing the pivot-pin I
and snap-ring L
7. Fix the bracket Bonto the gate by welding or using
appropriate screws for the gate-leaf material
PLEASE NOTE: bracket Bshould be level with the lower part
of bracket A

ENGLISH
47
3.4 - MOTOR UNBLOCKING
In the case of a power failure, the gate can be unblocked
by operating the motor:
1. Open the lock cover Jlocated on the front of the motor
2. Insert the key Linto the hole and turn clockwise until
reaching the end-stop
To reset the automation device, proceed as follows:
1. Turn the key Lanti-clockwise until reaching the end
stop and then extract it
2. Close the lock using the cover J
3.5 - FIXING THE OPENING
MECHANICAL STOP
1. elease the motor reducer
2. Open the leaf/door to its maximum opening position
3. Position stop Min close contact with the arm
4. Tighten the screws N
5. Loosen the screws fixing the straight arm to the motor
reducer
6. Position the casing Don the straight arm and tighten
the screw Eafter having inserted the washer

ENGLISH
48
PD12 is provided with a display that, not only makes
programming simple, but also allows a continuous monitoring of
the input statuses; in addition, thanks to a menu structure, the
working schedule and the operation logic can be set easily.
In compliance with the European standards concerning electrical
safety and electromagnetic compatibility (EN 60335-1, EN 50081-
1 and EN 50082-1) it has been equipped with the low voltage
circuit total electric insulation (motors included) from the network
voltage.
Other characteristics:
• Power supply protected from short circuits within the
controller, on the motors and on the connected accessories.
• Adjustment of the power by partializing the current.
• Detecting obstacles by monitoring the current on the motors
(current sensing probe)
• Automatic learning of the operation time
• Obstacle sensor: a system allowing detection of whether
movement of the gate is impeded by an obstacle.
This system is based on measurement of the current absorbed
by the motor: an unexpected increase in current absorption
indicates the presence of an obstacle.
• Tests for safety devices (photocells and safety ribbons) before
each opening.
• Deactivation of safety inputs through the configuration menu:
no jumper is required for terminals concerning safety devices
that have not been installed, yet. You will only need to disable
this function from its relevant menu.
• The device can operate without mains power, by using the
optional battery pack (code 161212).
• Low voltage output that can be used for a signal light or a
24V flashing light.
• Auxiliary relay with programmable logic for courtesy light,
flashing light or other use.
• ENE GY SAVING function
4.1 - ENERGY SAVING FUNCTION
This function is useful for reducing the energy consumption of
the automation device while in stand-by mode.
If the function is enabled, the control unit will enter ENE GY
SAVING mode under the following conditions:
• 5 seconds after completion of an operational cycle
• 5 seconds after an opening (if automatic closure is not
enabled)
• 30 seconds after exiting the programming menu
In ENE GY SAVING mode, power to the accessories, display and
flashing lights is deactivated.
ENE GY SAVING mode is exited:
• If an operational cycle is activated
• If one of the menus is accessed
Installation of control unit and safety devices must be carried out
with power disconnected.
4.3 - CONNECTION OF THE MOTOR
The control unit is supplied already connected to the MASTE
motor.
The SLAVE motor (if used) should be connected to terminals
K1 - K2 - K3, following the polarity indicated on the labels
attached to the control unit and the Slave motor itself.

ENGLISH
49
PHOTOCELLS - INSTRUCTIONS
• The control unit powers the photocells at a nominal voltage of
24 Vdc, with an electronic fuse that breaks the current in the
case of an overload.
• If the transmitter power supply is connected to terminals
K8 and K9, the control unit can perform the photocell
operation test prior to starting gate opening.
• The photocells on the interior side should be installed so as to
completely cover the gate opening area.
• If several pairs of photocells are installed on the same side of
the gate, the receiver N.C. outputs should be connected in
series.
• The photocells are not powered when the control unit is in
ENE GY SAVING mode.
4.4 - EXTERNAL PHOTOCELL CONNECTION
Photocells installed on the exterior side of the gate should be
connected as follows:
• Connect the transmitter power supply to terminals
K8 (+Test) and K9 (-)
• Connect the receiver power supply to terminals
K10 (+24 VDC) and K9 (-)
• Connect the receiver N.C. output to terminals
J5 (PHOTO) and J4 (COM)
Photocells thus connected are active during closure.
In the case of tripping the photocell, the control unit immediately
re-opens the gate (without waiting for disengagement).
4.5 - INTERNAL PHOTOCELL CONNECTION
Photocells installed on the interior side of the gate should be
connected as follows:
• Connect the transmitter power supply to terminals
K8 (+Test) and K9 (-)
• Connect the receiver power supply to terminals
K10 (+24 VDC) and K9 (-)
• Connect the receiver N.C. output to terminals
J6 (PHOTO) and J4 (COM)
Photocells thus connected are active both during opening and
during closing. In the case of the photocell tripping, the control
unit immediately stops the gate.
When the photocell is disengaged, the gate re-opens fully.
SAFETY RIBBONS - INSTRUCTIONS
• If several edges, with normally closed contacts, are used, the
outputs should be connected in series.
• If several conductive rubber edges are used, the outputs should
be connected in cascade, and only the final edge should be
terminated on the nominal resistance.
• Active edges connected to the accessory power supply are
inactive when the control unit switches to ENE GY SAVING
mode.
• To meet the requirements of EN12978, it is necessary to install
conductive rubber sensitive edges; contact normally closed
sensitive edges should have a control unit that constantly
verifies their correct operation. If control units with the option
to conduct testing by interrupting the power are used, connect
the control unit power cables between terminals K9 (-) and
K8 (+Test) on the PD12.
Otherwise, connect them between terminals
K10 (+) and K9 (-).
Testing the edges should be activated by means of the
Co.tE menu.
4.6 - CONNECTING SAFETY RIBBONS
The control unit considers two kinds of safety ribbons,
depending on the terminal to which they are connected:
•Type 1 (fixed): they are mounted on walls or on other fixed
obstacles that are approached by the gate doors during the
opening phase. When type 1 safety ribbons operate during the
gate opening phase, the control unit will close the doors
for 3 seconds, then it stands still; when type 1 safety ribbons
operate during the gate closing phase, the control unit will
stand still immediately. The direction of the gate at next
command of STA T or PEDEST IAN STA T depends upon the
parameter STOP (it inverts or continues the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
•Type 2 (mobile): they are mounted to the door ends.
When type 2 safety ribbons operate during the gate opening
phase, the control unit will stand still immediately; when
type 2 safety ribbons operate during the gate closing, the
control unit will open the doors for 3 seconds, then it will
stand still. The direction of the gate at next command of
STA T or PEDEST IAN STA T depends upon the parameter
STOP (it inverts or continues the motion). If the input STOP
is disabled, the command makes the motion continue in the
same direction.
Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2 kohm
nominal resistance.
Connect type 1 safety ribbons cables between terminals
J7 (EDGE1) and J9 (COM) of the control unit.
Connect type 2 safety ribbons cables between terminals
J8 (EDGE2) and J9 (COM) of the control unit.

ENGLISH
50
PD12 control unit is equipped with two activation inputs, whose
operation depends on the programmed operation modes
(see Strt item of programming menu):
•Standard mode: a command being on the first input will
cause the complete opening of the gate (start); a command
being on the second input will cause the partial opening of
the gate (pedestrian start).
•Open/Close command: a command on the first input always
controls the gate opening, while a command on the second
input always controls the gate closing.
There is an impulse command, that is to say that an impulse
will cause the complete gate opening or closing.
•Manned operation: a command on the first input always
controls the gate opening, while a command on the second
input always controls the gate closing.
There is a monostable command, that is to say, the gate will
be opened or closed as long as the contact is closed and it will
immediately stop as the contact is open.
•Timer mode: it is similar to the standard mode but the gate
stays open (completely or partially) while the contact is closed
on input; as soon as the contact is open the pause time count
down will start, after which the gate will be closed again.
This function allows programming the gate opening time
during the day, by making use of an external timer.
Automatic closing must be enabled.
In all modes, inputs must be connected to devices having
normally open contacts.
Connect cables of device controlling the first input between
terminals J1 (START) and J4 (COM) of the control unit.
Connect cables of device controlling the second input between
terminals J2 (START P.) and J4 (COM) of the control unit.
The first input function can also be activated by pressing key
outside the programming menu or by means of a remote control
stored on channel 1 (see relevant instructions of M 1 receiver).
The second input function can also be activated by pressing
key outside the programming menu or by means of a
remote control stored on channel 2.
For a better safety, you can fit a stop switch that will cause the
immediate gate stop when activated. This switch must have a
normally close contact (NC) that will get open in case of
operation.
In case the STOP switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a start command (if the start function
in pause is disabled, it will be temporarily enabled to allow the
gate release).
Connect the stop switch cables between terminal J3 (STOP) and
J4 (COM) of the control unit.
The stop switch function can be activated by means of a
remote control stored on channel 3 (see relevant instructions of
M 1 receiver).
4.9 - LOW VOLTAGE LIGHT OUTPUT
The PD12 control unit has a 24 VDC output that allows
connection of a maximum load of 3 W.
This output can be used to connect a warning light, indicating
the status of the gate, or for a low voltage flashing light
(e.g. LUMOS-24V).
Connect the low voltage signal light or flashing light wires to
terminals K7 (+) and K6 (-).
CAUTION: Pay attention to the polarity of the connected
device if necessary.
4.10 - COURTESY LIGHTS
Thanks to the output COU TESY LIGHT the control unit
allows the connection of an electric appliance (e.g. courtesy
light or garden lights), controlled automatically or by means of
the special transmitter key.
The courtesy light terminals can be alternatively used for a 230V
flashing light with integrated flasher.
The output COU TESY LIGHT is a simple N.O. contact with no
power supply.
Connect the cables to terminals B1 and B2.

ENGLISH
51
An electric lock can be assembled on the gate, to ensure a good
closing of doors. Make use of a 12V lock.
Connect lock cables to terminals K4 and K5 of the control unit.
4.12 - EXTERNAL AERIAL
We suggest to use the external aerial (model: ANS433) in
order to guarantee the maximal range.
Connect the antenna hot pole to terminal A2 (ANT) of the
control unit and the braiding to terminal A1 (ANT-).
NOTE: using the LUMOS-24V flashing light with built-in antenna,
connect the terminal 3of the flashing light to the terminal
A2 (ANT) of the control unit and the terminal 4of the flashing
light to the terminal A1 (ANT-) of the control unit PD12
4.13 - PLUG IN RECEIVER
PD12 control unit is suitable for plugging in a M 1 receiver
having a high-sensitivity super-heterodyne architecture.
WARNING: it is necessary to turn off the control unit
power before doing the operations mentioned here below.
Pay attention to the way you connect the removable
modules.
M 1 module receiver is provided with 4 channels and each of
them is suitable for a command of PD12 control unit:
• CHANNEL 1 쩚쩛STA T
• CHANNEL 2 쩚쩛PEDEST IAN STA T
• CHANNEL 3 쩚쩛STOP
• CHANNEL 4 쩚쩛COU TESY LIGHT
NOTE: Before programming 4 channels and function
logics read carefully the instructions of MR1.
4.14 - INTERFACE
The ADI (Additional Devices Interface) interface of the control
unit PD12 allows the connection to V2 optional modules.
efer to V2 catalogue or to the technical sheets to see which
optional modules with ADI interface are available for this control
unit.
NOTE Please read the instructions of each single module to
install the optional modules.
4.16 - BATTERY POWER
In the case of an electricity black-out, the device may be powered
using a battery pack (accessory code 161212).
The battery pack should be housed in the specific seating, as
shown in the figure.
Connect the battery pack connecter to the BATTE Y terminals on
the control unit.
The control unit must be fed by a 230V 50Hz (120V - 50/60Hz
for the 120V models) electric line, protected by a differential
magnetothermal switch complying with the law provisions in
force.
Connect the power supply wires to terminals Land Non the
board located next to the transformer.
Connect the earth cable to terminal

ENGLISH
52
Phase power supply 230Vac
Earth
Neutral power supply 230Vac

ENGLISH
53
B1 - B2 230Vac courtesy or flashing lights
K1 Motor 2 (+)
K2 Motor 2 (ground)
K3 Motor 2 (-)
K4 - K5 12V electrolock
K6 - K7 24V courtesy or flashing lights
K8 +24Vdc supply - photocell/optical edge TX for
functional Test
K9 Accessory power common (-)
K10 +24Vdc supply for photocells and other
accessories
J1 Open command for connecting traditional
devices with N.O. contact
J2 Pedestrian open command for connecting
traditional devices with N.O. contact
J3 STOP command. N.C. contact
J4 Common (-)
J5 Exterior photocell. N.C. contact
J6 Interior photocell. N.C. contact
J7 Type 1 edges (fixed). N.C. contact
J8 Type 2 edges (mobile). N.C. contact
J9 Accessories common (-)
A1 Antenna shield
A2 Antenna
BATTERY Battery pack (code 161212)
RECEIVER Connector for M 1 receiver
Module interface
M1 Motor 1
24Vdc
Power Supply Control unit power supply (+24 VDC)
OVERLOAD Signals an overload on the accessory power
supply
PLEASE NOTE: the highlighted connections are
factory pre-wired
5.1 - DISPLAY
When power is on, the control unit checks that display correctly
operates by switching on all segments for 1.5 sec. 8.8.8.8.
Firmware version, e.g. Pr I.0, will be viewed in the following
1.5 sec.
Panel will be viewed upon completion of this test.
The control panel represents the physical status of the
terminal board contacts and of the program mode keys: if the
upper vertical segment is on, the contact is closed; if the lower
vertical segment is on, the contact is open (the above picture
shows an instance where the inputs PHOTO, PHOTO-I, EDGE and
STOP have all been correctly connected).
PLEASE NOTE: if the panel is off, the control unit should be
in ENERGY SAVING mode; press the OK key to turn it on.
Points being among display digits show the status of
programming push-buttons: as soon as a push-button is pressed,
its relevant point turns on.
The arrows on the left of the display show the state of the start
inputs. The arrows light when the related input is closed.
The arrows on the display right side show the gate status:
• The highest arrow turns on when the gate is into its opening
phase. If it blinks, it means that the opening has been caused
by a safety device (border or obstacle detector).
• The central arrow shows that the gate is on pause.
If it blinks, it means that the time countdown for the
automatic closing has been activated.
• The lowest arrow blinks when the gate is into its closing
phase. If it blinks, it means that the closing has been caused
by a safety device (border or obstacle detector).

ENGLISH
54
6 - INITIALISING THE CONTROL
UNIT
This operation is necessary when the control unit is installed for
the first time, and is used to define the gate leaf starting order
and the direction of rotation of the two motors.
Until initialisation is performed, it is not possible to operate the
gate or program the control unit.
The initialisation procedure steps are as follows:
1. Starting initialisation
2. Selecting the superior and inferior gate leaves
3. Selecting the opening direction
4. Verifying Slave motor connection
5. Self-training the working times
WARNING:
• Ensure that the motors and accessories are connected correctly
prior to performing initialisation
• Position the gate leaves roughly at the half way points (unblock
the motors, operate the gate leaves, re-block the motors)
• Firstly, the procedure will involve short movements of the gate
leaves. In the final phase, the gate is moved through its entire
path. The operator should be positioned so as not to interfere
with the movement of the gate leaves and so as not to trip any
photocells
• Installation is automatically interrupted if no operations are
performed for one minute
• The initialisation procedure involves the loading of default
values for all programming menu parameters
Press and hold OK for approx. 2 seconds, until the message “-ini” appears. On release of the key, the message GO appears.
Pressing OK starts the procedure. The arrow keys can be used to select “ESC”, thus exiting without starting the procedure.
Starting initialisation
The control unit moves the Master motor first in one direction,
then in the other, 3 times
Exit (initialisation incomplete)
Main screen
Start
The control unit functions and times are programmed by means
of a special configuration menu, which can be accessed and
explored by using the 3 keys, , and OK, located on the side of
the control unit display.
PLEASE NOTE: Outside the configuration menu, pressing
the key activates the START command, pressing the key
activates the PEDESTRIAN START command.
In the manual, the control unit programming procedure is
represented by block diagrams, consisting of the various display
views.
The various blocks include symbols showing the user the keys to
be pressed to navigate around the menu.
When a time is written to the side of the symbol, this means the
key should be pressed and held for the length of time indicated.
The following table describes the functions of the push-buttons:
Press and release the push-button OK
Keep pressed the push-button OK for 2 seconds
elease the push-button OK
Press and release the push-button
Press and release the push-button

ENGLISH
55
the gate leaf in motion
SUP the gate leaf in motion is the leaf that should open first
inF the gate leaf in motion is the leaf that should open second
PLEASE NOTE: if installation envisages one motor only, select SUP
Select this parameter depending on the direction of opening of gate leaf 1
AP1 the gate leaf is opening
Ch1 the gate leaf is closing
Having selected this parameter, the control unit moves the SLAVE
motor
1If the control unit detects the SLAVE motor, the display shows AP2
Select this parameter depending on the direction of opening of gate leaf 2
AP2 the gate leaf is opening
Ch2 the gate leaf is closing
Having selected the parameter, press OK to move to the next phase.
If the display shows Er93, this means the SLAVE motor is connected
incorrectly.
Check the SLAVE motor connection and repeat the initialisation
procedure
2If the control unit does NOT detect the SLAVE motor, the display
shows SinG
If the installation envisages only one motor, press OK to move to the
next phase.
If the installation envisages two motors, select the doP menu option and
press OK.
The display will show Er94 to indicate that the SLAVE motor is not
connected, or is connected incorrectly.
Check the SLAVE motor connection and repeat the initialisation
procedure
3If the control unit does not detect a photocell on the PHOTO input,
the display shows Ft.no
If the installation does not envisage the use of a photocell, select Ft.no
and press OK to move to the next phase.
The photocell will be automatically disabled.
If installation envisages the use of a photocell, select Ft.Si and press
OK. The display will show Er91 to indicate that the photocell is not
connected, or is connected incorrectly.
Check the photocell connection and repeat the procedure.
4If the control unit detects a photocell connected correctly to the
PHOTO input, it automatically switches to the working time
self-training phase.
Press OK to start the self-training phase.
Select ESC and press OK to exit the menu without performing the time
self-training phase.
Please note: in the case of exiting without self-training, it will not
be possible to operate the gate.
In any case, it will be possible to perform self-training in a separate
phase and program the remainder of the control unit functions, using
the specific menu.

ENGLISH
56
UNIT SETTINGS
Once initialisation is performed (even without time self-training), it
will be possible to access the various control unit functions,
including initialisation itself.
1. Press and hold the OK key until the display shows the menu
desired
2. elease the OK key: the display will show the first item in the
sub-menu
-CFG apid configuration
-PrG Programming the control unit (full menu)
-Cnt Cycle counter
-APP Self-training the working times
-dEF Loading the default parameters
-ini Control unit initialisation
apid configuration is a menu allowing the main control unit
parameters to be programmed with a few operations.
It is essential the initialisation procedure has already been
performed (even without time self-training) in order to
perform rapid configuration.
1. Press and hold the OK key until the display shows the -CFG
menu
2. elease the OK key: the display will show the first item in the
Pot menu.
Pot. Power adjustment
SEnS Obstacle sensor adjustment
LoG. Operation logic
FinE Exit the menu

ENGLISH
57
This rapid configuration menu option allows the motor power to
be adjusted. The value displayed is the value currently set. Using
the and keys, select the value to be set and press OK to
confirm and continue.
30 ÷ 100 Values from 30 (minimum) to 100 (maximum).
Equal values for both motors
PErS Customised configuration: if the display shows
PErS, this means the two motors have different
power values set using the Pot1 and Pot2 options
in the control unit programming menu.
Selecting the PErS options exits the menu,
maintaining the previously set values.
8.2 - OBSTACLE SENSOR ADJUSTMENT
The PD12 control unit has a sophisticated system allowing detection of whether gate movement is impeded by an obstacle.
This system is based on measurement of the current absorbed by the motor: an unexpected increase in current absorption indicates the
presence of an obstacle. the obstacle sensor is also used to recognise the arrest points.
Detection of an obstacle during normal movement of the gate results in brief inversion of motion in order to free the obstacle. The gate is
stopped when one of the following conditions is present:
- During slowing
- During the first work cycle after accessing the programming menu
- After having powered-up the control unit
This menu option is used to adjust the motor current value that trips the obstacle sensor.
The value displayed is the value currently set. Using the and keys, select the value to be set and press OK to confirm and continue.
The possible options are:
1.0 ÷ 3.5 Values from 1.0 to 3.5 Amperes: values common to both
motors. The minimum value corresponds to maximum
obstacle sensor sensitivity, and vice-versa.
Based on the value selected, the control unit also calculates
the acceleration and deceleration rate and the start thrust
function.
PErS Customised configuration: if the display shows PErS, this
means the two motors have different values set using the
SEn1 and SEn2 options in the control unit programming
menu.
Selecting the PErS options exits the menu, maintaining the
previously set values.
Please note: if time self-training has been performed during
initialisation, the control unit has also performed automatic strain
recognition and has automatically set the sensitivity value.
If, on the other hand, self-training has not been performed, the
pre-set value is the default.

ENGLISH
58
This rapid configuration option is used to define the start command action (from the terminal board, from the remote control or from the
keypad)
The possible options are:
P - P Step Logic - the Start command results in opening, stop, closure, stop, in sequence.
AUto Automatic logic - the Start command is used to open the gate.
- During opening, other Start commands are ignored. Closure is automatic after a programmable pause time
- During the pause, a Start command restarts the pause time count from the beginning.
- During closure, a Start command immediately reopens the gate.
PLEASE NOTE: If automatic logic is selected, the pause time adjustment option is accessed (up to 20 minutes,
the default value is 15 seconds).
PErS Customised logic: the Start command acts in accordance with the programming of the various Programming Menu parameters.
Selecting the PErS options exits the menu, maintaining the previously set values.
8.4 - EXITING RAPID CONFIGURATION
This menu closes programming (both predefined and customised), saving the modified data in the memory
PLEASE NOTE: if the menu is exited due to time out (after 1 minute without pressing any keys) the data set is not stored.
This manual suits for next models
2
Table of contents
Other V2 Controllers manuals
Popular Controllers manuals by other brands

Swagelok
Swagelok KFB Series Maintenance instructions

Danfoss
Danfoss ERC 112D VSC user guide

Siegenia
Siegenia Drive Connect Box Installation and operating instructions

Beam Labs
Beam Labs Pixelator Plus product manual

KIPI
KIPI ecoMAX860P3-C Installation and operating manual

Salus
Salus PCSol 201 Installation and operation manual