V2 AYROS-24V series User manual

ZIS334
IL 393-1
EDIZ. 22/08/2018
I
ATTUATORE ELETTROMECCANICO
IRREVERSIBILE 24V PER CANCELLI
SCORREVOLI FINO A 1000 KG
DI PESO
GB
24V ELECTRO-MECHANICAL
IRREVERSIBLE RACK ACTUATOR
FOR SLIDING GATES UP TO 1000 KG
F
OPERATEUR ELECTROMECANIQUE
IRREVERSIBLE 24V POUR PORTAILS
COULISSANTS JUSQU’A 1000 KG
DE POIDS
E
MOTOR ELECTROMECANICO
IRREVERSIBLES 24V PARA PUERTAS
CORREDERAS HASTA 1000 KG
DE PESO
AYROS-24V

200 mm
343 mm
178 mm
226 mm
334 mm
3 mm 328 mm
200 mm
343 mm
160 mm
74 mm
50 mm
100 mm
128 mm
206 mm
283 mm

ENGLISH
- 29 -
INDEX
1 - GENERAL SAFETY INFORMATION ........................................................................................................................
1.1 - PRELIMINARY CHECKS AND IDENTIFICATION OF THE TYPE TO BE USED..........................................................
1.2 - TECHNICAL ASSISTANCE SERVICE...................................................................................................................
1.3 - EU DECLARATION OF CONFORMITY ...............................................................................................................
2 - TECHNICAL DATA ..................................................................................................................................................
3 - INSTALLATION OF THE MOTOR............................................................................................................................
3.1 - INSTALLATION OF THE MOTOR .......................................................................................................................
3.2 - MOUNTING THE RACK ...................................................................................................................................
3.3 - FIXING OF THE MOTOR...................................................................................................................................
3.4 - INSTALLING THE MAGNETIC LIMIT SWITCHES .................................................................................................
3.5 - MOTOR OVERRIDING SYSTEM ........................................................................................................................
3.6 - INSTALLATION LAYOUT ...................................................................................................................................
4 - CONTROL UNIT......................................................................................................................................................
4.1 - POWER SUPPLY...............................................................................................................................................
4.2 - BATTERY POWER ............................................................................................................................................
4.3 - ACTIVATION INPUTS........................................................................................................................................
4.4 - STOP...............................................................................................................................................................
4.5 - CONNECTING PHOTOCELLS............................................................................................................................
4.6 - CONNECTING SAFETY RIBBONS......................................................................................................................
4.7 - LOW VOLTAGE LIGHT OUTPUT........................................................................................................................
4.8 - COURTESY LIGHTS..........................................................................................................................................
4.9 - EXTERNAL AERIAL...........................................................................................................................................
4.10 - PLUG IN RECEIVER ........................................................................................................................................
4.11 - ADI INTERFACE .............................................................................................................................................
4.12 - ELECTRICAL CONNECTION............................................................................................................................
5 - CONTROL PANEL ...................................................................................................................................................
5.1 - DISPLAY ..........................................................................................................................................................
5.2 - USE OF THE KEYS FOR PROGRAMMING..........................................................................................................
6 - ACCESSING THE CONTROL UNIT SETTINGS.........................................................................................................
7 - QUICK CONFIGURATION.......................................................................................................................................
8 - LOADING THE DEFAULT PARAMETERS ................................................................................................................
9 - INSTALLATION MENU............................................................................................................................................
9.1 - AUTOMATIC LEARNING OF THE RUN LIMITS ...................................................................................................
9.2 - MANUAL HANDLING ......................................................................................................................................
10 - EMERGENCY DEAD MAN OPERATION...............................................................................................................
11 - READING OF CYCLE COUNTER ...........................................................................................................................
11.1 - SIGNAL OF SERVICE REQUIRED .....................................................................................................................
12 - PROGRAMMING THE CONTROL UNIT................................................................................................................
13 - OPERATION DEFECTS ..........................................................................................................................................
14 - TESTING AND START-UP......................................................................................................................................
15 - MAINTENANCE....................................................................................................................................................
16 - DISPOSAL OF THE PRODUCT..............................................................................................................................
30
31
32
32
33
34
34
35
35
36
37
38
40
40
40
40
40
40
41
41
41
42
42
42
42
44
44
44
45
45
45
46
46
46
47
47
47
48
53
54
54
54

ENGLISH
- 30 -
AUTOMATION DEVICE
INSTALLERS MANUAL
1 - GENERAL SAFETY INFORMATION
mPrior to proceeding with installation, it is essential the
instructions be read in full, since they contain important
information regarding safety, installation, use and
maintenance.
AUTOMATION MUST BE IMPLEMENTED IN COMPLIANCE WITH
THE EUROPEAN REGULATIONS IN FORCE:
EN 60204-1, EN 12445, EN 12453, EN 13241-1, EN 12635
• The installer must provide for a device (es. magnetotermical
switch) ensuring the omnipolar sectioning of the equipment
from the power supply. The standards require a separation of
the contacts of at least 3 mm in each pole (EN 60335-1).
• The plastic case has an IP44 insulation; to connect flexible or
rigid pipes, use pipefittings having the same insulation level.
• Installation requires mechanical and electrical skills, therefore it
shall be carried out by qualified personnel only, who can issue
the Compliance Certificate concerning the whole installation
(Machine Directive 2006/42/CEE, Annex IIA).
• Also the automation upstream electric system shall comply with
the laws and rules in force and be carried out workmanlike.
• We recommend to make use of an emergency button, to be
installed by the automation (connected to the control unit
STOP input) so that the gate may be immediately stopped in
case of danger.
• For correct installation of the system, we recommend following
the instructions issued by UNAC very carefully
• This instruction manual is only for qualified technicians, who
specialize in installations and automations.
• The contents of this instruction manual do not concern the end
user.
• Every programming and/or every maintenance service should
be done only by qualified technicians.
• Anything not expressly described in these instructions is
prohibited; unforeseen uses may be a source of danger to
people and property.
• Do not install the product in explosive environments and
atmospheres: the presence of inflammable gases or fumes is a
serious safety hazard.
• Do not make any modifications to any part of the automation
device, or the accessories connected to it, unless described in
this manual.
• Any other modifications will void the warranty on the product.
• The installation steps should be conducted so as to avoid rainy
weather, which can expose electronic circuits to dangerous
water seepage.
• All operations requiring the casing of the device to opened
should be performed with the control unit disconnected from
the electricity supply and with a warning notice displayed, for
example: ”CAUTION, MAINTENANCE IN PROGRESS”.
• Avoid exposing the device close to sources of heat and flame.
• In the event of interventions on automatic or differential
breakers or fuses, it is essential that faults be identified and
resolved prior to resetting. In the case of faults that cannot
be resolved using the information to be found in this manual,
consult the V2 customer assistance service.
• V2 declines all responsibility for failure to comply with good
construction practice standards in addition to structural
deformation of the gate that might occur during use.
• V2 reserves the right to make modifications to the product
without prior warning.
• Installation/maintenance personnel should wear individual
protection devices (IPDs), such as overalls, safety helmets, boots
and gloves.
• The ambient operating temperature should be that indicated in
the technical characteristics table.
• The automation device should be shut down immediately in
the event of any anomalous or hazardous situation; the fault
or malfunction should be immediately reported to the person
responsible.
• All safety and hazard warnings on the machinery and
equipment should be complied with.
• Electromechanical actuators for gates are not intended to be
used by people (including children) with diminished physical,
sensory or mental capacity, or lacking in experience or
knowledge, unless they are under supervision or have been
instructed in use of the actuator by a person responsible for
safety.
V2 has the right to modify the product without previous
notice; it also declines any responsibility to damage or
injury to people or things caused by improper use or wrong
installation.

ENGLISH
- 31 -
1.1 - PRELIMINARY CHECKS AND IDENTIFICATION OF THE TYPE TO BE USED
The automation device should not be used until installation, as specified in “Testing and start-up”, has been performed.
It should be remembered that the device does not compensate for defects caused by improper installation, or poor maintenance, thus, prior
to proceeding with installation, ensure that the structure is suitable and meets current standards and, if necessary, perform any structural
modifications aimed at the implementation of safety gaps and the protection or segregation of all crushing, shearing and transit zones, and
verify that:
• The gate has no friction points, either during closing or opening.
• The gate must be equipped with mechanical stoppers.
• The gate is well balanced, i.e. there is no tendency to move spontaneously when stopped in any position.
• The position identified for fixing the motor reducer allows easy and safe manual manoeuvring, compatible with the size of the motor
reducer itself.
• The support on which the automation device will be fixed is solid and durable.
• The mains power supply to which the automation device is connected has a dedicated safety earthing system and differential breaker
with tripping current less than or equal to 30 mA (the breaker gap distance should be greater than or equal to 3 mm).
Warning: The minimum safety level depends on the type of use; please refer to the following outline:
CLOSURE USE TYPE
TYPE OF ACTIVATION
COMMANDS
GROUP 1
Informed people
(use in private area)
GROUP 2
Informed people
(use in public area)
GROUP 3
Informed people
(unlimited use)
Man-present command A B Not possible
Remote control and closure in
view (e.g. infrared)
C or E C or E C and D or E
Remote control and closure not
in view (e.g. radio)
C or E C and D or E C and D or E
Automatic control
(e.g. timed closure control)
C and D or E C and D or E C and D or E
GROUP 1 -Only a limited number of people are authorised for use, and closure is not in a public area. Examples of this type are gates inside
business premises, where the sole users are employees, or a part of them who have been suitably informed.
GROUP 2 - Only a limited number of people are authorised for use, but in this case, closure is in a public area. An example of this may be a
company gate that accesses onto a public street, and which is only used by employees.
GROUP 3 - Anyone can use the automated closure, which is thus located on public land. For example the access gate to a supermarket or
an office, or a hospital.
PROTECTION A - Closure is activated by means of a control button with the person present, i.e. with maintained action.
PROTECTION B - With the person present, closure is activated by a command controlled by means of a key-switch or the like, in order to
prevent use by unauthorised persons.
PROTECTION C - Restricts the force of the leaf of the door or gate. I.e., in the case of the gate striking an obstacle, the impact force must
fall within a curve established by the regulations.
PROTECTION D - Devices, such as photocells, capable of detecting the presence of people or obstacles. They may be active on just one side
or on both sides of the door or gate.
PROTECTION E - Sensitive devices, such as footboards or immaterial barriers, capable of detecting the presence of a person, and installed in
such a way that the latter cannot be struck in any way by a moving leaf or panel. These devices should be active within the entire “danger
zone” of the gate. The Machinery Directive defines “Danger Zone” as any zone surrounding and/or near machinery where the presence of
an exposed person constitutes a risk to the health and safety of that person.
The risk analysis should take into consideration all danger zones for the automation device, which should be appropriately
protected and marked.
In a clearly visible area, apply a sign with information identifying the motorised door or gate.
The installer should provide the user with all the information relating to automatic operation, emergency opening and
maintenance of the motorised door or gate.

ENGLISH
- 32 -
1.2 - TECHNICAL ASSISTANCE SERVICE
For any installation problem please contact our Customer Service
at the number +39-0172.812411 operating Monday to Friday
from 8:30 to 12:30 and from 14:00 to 18:00.
1.3 - EU DECLARATION OF CONFORMITY
AND DECLARATION OF INCORPORATION OF
PARTLY COMPLETED MACHINE
Declaration in accordance with Directives: 2014/35/UE (LVD);
2014/30/UE (EMC); 2006/42/CE (MD) ANNEX II, PART B
The manufacturer V2 S.p.A., headquarters in Corso Principi di
Piemonte 65, 12035, Racconigi (CN), Italy
Under its sole responsibility hereby declares that:
the partly completed machinery model(s):
AYROS500D-24V-F
AYROS600D-24V
AYROS1000D-24V
Description: electromechanical actuator for sliding gates
• is intended to be installed on sliding gates, to create a machine
according to the provisions of the Directive 2006/42/EC.
The machinery must not be put into service until the final
machinery into which it has to be incorporated has been
declared in conformity with the provisions of the Directive
2006/42/EC (annex II-A).
• is compliant with the applicable essential safety requirements
of the following Directives:
Machinery Directive 2006/42/EC (annex I, chapter 1)
Low Voltage Directive 2014/35/EU
Electromagnetic Compatibility Directive 2014/30/EU
Directive ROHS2 2011/65/CE
The relevant technical documentation is available at the national
authorities’ request after justifiable request to:
V2 S.p.A.
Corso Principi di Piemonte 65, 12035, Racconigi (CN), Italy
The person empowered to draw up the declaration and to provide
the technical documentation:
Antonio Livio Costamagna
Legal representative of V2 S.p.A.
Racconigi, il 01/06/2015
2 - TECHNICAL DATA
AYROS 500D
24V-F
AYROS
600D-24V
AYROS
1000D-24V
AYROS 500D
24V-F-120V
AYROS 600D
24V-120V
AYROS 1000D
24V-120V
Gate maximum weight 500 Kg 600 Kg 1000 Kg 500 Kg 600 Kg 1000 Kg
Power supply 230 VAC
50 Hz
230 VAC
50 Hz
230 VAC
50 Hz
120 VAC
50-60 Hz
120 VAC
50-60 Hz
120 VAC
50-60 Hz
Maximum power 550 W 400 W 550 W 550 W 400 W 550 W
Full load current 2,5 A 2 A 2,5 A 3,5 A 3 A 3,5 A
Gate maximum speed 0,25 - 0,4
(@200N -
unloaded)
0,14 - 0,26
(@300N -
unloaded)
0,16 - 0,22
(@450N -
unloaded)
0,25 - 0,4
(@200N -
unloaded)
0,14 - 0,26
(@300N -
unloaded)
0,16 - 0,22
(@450N -
unloaded)
Maximum thrust 400 N 600 N 850 N 400 N 600 N 850 N
Duty cicle 60 % 60 % 60 % 60 % 60 % 60 %
Pinion M4 - Z18 M4 - Z18 M4 - Z18 M4 - Z18 M4 - Z18 M4 - Z18
Operation temperature -20 ÷ +55 °C -20 ÷ +55 °C -20 ÷ +55 °C -20 ÷ +55 °C -20 ÷ +55 °C -20 ÷ +55 °C
Weight 18 Kg 16 Kg 18 Kg 18 Kg 16 Kg 18 Kg
Protection IP44 IP44 IP44 IP44 IP44 IP44
Maximum load on 24 VAC
attachments
7 W 7 W 7 W 7 W 7 W 7 W
Protection fuses 2,5 A 2,5 A 2,5 A 4 A 4 A 4 A

ENGLISH
- 33 -
WARNING: The following chart indicates the recommended maximum speed that can be programmed (via the Pot
Parameter) depending on door weight
mWARNING – DO NOT EXCEED THE INDICATED MAXIMUM SPEED
10,00
15,00
20,00
25,00
30,00
35,00
40,00
50 100 150 200 250 300 350 400 450 500
10,00
12,00
14,00
16,00
18,00
20,00
22,00
24,00
26,00
100 150 200 250 300 400 450 500 550 600
10,00
12,00
14,00
16,00
18,00
20,00
22,00
24,00
26,00
100 200 300 400 500 600 700 800 900 1000
AYROS500-24V-F
AYROS600-24V
AYROS1000-24V
Maximum speed [cm/s]Maximum speed [cm/s]Maximum speed [cm/s]
Gate weight [kg]
Gate weight [kg]
Gate weight [kg]

ENGLISH
- 34 -
50 mm200 mm
20 mm343 mm
60mm
10cm
30cm
10cm
3 - INSTALLATION OF THE MOTOR
3.1 - POSITIONING OF THE MOTOR
To fix AYROS, follow the instructions below:
1. use the measurements indicated in the drawing for the
foundations
2. Arrange for one or two pipes for the passage of electric cables
3. Assemble the 4 clamps on the anchoring plate and fix them
with the 4 bolts issued with the motor
4. Pour the concrete and position the anchoring plate
mWARNING: check that the plate be on a perfectly
levelled surface and parallel to the gate
5. Wait for the complete setting of the concrete
6. Unscrew the bolts fixing the base to the clamps and put the
motor on the plate
7. Adjust the 4 grains to make the motor be perfectly levelled
8. Control that the motor is perfectly parallel to the gate, then
insert the 4 washers Rand lightly screw the 4 bolts D
m WARNING: put the washer G into the hole for the
passing of the cables as shown in the picture. Pierce the
washer to let the cable to be connected to the control
unit pass, paying attention to the dimensions in order to
avoid the entrance of insects and other small animals.

ENGLISH
- 35 -
97 mm
2 mm
>5 mm
D
3.2 - MOUNTING THE RACK
1. Release the motor and turn the gate completely open.
2. Fix all the rack elements to the gate, making sure that
they stand at the same height than the motor pinion.
The rack MUST BE positioned 1 or 2 mm over the
pinion of the motor all the gate length.
3.3 - FIXING OF THE MOTOR
Check the following points:
1. the motor must be on a levelled surface and perfectly
parallel to the gate
2. the distance between pinion and rack must be
1 or 2 mm. If needed, adjust the 4 grains
3. the rack must be trued up with the pinion of the motor
4. the minimum distance between the maximum overall of
the gate and the case of the pinion of the motor must
be of at least 5 mm
5. Check the above indicated conditions and proceed
fixing the 4 bolts Danchoring the motor to the plate.

ENGLISH
- 36 -
Max 38 mm
102 mm
DXSX
DXSX
3.4 - INSTALLING THE MAGNETIC LIMIT
SWITCHES
mWARNING: For your safety, it is necessary that the gate
is equipped with mechanical stoppers.
If the gate is not equipped with these stoppers, an erratic
movement past the range limit may cause the gate to fall.
Install the supplied magnet holder on the rack in a way that, in
the opening and closing limit positions, the magnet be positioned
next to the magnetic sensor behind the hood (as near as possible
to the hood).
The supplied magnets have been colored differently in order to be
distinguished from each other:
BLUE MAGNET = RIGHT LIMIT SWITCH (DX)
RED MAGNET = LEFT LIMIT SWITCH (SX)
The type of limit switch (RIGHT/LEFT) depends on the position
of the limit switch towards the motor, independently from the
opening sense.
mWARNING: Once checked the proper working of the
system, we suggest to weld the end-of-stroke brackets on
the rack.

ENGLISH
- 37 -
L K J
3.5 - MOTOR OVERRIDING SYSTEM
In case of absence of current, the gate can be released by
operating on the motor:
1. Open the hatch of the lock Jin front of the motor
2. Insert the key Kin the lock and turn clockwise to open
the hatch of the release on the side
3. Insert the key Linto the hole and turn clockwise until
reached the limit switch
4. At this point you can manually move the gate
To restore the automation, proceed as follows:
1. Bring the gate to the fully closed position
2. turn the key Lanticlockwise until reached the limit
switch, then draw it out
3. turn the key Kanticlockwise closing the hatch of the
lock, then draw it out
4. Close the lock with the hatch J

ENGLISH
- 38 -
1 3 E
5
4
A
B
F
D
2
C
3.6 - INSTALLATION LAYOUT
LENGTH OF THE CABLE < 10 metres from 10 to 20 metres from 20 to 30 metres
Power supply 230V/120V 3G x 1,5 mm23G x 1,5 mm23G x 2,5 mm2
Photocells (TX) 2 x 0,5 mm22 x 0,5 mm22 x 0,5 mm2
Key switch 4 x 0,5 mm24 x 0,5 mm24 x 0,5 mm2
Photocells (RX) 2 x 0,5 mm22 x 0,5 mm22 x 0,5 mm2
Flashing light 2 x 1,5 mm22 x 1,5 mm22 x 1,5 mm2
Antenna (integrated into the flashing light) RG174 RG174 RG174
A
B
C
D
E
F
1
2
3
4
5
Key switch
Pillar photocells
Pillar-mounted digital radio switch
Safety edges
WES-ADI module (via radio management of edges)
WES sensors
Motor
Transmitter
Receiving module
Photocells
Flashing light
COMPONENTS ADDITIONAL ACCESSORIES

ENGLISH
- 39 -
4 - CONTROL UNIT
PD14 is provided with a display that, not only makes
programming simple, but also allows a continuous monitoring of
the input statuses; in addition, thanks to a menu structure, the
working schedule and the operation logic can be set easily.
In compliance with the European standards concerning
electrical safety and electromagnetic compatibility
(EN 60335-1, EN 50081-1 and EN 50082-1) it has been
equipped with the low voltage circuit total electric insulation
(motors included) from the network voltage.
Other characteristics:
• Power supply protected from short circuits within the controller,
on the motors and on the connected accessories.
• Adjustment of the power by partializing the current.
• Detecting obstacles by monitoring the current on the motors
(current sensing probe and encoder)
• Automatic learning of the limit switch position
• Tests for safety devices (photocells, safety ribbons and mosfet)
before each opening.
• Deactivation of safety inputs through the configuration menu:
no jumper is required for terminals concerning safety devices
that have not been installed, yet. You will only need to disable
this function from its relevant menu.
• The device can operate without mains power, by using the
optional battery pack (code 161212).
• Low voltage output that can be used for a signal light or a
24 V flashing light.
• Auxiliary relay with programmable logic for courtesy light,
flashing light or other use.
• ENERGY SAVING FUNCTION
• Synchronized operation of two motors using the SYNCRO
optional module (compatible with the control units PD14 from
version 1.1 onward)
mWARNING: Installation of control unit and safety
devices must be carried out with power disconnected.
4.1 - POWER SUPPLY
The control unit must be fed by a 230V-50Hz (120V - 50/60Hz
for the model 120V) electric line, protected by a differential
magnetothermal switch complying with the law provisions in
force.
Connect the power supply wires to terminals Land Non the
board located next to the transformer.
Connect the earth cable to terminal
4.2 - BATTERY POWER
In the case of an electricity black-out, the device may be powered
using a battery pack (accessory code 161212).
The battery pack should be housed in the specific seating, as
shown in the figure.
Connect the battery pack connecter to the BATTERY terminals on
the control unit.

ENGLISH
- 40 -
4.3 - ACTIVATION INPUTS
PD14 control unit is equipped with two activation inputs (START
and START P.), whose operation depends on the programmed
operation modes (see Strt item of programming menu):
mWARNING: If you use maintained command devices
(magnetic loop detectors, timers, presence detectors, etc.)
clock mode must be used (parameter Strt = oroL).
Standard mode
START = START (a command will cause the complete
opening of the gate)
START P. = PEDESTRIAN START (a command will cause the
partial opening of the gate)
Open/Close command
START = OPENING (always controls the gate opening)
START P. = CLOSING (always controls the gate closing)
This is an impulse command, that is to say that an impulse will
cause the complete gate opening or closing.
Manned operation
START = OPENING (always controls the gate opening)
START P. = CLOSING (always controls the gate closing)
This is a monostable command, that is to say, the gate will be
opened or closed as long as the contact is closed and it will
immediately stop as the contact is open
Timer mode
This feature allows you to program time slots during the day
for the gate to be open by using an external timer or other
maintained command devices (e.g. magnetic loop detectors or
presence detectors).
START = START (a command will cause the complete opening of
the gate)
START P. = PEDESTRIAN START (a command will cause the partial
opening of the gate)
The gate stays open (completely or partially) while the contact is
closed on input; as soon as the contact is open the pause time
count down will start, after which the gate will be closed again.
ATTENTION: Automatic closing must be enabled
NOTE: If the parameter P.APP = 0the timer connected to
START P. does not cause the opening, but can inhibit the
automatic closing at preset times.
In all modes, inputs must be connected to devices having normally
open contacts.
Connect cables of device controlling the START input between
terminals J1 (START) and J4 (COM) of the control unit.
Connect cables of device controlling the START P. input between
terminals J2 (START P.) and J4 (COM) of the control unit.
The START input function can also be activated by pressing hkey
(outside the programming menu) or by means of a remote
control stored on channel 1 of MR receiver.
The START P. input function can also be activated by pressing i
key (outside the programming menu) or by means of a remote
control stored on channel 2 of MR receiver.
4.4 - STOP
For a better safety, you can fit a stop switch that will cause the
immediate gate stop when activated. This switch must have a
normally close contact that will get open in case of operation.
In case the stop switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a START command.
Connect the stop switch cables between terminal J3 (STOP) and
J4 (COM) of the control unit.
The STOP switch function can be activated by means of a remote
control stored on channel 3 of MR receiver.
mPHOTOCELLS - REMARKS
• The control unit powers the photocells at a nominal voltage of
24 Vdc, with an electronic fuse that breaks the current in the
case of an overload.
• If the transmitter power supply is connected to terminals E3 (+)
and E2 (-), the control unit can perform the photocell operation
test prior to starting gate opening.
• The photocells on the interior side should be installed so as to
completely cover the gate opening area.
• If several pairs of photocells are installed on the same side of
the gate, the receiver N.C. outputs should be connected in
series.
• The photocells are not powered when the control unit is in
ENERGY SAVING mode.
4.5 - CONNECTING PHOTOCELLS
The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:
Photocell 1
Photocells installed on the gate inner side, which are active both
during the opening and the closing phase. When photocells 1
operate, the control unit stops the gate; as soon as the photocell
beam is free, the control unit will open the gate completely.
Photocell 2
Photocells installed on the external gate side and which are active
during the closing phase only. When photocells 2 operate, the
control unit opens the gate immediately, without waiting for
release.
• Connect power supply cables of photocells transmitter
between terminals E3 (+) and E2 (-) of the control unit.
• Connect power supply cables of photocells receiver between
terminals E1 (+) and E2 (-) of the control unit.
• Connect receiver output of photocells 1 between terminals
J5 (PHOTO1) and J9 (COM) of the control unit and receiver
output of photocells 2 between terminals J6 (PHOTO2) and
J9 (COM) of the control unit.
Use outputs having normally closed contact.

ENGLISH
- 41 -
4.7 - LOW VOLTAGE LIGHT OUTPUT
The PD14 control unit has a 24 VDC output that allows
connection of a maximum load of 3W.
This output can be used to connect a warning light, indicating the
status of the gate, or for a low voltage flashing light.
Connect the low voltage signal light or flashing light wires to
terminals E4 (+) and E5 (-).
CAUTION: Pay attention to the polarity of the connected
device if necessary.
4.8 - COURTESY LIGHTS
Thanks to the output COURTESY LIGHT the control unit allows
the connection of an electric appliance (e.g. courtesy light or
garden lights), controlled automatically or by means of the special
transmitter key.
The courtesy light terminals can be alternatively used for a
230V/120V flashing light with integrated flasher.
The output COURTESY LIGHT is a simple N.O. contact with no
power supply.
Connect the cables to terminals B1 and B2.
4.9 - EXTERNAL AERIAL
We suggest to use the external aerial (model: ANS433) in order to
guarantee the maximal range.
Connect the antenna hot pole to terminal A2 (ANT) of the
control unit and the shield to terminal A1 (ANT-).
4.10 - PLUG IN RECEIVER
PD14 control unit is suitable for plugging in a MR receiver having
a high-sensitivity super-heterodyne architecture.
mWARNING: Pay attention to the way you connect the
removable modules.
MR module receiver is provided with 4 channels and each of
them is suitable for a command of PD14 control unit:
• CHANNEL 1 gSTART
• CHANNEL 2 gPEDESTRIAN START
• CHANNEL 3 gSTOP
• CHANNEL 4 gCOURTESY LIGHT
NOTE: Before programming 4 channels and function logics
read carefully the instructions of MR.
mSAFETY RIBBONS - REMARKS
• If several edges, with normally closed contacts, are used, the
outputs should be connected in series.
• If several conductive rubber edges are used, the outputs should
be connected in cascade, and only the final edge should be
terminated on the nominal resistance.
• Active edges connected to the accessory power supply are
inactive when the control unit switches to ENERGY SAVING
mode.
• To meet the requirements of EN12978, it is necessary to install
conductive rubber sensitive edges; contact normally closed
sensitive edges should have a control unit that constantly
verifies their correct operation. If control units with the option
to conduct testing by interrupting the power are used, connect
the control unit power cables between terminals E3 (+) and
E2 (-) on the PD14.
Otherwise, connect them between terminals E1 (+) and E2 (-).
Testing the edges should be activated by means of the Co.tE
menu.
4.6 - CONNECTING SAFETY RIBBONS
The control unit considers two kinds of safety ribbons, depending
on the terminal to which they are connected:
Type 1 (fixed)
They are mounted on walls or on other fixed obstacles that are
approached by the gate doors during the opening phase.
When type 1 safety ribbons operate during the gate opening
phase, the control unit will close the doors for 3 seconds, then it
stands still; when type 1 safety ribbons operate during the gate
closing phase, the control unit will stand still immediately. The
direction of the gate at next command of START or PEDESTRIAN
START depends upon the parameter STOP (it inverts or continues
the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
Type 2 (mobile)
They are mounted to the door ends.
When type 2 safety ribbons operate during the gate opening
phase, the control unit will stand still immediately; when type 2
safety ribbons operate during the gate closing, the control unit
will open the doors for 3 seconds, then it will stand still. The
direction of the gate at next command of START or PEDESTRIAN
START depends upon the parameter STOP (it inverts or continues
the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2
kohm nominal resistance.
Connect type 1 safety ribbons cables between terminals
J7 (EDGE1) and J9 (COM) of the control unit.
Connect type 2 safety ribbons cables between terminals
J8 (EDGE2) and J9 (COM) of the control unit.

ENGLISH
- 42 -
4.12 - ELECTRICAL CONNECTION
J1 START - Open command for connecting
traditional devices with N.O. contact
mWARNING: If you use maintained
command devices (magnetic loop detectors,
timers, presence detectors, etc.) clock mode
must be used (parameter Strt = oroL).
J2 START P. - Pedestrian open command for
connecting traditional devices with N.O. contact
mWARNING: If you use maintained
command devices (magnetic loop detectors,
timers, presence detectors, etc.) clock mode
must be used (parameter Strt = oroL).
J3 STOP command. N.C. contact
J4 Common (-)
J5 Photocell 1. N.C. contact
J6 Photocell 2. N.C. contact
J7 Type 1 edges. N.C. contact
J8 Type 2 edges. N.C. contact
J9 Accessories common (-)
E1 +24Vdc supply for photocells and other
accessories
E2 Accessory power common (-)
E3 +24Vdc supply - photocell/optical edge TX for
functional Test.
Connect power supply cables of photocells
transmitter between terminals E2 and E3
E4 - E5 Warning light or flashing light (24V)
A1 Antenna shield
A2 Antenna
B1 - B2 Courtesy or flashing lights (230V/120V)
LPower phase 230V/120V
NNeutral 230V/120V
BATTERY Battery pack (code 161212)
RECEIVER Connector for MRx receiver
ADI ADI Module interface
OVERLOAD It shows that there is an overload on accessories
power supply
MAINS It shows that the control unit is power supplied
MMotor
LIMIT
SENSOR
Limit sensor
ENCODER Encoder
24 Vdc
POWER
SUPPLY
Control unit power supply (+24 VDC)
4.11 - ADI INTERFACE
The ADI (Additional Devices Interface) interface of the control unit
PD14 allows the connection to V2 optional modules.
Refer to V2 catalogue or to the technical sheets to see which
optional modules with ADI interface are available for this control
unit.
mWARNING: Please read the instructions of each single
module to install the optional modules.
For some devices, it is possible to configure the mode for
interfacing with the control unit; in addition, it is necessary to
enable the interface so that the control unit can process the
signals arriving from the ADI device.
Please refer to the i.Adi programming menu to enable the ADI
interface and access the device configuration menu.
ADI devices use the display of the control unit to issue alarms or
display the configuration of the control unit.
The device connected to the Adi interface is able to signal to the
control unit three alarm signals, which are displayed on the
control unit display as follows:
• PHOTOCELL ALARMS - the upper segment comes on: the gate
stops moving, when the alarm stops opening restarts.
• EDGE ALARM - the lower segment comes on: inverts motion of
the gate for 3 seconds.
• STOP ALARM - both segments start flashing: the gate stops
and cannot restart until the alarm stops.
• SLAVE - segment steadily lit: it is used by the optional module
SYNCRO to indicate that the control unit is configured as
SLAVE.
PLEASE NOTE: the highlighted connections are factory
pre-wired
mCAUTION: Never reverse the connectors
PHOTOCELL ALARM
STOP ALARM
EDGE ALARM
SLAVE

ENGLISH
- 43 -
J9J8J7J6J5J4J3J2J1 B1 B2
E5E3 E4E2E1
RECEIVER
BATTERY
+
LIMIT
SENSOR
ENCODER
START
START P.
STOP
COM
PHOTO1
PHOTO2
EDGE1
EDGE2
COM
+Vdc (Functional Test)
COM
+Vdc
24 Vdc
POWER SUPPLY
ACCESSORIES
M
24Vdc
LAMP
24Vdc - 3W
COURTESY LIGHT
CONTACT
ANTENNA
A1 A2
OVERLOAD
L N
F1 = 2,5A (230V)
4A (120V)
MAINS

ENGLISH
- 44 -
5 - CONTROL PANEL
5.1 - DISPLAY
When power is on, the control unit checks that display correctly
operates by switching on all segments for 1.5 sec. 8.8.8.8.
Firmware version, e.g. Pr I.0, will be viewed in the following
1.5 sec.
Panel will be viewed upon completion of this test.
PLEASE NOTE: if the panel is off, the control unit should be
in ENERGY SAVING mode; press the OK key to turn it on.
The control panel represents the physical status of the terminal
board contacts and of the program mode keys: if the upper
vertical segment is on, the contact is closed; if the lower vertical
segment is on, the contact is open (the above picture shows an
instance where the inputs PHOTO1, PHOTO2, EDGE1, EDGE2 and
STOP have all been correctly connected).
NOTE: if you are using an ADI module, other segments may
appear on the display, see the paragraph dedicated to the
“ADI INTERFACE”
Points being among display digits show the status of
programming push-buttons: as soon as a push-button is pressed,
its relevant point turns on.
The arrows on the left of the display show the state of the start
inputs. The arrows light when the related input is closed.
The arrows on the display right side show the gate status:
• The highest arrow turns on when the gate is into its opening
phase. If it blinks, it means that the opening has been caused
by a safety device (border or obstacle detector).
• The central arrow shows that the gate is on pause. If it blinks, it
means that the time countdown for the automatic closing has
been activated.
• The lowest arrow blinks when the gate is into its closing phase.
If it blinks, it means that the closing has been caused by a
safety device (border or obstacle detector).
OPENING IN PROGRESS
OPENED CONTACTCLOSED CONTACT
START
PEDESTRIAN
START
PAUSE (GATE OPENED)
CLOSING IN PROGRESS
LIMIT SWITCH (SX)
LIMIT SWITCH (DX)
SAFETY RIBBON 2
OK
STOP
PHOTOCELL 1
PHOTOCELL 2
SAFETY RIBBON 1
5.2 - USE OF THE KEYS FOR PROGRAMMING
The control unit functions and times are programmed by means
of a special configuration menu, which can be accessed and
explored by using the 3 keys, h, iand OK, located on the side of
the control unit display.
PLEASE NOTE: Outside the configuration menu, pressing
the hkey activates the START command, pressing the ikey
activates the PEDESTRIAN START command.
There are the following three kinds of menu items:
• Function menu
• Time menu
• Value menu
Function menu setup
Function menus allow selecting a function from among a group
of available options. When you enter into a function menu, the
current active option will be viewed; you can scroll all available
options through iand hkeys. By pressing the OK key, you
will activate the option viewed and you will return to the
configuration menu.
Time menu setup
Time menus allow setting a function duration. When you enter
into a time menu, the current setup value will be viewed; the
display mode depends on the current value:
• Each time you press hkey, current time value increases and
each time you press the ikey, current time value decreases.
• By holding down the hkey, you can quickly increase the time
value, up to reach the max. value allowed for this item.
• Vice versa, by holding down the i key, you can quickly decrease
the time value down to reach 0.0”
• In some circumstances, setting the value to 0means that
the relevant function is disabled, in this case, no will appear
instead of 0.0”
• By pressing on OK you will confirm the displayed value and you
will return to the configuration menu.
Value menu setup
Value menus are similar to time menus; however, the setup value
can be any number.
By holding down hor ikeys, the value will increase or decrease
slowly.
By pressing on OK you will confirm the displayed value and you
will return to the configuration menu.
The main programming menus of the control unit are shown in
the next pages.
To go through the menus use the three keys h, iand OK
according to the following chart:
Press and release the push-button OK
Keep pressed the push-button OK for 2 seconds
Release the push-button OK
Press and release the push-button h
Press and release the push-button i

ENGLISH
- 45 -
6 - ACCESSING THE CONTROL UNIT SETTINGS
1. Press and hold the OK key until the display shows the menu
desired
2. Release the OK key: the display will show the first item in the
sub-menu
-PrG Programming the control unit (chapter 12)
-Cnt Cycle counter (chapter 11)
-SEt Installation menù (chapter 9)
-dEF Loading the default parameters (chapter 9)
mWARNING: in case no operation is carried out for
more than one minute, the control unit exits from the
programming mode without saving any of your setups and
changes, which will get lost.
7 - QUICK CONFIGURATION
This paragraph concerns a quick procedure to set the control unit
and set it at work immediately.
We recommend following these instructions, in order to
check quickly the correct operation of control unit, motor
and accessories, and then changing the configuration in
case of any non-satisfactory parameter.
1. Call up the default configuration: see chapter 8
2. Set items
dir - StoP - Fot1 - Fot2 - CoS1 - CoS2
according to the safety devices installed on the gate.
For the position of the item menus inside the main menu and
for the options related to each item menu, refer to the
chapter 12.
3. Start the self-learning cycle: see chapter 9-9.1 (AUTOMATIC
LEARNING OF THE RUN LIMITS)
4. Check that the automation work properly and if necessary
modify the configuration of the desired parameters.
8 - LOADING THE DEFAULT PARAMETERS
If necessary, it is possible to restore all parameters to their
standard or default values (see the final summary table).
mPLEASE NOTE: This procedure results in the loss of all
customised parameters.
1. Press and hold the OK key until the display shows -dEF
2. Release the OK key: the display shows ESC (only press the OK
key if it is desired to exit this menu)
3. Press the ikey: the display shows dEF
4. Press the OK key: the display shows no
5. Press the ikey: the display shows Si
6. Press the OK key: all parameters are overwritten with their
default values (see Chapter 12), the control units exits
programming mode and the display shows the control panel.
-PrG d i r
-Cnt tot
-SEt ESC
----
2’’
4’’
6’’
-dEF ESC
8’’
10’’
dEF.
ESC
-dEF
Si
no

ENGLISH
- 46 -
9 - INSTALLATION MENÙ (SEt)
This menu allows you to perform the movements of the gate
needed during installation.
The automatic learning procedure enables to save run limits based
on data collected by the encoder.
The manual handling procedure allows to control the gate in hold
to run mode in special cases such as during installation /
maintenance or a malfunction of the photocells or edges.
mATTENTION: before proceeding, make sure to position
the mechanical stops and the limit sensors correctly.
1. Press and hold the OK key until the display shows -SEt
2. Release the OK key: the display shows ESC (only press the OK
key if it is desired to exit this menu)
3. Use the keys hand ito select the menu Mov to activate
manual handling or APPr to start the automatic learning
procedure of the run limits
4. Press OK to start the selected procedure
9.1 - AUTOMATIC LEARNING OF THE RUN
LIMITS
mCAUTION: to perform the self-learning procedure it
is necessary to disable the ADI interface by means of the
menu i.Adi . If some safeties are controlled by means of the
ADI module, they will not be active during the self-learning
CAUTION: During self-learning, the power applied to the
motor is that set in the Po.AL parameter
5. The display shows the control panel and the automatic learning
procedure of the run limits starts.
5.1 If the gate is not at the closed limit, the motor will
activate to close at the slow speed until it reaches the
range limit.
5.2 Gate opening is activated until the opening limit switch is
reached.
5.3 Gate closing is activated until the closing limit switch is
reached.
6. If the obstacle sensor has been enabled, the display shows the
recommended value for the obstacle sensor. If no operations
are performed for 20 seconds, the control unit exits the
programming phase, without saving the value recommended.
7. The recommended value may be modified by pressing the h
and ikeys, and pressing the OK key confirms the displayed
value and the display shows SEnS
8. Press and hold the ikey until the display shows FinE, then
press the OK key, select the option Si and then press the
OK key to exit programming mode, storing the value for the
sensors.
mPLEASE NOTE: If the control unit is left to time out
from programming mode (1 minute), the obstacle sensor
return to the value that was set prior to performing self-
training (according to the default values, the sensor is
disabled). On the other hand, the limit switch positions are
always stored.
9.2 - MANUAL HANDLING
mWARNING: when this procedure is activated the
safeties are not active.
5. The display shows MAn
6. Press and hold the hkey to open the gate or the ibutton to
close the gate
7. Release the button to stop the gate
8. To exit this menu, press OK
NOTE: If the motor is inactive for more than one minute
the procedure terminates automatically.
APPr
ESC
Mov
MAn
-SEt
Other manuals for AYROS-24V series
1
Table of contents
Other V2 Controllers manuals
Popular Controllers manuals by other brands

Swagelok
Swagelok KFB Series Maintenance instructions

Danfoss
Danfoss ERC 112D VSC user guide

Siegenia
Siegenia Drive Connect Box Installation and operating instructions

Beam Labs
Beam Labs Pixelator Plus product manual

KIPI
KIPI ecoMAX860P3-C Installation and operating manual

Salus
Salus PCSol 201 Installation and operation manual