DSC 3G2080 User manual

3G2080(R)
Cellular Alarm Communicator - International
TL2803G(R)
Internet and HSPA Dual-Path Alarm Communicator -
International
Installation Guide v4.1
For installation manual visit www.dsc.com
Warning: This manual contains information on limitations regarding product use and function and inform-
ation on the limitations as to the liability of the manufacturer. The entire manual should be carefully read.

WARNING: Installer please read
carefully
Note to Installers
The warningson this page contain vitalinformation. Asthe only individualin con-
tact with system users, it is the installer’s responsibility to bring each item in this
warning to the attention of allusersof thissystem.
System Failures
Thissystemhasbeen carefullydesigned to be aseffective aspossible. There are
circumstances, however, involving fire, burglary, or other types of emergencies
where it may not provide protection. Any alarmsystem of anytype may be com-
promised deliberatelyor mayfailto operate as expected for a varietyof reasons.
Some, but not all, of the reasonsmay be:
Access by Intruders
Intrudersmayenter through an unprotected accesspoint, circumvent a sensing
device, evade detection by moving through an area of insufficient coverage, dis-
connect a warning device, orinterfere with or prevent the proper operation of the
system.
Component Failure
Although everyefforthas been made to make thissystem asreliable as possible,
the systemmayfailto function asintended due to the failure of a component.
Compromise of Radio Frequency (Wireless) Devices
Signalsmay not reach the receiver under all circumstances which could include
metalobjectsplaced on ornear the radio path ordeliberate jamming orotherinad-
vertent radio signalinterference.
Criminal Knowledge
Thissystem contains security features which were known to be effective at the
time of manufacture. It is possible forpersonswith criminalintent to develop tech-
niqueswhich reduce the effectivenessof these features. It is important that the
securitysystembe reviewed periodicallyto ensure that its featuresremain effect-
ive and that it isupdated orreplaced if it isfound that it does not provide the pro-
tection expected.
Failure of Replaceable Batteries
Thissystem’s wirelesstransmitters have been designed to provide several years
of battery life under normal conditions.The expected battery life isa function of
the device environment, usage, and type. Ambient conditionssuch as high humid-
ity,high or low temperatures, or large temperature fluctuations may reduce the
expected battery life. While each transmitting device has a low battery monitor
which identifies when the batteries need to be replaced, this monitor may fail to
operate as expected. Regulartesting and maintenance willkeep the system in
good operating condition.
Inadequate Installation
A security system must be installed properly in order to provide adequate pro-
tection. Every installation should be evaluated by a security professional to
ensure that allaccess points and areas are covered. Locks and latches on win-
dows and doors must be secure and operate as intended. Windows, doors,
walls, ceilingsand other building materials must be of sufficient strength and con-
struction to provide the levelof protection expected. Areevaluation mustbe done
during and after any construction activity. An evaluation bythe fire and/or police
department is highlyrecommended if thisservice isavailable.
Inadequate Testing
Most problems that would prevent an alarm systemfrom operating as intended
can be found byregular testing and maintenance. The complete system should
be tested weeklyand immediatelyaftera break-in, an attempted break-in, a fire,
a storm, an earthquake, an accident, orany kind of construction activityinside or
outside the premises. The testing should include all sensing devices, keypads,
consoles, alarm indicating devices, and any other operational devices that are
part of the system.
Insufficient Time
There may be circumstanceswhen the systemwill operate asintended, yet the
occupants will not be protected from an emergency due to their inability to
respond to the warnings in a timelymanner. If the systemis remotely monitored,
the response may not occurin time to protect the occupantsor theirbelongings.
Motion Detectors
Motion detectorscan onlydetectmotion within the designated areasasshown in
their respective installation instructions. They cannot discriminate between
intruders and intended occupants. Motion detectors do not provide volumetric
area protection. Theyhave multiple beams of detection and motion can only be
detected in unobstructed areas covered by these beams. They cannot detect
motion which occurs behind walls, ceilings, floor, closed doors, glass partitions,
glass doors or windows. Any type of tampering whether intentional or unin-
tentionalsuch asmasking, painting, or spraying of anymaterialon the lenses, mir-
rors, windows or any other part of the detection system will impair its proper
operation.
Passive infrared motion detectors operate by sensing changes in temperature.
However their effectiveness can be reduced when the ambient temperature
risesnear orabove bodytemperature orif thereare intentionalor unintentional
sourcesof heat in ornear the detection area. Some of these heat sources could
be heaters, radiators, stoves, barbecues, fireplaces, sunlight, steam vents, light-
ing and so on.
Power Failure
Control units, intrusion detectors, smoke detectors and many other security
devicesrequire an adequate powersupplyforproperoperation. If a device oper-
atesfrombatteries, it ispossible forthe batteriesto fail. Even if the batteries have
not failed, they must be charged, in good condition and installed correctly. If a
device operates only by AC power, any interruption, however brief, will render
that device inoperative while it doesnot have power. Power interruptionsof any
length are often accompanied by voltage fluctuationswhich may damage elec-
tronic equipment such as a security system. After a power interruption has
occurred, immediatelyconduct a complete systemtest to ensure that the system
operatesasintended.
Security and Insurance
Regardlessof itscapabilities, an alarmsystemisnot a substitute for propertyor life
insurance. An alarmsystemalso isnot a substitute for propertyowners, renters, or
other occupants to act prudentlyto prevent or minimize the harmful effectsof an
emergency situation.
Smoke Detectors
Smoke detectorsthat are a part of thissystemmaynot properlyalert occupants of
a fire for a number of reasons, some of which follow. The smoke detectors may
have been improperlyinstalled or positioned. Smoke maynot be able to reach the
smoke detectors, such aswhen the fire is in a chimney, walls orroofs, or on the
other side of closed doors. Smoke detectorsmay not detect smoke from fires on
anotherlevelof the residence or building.
Everyfire isdifferent in the amount of smoke produced and the rate of burning.
Smoke detectorscannot sense alltypesof firesequallywell. Smoke detectorsmay
not provide timelywarning of fires caused bycarelessnessorsafetyhazards such
as smoking in bed, violent explosions, escaping gas, improper storage of flam-
mable materials, overloaded electrical circuits, children playing with matches, or
arson.
Even if the smoke detector operates as intended, there may be circumstances
when there isinsufficient warning to allow alloccupantsto escape in time to avoid
injuryordeath.
Telephone Lines
If telephone lines are used to transmitalarms, theymay be out of service or busy
forcertain periods of time. Also an intrudermaycut the telephone line ordefeat its
operation bymore sophisticated meanswhich maybe difficult to detect.
Warning Devices
Warning devices such as sirens, bells, horns, or strobes may not warn people or
waken someone sleeping if there isan intervening wallor door. If warning devices
are located on a different levelof the residence orpremise, then it is less likely that
the occupants will be alerted or awakened. Audible warning devices may be
interfered with byother noise sourcessuch asstereos, radios,televisions, air con-
ditioners, otherappliances, or passing traffic. Audible warning devices, however
loud, maynot be heard by a hearing-impaired person.
2

General
IMPORTANT
This installation manual shall be used in conjunction with the control panel. All the safety instructions specified within that
manual shall be observed. The control panel is referenced as the “panel” throughout this document. This installation guide
provides the basic wiring, programming and troubleshooting information.
The HSPA(3G)/dual-path alarm communicator is a fixed, wall-mounted unit,and shall be installed in the location specified in
these instructions.The equipment enclosure must be fully assembled and closed, with all the necessary screws/tabs, and
secured to a wall before operation. Internal wiring must be routed in a manner that prevents:
lExcessive strain on wire and on terminal connections,
lInterference between power limited and non power limited wiring,
lLoosening of terminal connections, or
lDamage of conductor insulation.
WARNING: Never install this equipment during a lightning storm!
Safety Information
The installer mustinstructthe system user on each of the following:
lDo not attempt to service this product. Opening or removing covers may expose the user to dangerous voltages or other
risks.
lAny servicing shall be referred to service persons only.
lUse authorized accessories only with this equipment.
lDo not stay close to the equipment during device operation.
lDo not touch the external antenna.
Model Information
This manual covers the following models of alarm communicators: TL2803GR, TL2803G, 3G2080R, 3G2080 (850/1900MHz
operation), TL2803GR-EU, TL2803G-EU, 3G2080R-EU, 3G2080-EU (900/2100MHz operation), TL2803G-AU, 3G2080-AU,
TL2803GR-AU, and 3G2080R-AU (850/2100MHz operation). References to model names TL2803G (R) and 3G2080(R)
throughout this manual apply to all specified models unless stated differently. Models ending in “R” include a built-in RS-232
interface for connecting to local third party applications.
The TL2803G(R)/3G2080(R) supports integration over cellular/IP, available with licensed third party product solutions. Specific
programming for the related programming sections is to be provided by the third party. A current list of compatible third party
solutions can be found at www.dsc.com.
3G2080(R): Is a HSPA(3G) cellular alarm communicator that sends alarm communication to Sur-Gard System I, II, III (SG-
DRL3IP), IV (SG-DRL4IP), and 5 (SG-DRL5IP) central station receivers via a HSPA(3G)/GPRS digital cellular network.
TL2803G(R): Is a dual-path HSPA(3G) Ethernet alarm communicator that sends alarm communication to Sur-Gard System I,
II, III, IV, and 5 central station receivers through Ethernet/Internet or a HSPA(3G)/GPRS digital cellular network.
The communicator can be used as either a backup or primary communicator. The communicator supports Internet Protocol (IP)
transmission of panel and communicator events over Ethernet/Internet and/or HSPA/GPRS.
The cellular performance of the 3G2080(R) or TL2803G(R) communicator depends greatly on HSPA(3G)/GPRS network cov-
erage in the local area. The unit should not be mounted in the final location without first performing the communicator place-
ment test below to determine the best location for radio reception (minimum of one green LED ON). Optional antenna kits (GS-
15ANTQ, GS-25ANTQ and GS-50ANTQ) are available from DSC to improve signal strength as required.
NOTE: Prior to installation of the 3G2080(R) or TL2803G (R) communicator, confirm with the local service provider that the
HSPA(3G)/GPRS network is available and active in the area where the communicator will be installed, and that radio
signal strength (CSQ) is adequate.
Panel Mounting
The following communicators are compatible with HS2016, HS2032, HS2064, and HS2128 panels:
l3G2080(R) (HSPA(3G)/GPRS only)
lTL2803G(R) (Ethernet/Internet + HSPA(3G)/GPRS dual-path)
Features
l128-bit AES encryption via cellular and Ethernet/Internet (NIST validation cert. number 2645).
lBack up or primary cellular alarm communication.
lAutomatically switches to 2G (EDGE/GPRS) if HSPA(3G) service is not available.
lEthernet LAN/WAN 10/100 BASE-T (TL2803G(R) only).
lFully redundant Ethernet/Internet and cellular dual-path alarm communication (TL2803G(R) only).
lFull event reporting to central station.
3

lIndividual Internet and/or cellular periodic test transmission.
lIntegrated call routing.
lVisual Verification (Requires Sur-Gard System 5 Receiver)
lRemote firmware upgrade capability of the communicator and panel firmware via Ethernet and/or cellular.
lPanel remote uploading/downloading support via cellular and Ethernet/Internet.
lPC-LINK connection.
lProgrammable labels.
lSIA and Contact ID (CID) formats supported.
lSignal strength and trouble display LEDs.
lSupervision heartbeats sent via cellular and Ethernet/Internet.
lCommand and Control by SMS.
lThird party integration over cellular/IP.
Technical Specifications
The TL2803G(R) is also suitable to be used with a compatible control unit listed for dual line security transmission when used
in conjunction with a DACT or a Public Switched Data Network (PSDN) transmitter, where the PSDN provides the line security
and is the primary line. In this mode, alarm signals are to be sent simultaneously over both communication methods.
EN50131-1 Installation Requirements
For EN50131-1 compliant installations, the following programming options shall be set as described.
Supervision Heartbeat (required for ATS4 and ATS5):
l[851][004] set to 0087h (135s heartbeat).
NOTE: The compatible receiver at ARC location shall have supervision window programmed for 1800s (ATS4) or 180s
(ATS5).
l[851][005] options 1,2 and 3 shall be enabled
l[851][005] option 8 shall be enabled
Test transmission (required for ATS3):
l[851] System test options [026-029] shall be enabled (FF) for the communication paths available.
l[851][124-125] and [224-225] shall be programmed with time of day for test transmission and 1440 minutes (24h) for test
transmission cycle
Configuration of communication paths (all ATS classes)
l[300][001] select option 02 for auto routing (this will allow transmission of the events over all available communication
paths in the system)
l[380] enable option 5 (YES) for parallel transmission over all available communication paths (if redundant configuration is
desired)
l[382] enable option 5 (YES) this will enable Alternate communicator
l[384] enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1).
Ratings Compatibility
Table 1: Communicator Ratings
Model 3G2080(R)
Cellular only
TL2803G(R)
Internet and Cellular
Power Supply Ratings
Input Voltage
10.8-12.5 VDC
Power is supplied from the panel’s PC-Link header or a PCL-422 module in remote
cabinet installations. In remote cabinet installations, the PCL-422 module located with the
communicator is powered by either an HSM2204 or an HSM2300. Refer to the PCL-422
installation instructions for details.
Current Consumption
Standby Current 90mA @ 13.66V 120mA @ 13.66V
Alarm (Transmitting) Current 400mA @ 12V
Operating Frequency 900MHz, 1800MHz, 2100MHz
Typical Antenna Gain 2dBi
Environmental Specifications
Operating Temperature -10°C to 55°C
4

Model 3G2080(R)
Cellular only
TL2803G(R)
Internet and Cellular
Humidity 5% ~ 93% relative humidity, non-condensing
Mechanical Specifications
Board Dimensions (mm) 100 × 150 × 15 100 × 150 × 15
Weight (grams) with bracket 310 320
Table 2: Compatible Receivers and Panels
Communicator Receiver/Panel Description
3G2080(R) Receiver
lSur-Gard System I-IP Receiver, version 1.13+
lSur-Gard System II Receiver, version 2.10+
lSur-Gard SG-DRL3-IP, version 2.30+ (for Sur-Gard System III Receiver)
lSur-Gard SG-DRL4-IP version 1.20+ (for Sur-Gard System IV Receiver)
lSur-Gard SG-DRL5-IP version 1.00+ (for Sur-Gard System 5 Receiver)
TL2803G(R) Panel
lHS2016
lHS2032
lHS2064
lHS2128
NOTE: Enter [*][8][Installer Code][900] at keypad to view the panel version number.
Communicator Installation Configuration
This Internet and HSPA dual-path alarm communicator shall be installed by service persons only (service person is defined as
a person having the appropriate technical training and experience necessary to be aware of hazards to which that person may
be exposed in performing a task and can also take measures to minimize the risksto that person or other persons). The Com-
municator shall be installed and used within an environment that provides the pollution degree max 2, overvoltages category II,
in non-hazardous, indoor locations only. This manual shall be used with the installation manual of the panel which is con-
nected to the communicator. All instructions specified within the panel manual must be observed.
All the local rules imposed by local electrical codes shall be observed and respected during installation.
Installing the Ethernet Cable(TL2803G(R) Only)
A Category 5 (CAT 5) Ethernet cable must be run from a source with Internet connectivity to the communicator module, inside
the panel. The communicator end of the cable must be terminated with an RJ45 plug, which will connect to the communicator’s
RJ45 jack after the communicator is installed. All requirements for installation of CAT5 Ethernet cable must be observed for cor-
rect operation of the communicator, including, but not limited to, the following:
lDo NOT strip off cable sheathing more than required for proper termination.
lDo NOT kink/knot cable.
lDo NOT crush cable with cable ties.
lDo NOT untwist CAT5 pairs more than ½ in. (1.2cm).
lDo NOT splice cable.
lDo NOT bend cable at right angles or make any other sharp bends.
NOTE: CAT5 specification requires that any cable bend must have a minimum 2 in. (5 cm) bend radius. Maximum length of
CAT 5 cable is 328 ft. (100 m).
Inserting and Removing the SIM Card
1. Remove the front cover of the panel to access SIM holder.
2. Remove power from the panel and disconnect the battery and telephone line.
3. On the SIM card holder push gently to slide the cover downwards to OPEN. This will unlatch the SIM card holder on the
top edge of the communicator PCB. (See Figure 3).
4. Tilt the top of the SIM card holder downwards to accessthe SIM card.
NOTE: The SIM can be damaged by bending or scratching contacts. Use caution when handling SIM cards.
5. Insert or remove the SIM card, noting the orientation of the notches on the SIM card and the SIM card holder.
6. When inserting a SIM card, insert the card in the proper orientation and gently push the SIM card holder down and slide
the holder as indicated by the arrow on SIM holder, to LOCK.
7. Reconnectthe backup batteryand telephone line, apply AC power to panel, and replace the panel cover.
Running the RS-232 Cable (R models only)
When installing the communicator for use with third party applications an RS-232 cable must be connected between the third
party device and the communicator module.
NOTE: Maximum cable length for RS-232 cable is 8 ft.(2.4 m).
Please refer to the installation manual for the third party device for wiring instructions.
5

Installing Communicator in Panel
Installing Communicator with HS2016, HS2032, HS2064, and HS2128 Panel
NOTE: Before installing communicator or inserting/removing SIM, ensure that system power is OFF and telephone line is dis-
connected.
1. To assemble supplied mounting bracket, perform the following: (See Figure 1).
a. Remove the 4 white plastic standoffs from the bag provided with the communicator kit.
b. Insert the 4 standoffs through the backof the mounting bracket, into the holes at each corner. (The antenna mount-
ing tab should be facing away from you).
c. Place the bracket on a flat, solid surface. Hold the communicator component side up and orient the 4 holes on the
communicator with the 4 standoffs protruding from the bracket. Push the communicator firmly and evenly onto the
standoffs until it is securely attached to the mounting bracket.
d. Remove the panel front cover.
e. Remove and discard the circular knockout located in the top-right section of the panel. (This hole will be used for con-
nection of the supplied radio antenna).
f. Connect the supplied 5” (12.7 cm) antenna cable to the radio, by passing the connector through the hole on back of
the mounting bracket to the communicator board. Push the antenna connector firmly into the socket on the cellular
radio. (See Figure 3).
Figure 1: Communicator Mounting Bracket
Brass Washer
Nylon washer (flat)
Nylon Washer
with bushing
(thicker flat washer)
Brass nut
Antenna
Mounting Tab
Mounting
Holes
Mounting Holes
Antenna
Cable
Mounting Plate
External Antenna
Screw Thread
Communicator
Board
Mounting
Plate
Stand Off
2. Install the Communicator into the panel:
a. Attach one end of the PC-LINK cable to the panel PCLINK_2 header on the panel (red wire goes on the right-hand
pin of the panel PCLINK_2 header (see Figure 3)).
b. Insert the assembled communicator into the panel.
NOTE: Ensure that the threaded antenna connection point is visible through the knockout hole at the top right of the
panel.
c. Place the nylon washer with bushing (thick flat washer) onto the threaded section of the antenna cable. Insert the
threaded section through the antenna mounting knockout hole at top right of panel.
d. Place the second nylon washer (flat), followed by the brass washer and the brass nut, onto the threaded section of
the cable, outside the panel. Tighten the assembly by hand only (finger tight only- do not over tighten the antenna
assembly).
e. Locate the screw hole on the right side wall of the panel. See Figure 2 "screw". Line up the assembled com-
municator with the right side wall of the panel and, using the screw provided, secure the mounting bracket to the
panel.
f. Attach the other end of the PC-LINK cable to the communicator (red wire goes on the right-hand pin of the com-
municator PC-LINK header (See Figure 3)).
g. Using light pressure (finger tight only), attach the supplied white quad band whip antenna to the threaded antenna
connection point at top of the panel.
6

Figure 2: HS2016/2032/2064/2128 Control Panel
PC-Link
cable connector
screw
quad band
whip antenna
GSM Radio
RJ-45
UA601
Use light pressure
to attach antenna
nger tight only.
HS2016/2032/2064/2128
WARNING! - 3G2080(R)/TL2803G (R) modules are power limited. Do not route any wiring over the circuit board. Maintain
at least 1in. (25.4mm) separation between circuit board and wiring. A minimum of ¼ in. (7mm) separation must be main-
tained at all points between non-power limited wiring and power limited wiring.
3. To electrically connect the communicator to the panel, perform the following steps (See Figure 3).
a. Disconnect both AC power and battery connections from the panel, and disconnect telephone line.
b. Confirm that the SIM card is inserted in the holder and locked.
4. Install Network Cable (TL2803G(R) only). Route the CAT 5 Ethernet cable through back of the panel and plug it into the
communicator’s RJ45 jack.
NOTE: Before leaving the premises the Ethernet communication lines mustfirst be connected to an approved (acceptable to
local authorities) type NID. All wiring shall be performed according to the local electrical codes.
Figure 3: Communicator Wiring Diagram
AUDIO/DEFAULT
DSC
UA601
PC-LINK
PCLINK_2
COM
TL2803G(R)
3G2080(R)
AC
AC Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
AUX+
BELL +
PGM1 PGM3
RING
T-1
HS2016/2032/2064/2128
3G Radio
UA621
To external antenna
Input Ratings:
+10.8V ~ +12.5 VDC
90mA(3G2080(R))/120mA(TL2803G(R)) standby;
400mA alarm
DSC Panel min. power requirements:
- 16.5 VAC 40 VA transformer;
- 12 VDC 7Ah battery
Red
Red
Jumper pins 4 and 5
to reset.
L
o
c
k
1
From NID
TL2803G(R)
Use only CAT5
Supervised
RJ-45
GRN
YEL
TIP
R-1
BLK
RED
AUX -
BELL -
EGND
TX+
GND
TX-
RX+
RX-
SHLD
SIM
Network Link
YELLOW
PGM2 PGM4
Maximum cable length
100 m (328 ft)
RS-232
To 3rd party device
5. Install the RS-232 connections (R models only). If using the communicator with a third party device, wire the connections
as per the table below:
7

Table 3: RS-232 Connections
Third Party Device Communicator
TX RX+
Unused RX-
RX TX+
Unused TX-
GND GND
6. Perform the following steps for initial power on of the panel with communicator installed:
a. Reconnect the AC power, telephone line, and battery + connector to the panel.
(The communicator and panel will power up together).
b. Observe that the communicator’s red and yellow LEDsare flashing together while it initializes. The red and yellow
LEDs will continue to flash until the communicator has successfully communicated to all programmed receivers. If this
is the first time the communicator has been powered up in the panel, the module will initiate communication to C24
Communications to request remote programming.
NOTE: During radio reset, the two green LEDs will flash alternately.
NOTE: Initialization may take several minutes to complete. Red and yellow LEDs will flash together during initialization. Do not
continue to next step until the red and yellow LEDs have stopped flashing. (If only the yellow LED is flashing, there is a
communicator trouble and the green LEDs are not valid for communicator placement test). Correct trouble indicated by
flashes on yellow LED before continuing. (See Table 8 for troubleshooting assistance).
7. Perform the communicator placement test below.
8. Mount the panel in final location indicated by placement test.
Communicator Placement Test
3G2080(R) and TL2803G(R) only
To confirm that the cellular antenna location is suitable for radio operation, perform the placement test as follows:
NOTE: If radio signal strength is too low, relocate the panel or install an optional extension antenna during this procedure.
1. Confirm that the yellow LED on the communicator is not flashing. A flashing yellow LED indicates trouble on the com-
municator. See Table 8 to troubleshoot and correct the cause of this trouble before continuing to the next step.
2. Confirm that the strength of the radio signal on the yellow LED and the 2 green LEDs on the communicator meet or
exceed the minimum signal level requirement. Minimum signal level: The yellow LED is OFF and the green LED 1 (fur-
thest from the yellow LED) is ON (i.e., not flashing) for the panel location to be acceptable. For interpretation of receiver
strength on LEDs, refer to the table “Radio Signal Strength” on page 10.
Cellular Signal Strength Display - LCD Keypad only
The cellular network signal strength can be checked on the keypad LCD screen by entering installer programming section
[850]. The LCD will indicate the SIM card activation status followed by up to five bars of signal strength. This display will auto-
matically update every three seconds. For the relationship between signal strength bars, CSQ level, and signal level in dBm,
refer to “Radio Signal Strength” on page 10.
Table 4: Signal Strength Display
Description Display
SIM card active and current signal strength
SIM card inactive and current signal strength
Radio not registered
OR AND
NOTE: If the required signal strength is too low with the panel in its current location, the panel must be relocated or an external
antenna is required.
If required, the following cellular extension antenna kits are available to the installer:
lGS-15ANTQ - 4.57m (15’) internal antenna extension kit (suitable for interior mounting).
lGS-25ANTQ - 7.62m (25’) external antenna extension kit (suitable for interior/exterior mounting).
lGS-50ANTQ - 15.24m(50’) external antenna extension kit (suitable for interior/exterior mounting).
Specific instructions for the installation of the extension antenna are included with the kit. Observe all the electrical safety instruc-
tions regarding the installation of the antenna. All the wiring of the equipment shall be fully compliant with the local rules and
regulations.
8

3. If required, install the antenna extension and perform the following steps to determine the best location for placement of
the antenna:
a. Disconnect the white whip antenna from the panel.
b. Attach one end of the antenna extension cable to the threaded antenna connector on the panel and the other end to
the external antenna.
4. Move the extension antenna to various locations while observing the two green LEDs on the panel.
a. Continue to reposition the extension antenna until it receives an acceptable (minimum one green LED ON solid) sig-
nal strength.
NOTE: Minimum strength is: green LED 1 flashing and yellow LED off. If green LED 1 is flashing, relocation
should be considered.
b. Mount the supplied antenna extension bracket at the location that provides the best signal strength.
5. Alternately,reposition the panel to improve signal strength. Dismount the panel and move it to another location to
achieve the required signal strength. If the panel is relocated to improve signal strength, mount it in the new location.
6. When final panel/antenna location is determined, continue at the Initial Panel Programming section.
NOTE: If the SIM card is not activated, placement test will indicate the signal strength of the nearest cellular tower.
NOTE: In between displaying signal strength, the signal strength LEDs will flash alternately if an inactive SIM card is used. The
flashing indicates that the module is attempting to attach to the cellular network and will only last briefly.
Initial Panel Programming
HS2016/2032/2064/2128 Initial Programming
Please refer to panel manual section ‘Alternate Communicator Set-up’ for details.
1. In panel section [377] ‘Communication Variables’, subsection [002] ‘Communication Delays’, sub-subsection [1] ‘Com-
munication Delay’, program 060 (seconds).
2. In panel section [382] ‘Communicator Option 3’ set option [5] ON
3. In panel sections [300] subsections [001] to [004], program the subsection with 02 to 06
Table 5: Communicator Path Programming
Value Communication Method
02 Auto Routing
03 Ethernet 1
04 Ethernet 2
05 Cellular 1
06 Cellular 2
NOTE: Refer to panel manual for additional information
4. In panel section [350] ‘Communication Formats’, program the communication format as: CID (03) or SIA FSK (04).
5. In panel sections [311] - [318] ‘Partition Call Directions’, program the call direction options for the system.
6. In panel section [401] ‘DLS/SA Options’, set toggle option [2] ‘User Enable DLS’ to ON in order to perform panel DLS
session through cellular or Ethernet.
NOTE: Before leaving the premises, the installer should verify all programmed communications paths. See programming
options section [851][901] to send immediate test transmissions.
Communicator Troubles displayed on a HS2016/2032/2064/2128
The communication trouble is the only trouble that will appear on the keypad Liquid Crystal Display (LCD) when encountered
by a communicator installed in a HS2016/2032/2064/2128. For more information about the trouble on the communicator mod-
ule, refer to the panel event buffer or by accessing *2 to view the individual trouble types.
Communicator Status LEDs
The communicator has four on-board LED indicators. These include one yellow trouble LED, one red network connection
status LED and two green signal strength LEDs. The LED meaning is described in this section.
Yellow Trouble LED
This yellow LED will flash to indicate a trouble on the unit. The number of flashes indicates the type of trouble. See the table
below for the coded flashes and the conditions which will activate the trouble status LED.
9

Table 6: Yellow Trouble Status LED
# of
Flashes Trouble # of
Flashes Trouble
2 Panel Supervision Trouble 8 Receiver Supervision Trouble
4 Not Applicable 9 FTC Trouble
5 Cellular Trouble 10 C24 Communications Configuration Failure
6 Ethernet Trouble 12 Module Configuration Trouble
7 Receiver Not Available Trouble
NOTE: Only the highest priority trouble (2 flashes is the highest priority trouble) is indicated. When this trouble is restored, the
next highest trouble will indicate, if present. This will continue until all troubles have been cleared (yellow LED is not
flashing).
Red Network Connection Status LED
TL2803G(R)
BLINKING: Indicates communications in progress.
lOnce quickly for outgoing Ethernet transmission.
lTwice quickly to indicate incoming Ethernet ACK/NACK.
OFF: This is the normal state of the red network connection status LED. There are no network connection issues present.
ON: There is a problem with the Ethernet or the cellular network connection. LED will be ON if any of the following occur: Eth-
ernet cable is not connected, DHCP configuration times out, unit fails to get an IP address from the cellular network, or Cellular
connection has been reset.
(Green LED 1) (Green LED 2) and (Yellow LED) Signal Strength
NOTE: If the yellow LED is flashing, signal strength in table below is not valid.
See Table 8 for troubleshooting flashing yellow LED.
Table 7: Radio Signal Strength
Signal
Strength
CSQ
Level
Yellow
LED
Green
LED 2
Green
LED 1
Signal
Level
dBm
Action Required
Radio Not
Ready N/A N/A Alternate
Flashing
Alternate
Flashing N/A
If this status persists and the yellow LED shows 5
flashes, confirm that the SIM card is active.
Confirm cellular service is active in area.
Relocate panel or install external antenna.
No Signal 0 ON OFF OFF -108.8 Check all antenna connections.
1 Bar 1 - 4 Flashing
See Note OFF Flashing -108 ~ -
103 Relocate panel or install external antenna if yellow
trouble LED shows five flashes.
2 Bars 5 - 6 OFF OFF Flashing -102 ~ -
99
3 Bars 7 - 10 OFF OFF ON -98 ~ -91
Location is OK. Cellular signal strength is greater
than CSQ 7.
4 Bars 11-13 OFF Flashing ON -90 ~ -85
5 Bars 14 + OFF ON ON -84 and
higher
NOTE: The communicator will indicate cellular trouble (yellow LED = 5 flashes) if the calculated average CSQ Level is 4 or
less. The communicator signal strength can be viewed remotely with C24 Communications.
Network Activity LEDs - Red and Green(TL2803G(R) only)
lEthernet Activity: Red LED will blink quickly once for transmit, or twice for receive.
lCellular Activity: Green LED 2 will blink quickly once for transmit, or twice for receive
10

Communicator Reset/Update
Factory Defaults Reset
Reset the programming options for the communicator to the factory settings by installing the hardware jumper. Perform the fol-
lowing steps to reset the communicator:
NOTE: A jumper is required on AUDIO/DEFAULT pins 4 and 5 to reset the hardware values.
1. Remove panel front cover.
2. Locate the AUDIO/DEFAULT 5 pin connector on the communicator board (see Figure 3).
3. Apply a jumper to short the hardware default pins 4 and 5.
4. Remove AC and DC power from the panel and then reapply power to the panel.
5. Wait until the two green LEDs on the communicator begin flashing rapidly.
6. Remove the jumper from the hardware default pins 4 and 5 (green LEDs will stop flashing).
7. Replace the panel cover.
NOTE: The communicator has now been reset to the factory default values.
Firmware Update
The firmware of the device can be updated over cellular or Ethernet (remote or local updating):
lWhen the firmware update begins, all 4 LEDs are ON.
lDuring the firmware update process, the LEDs will cycle in a chaser pattern.
lDuring the firmware update process, the chaser pattern will briefly pause and resume again. This indicates firmware veri-
fication check has passed, and application update will begin.
lAfter a successful update, the unit will automatically restart.
lShould the update fail, all 4 LEDs will flash ON, then OFF together at 1 second intervals.
NOTE: If the firmware update fails,restart the communicator by cycling power. For persistent update failures, contact the dealer.
Communicator Troubleshooting
Table 8: Trouble Indications
Trouble indic-
ation
Trouble
Indicator Digit Possible Causes Trouble Possible Solution
No Indication N/A No Power
lCheckthe power connections between the panel and the
communicator.
lConfirm PC-LINK cable is properly installed between communicator
and panel.
Yellow LED
– ON Solid N/A No Signal
lConfirm that cellular network service is active in the area.
lEnsure the antenna is securely connected to the radio. Check
antenna stub cable is securely connected to the radio.
lIf an external antenna is used, ensure the antenna is securely
screwed on to the antenna cable connector. Check external antenna
for damage or open/short.
Trouble LED
– 2 Flashes 02
Panel
Supervision
Trouble
lCheck section [382] toggle option[5] is ON (Alternate Communicator
Enabled).
lEnsure the PC-LINK cable between the panel and communicator is
connected properly (not reversed) and is securely in place.
Yellow LED
– 5 Flashes 05 Cellular Trouble
lConfirm that cellular service is available and active in the area.
lCheck all antenna connections.
lEnsure average radio signal strength is CSQ 5 or higher. (See Table
7 ).
lEnsure the SIM card is properly inserted into the SIM card holder.
lEnsure the SIM card has been activated (could take up to 24 hrs after
install).
lIf this trouble persists, relocate the panel (and communicator) or
install an external antenna extension kit.
Yellow LED
– 6 Flashes 06 Ethernet Trouble
lCheck with the ISP to confirm Internet service is active in the area.
lEnsure the Ethernet cable is securely inserted into the RJ45 jack of
the communicator and the hub/router/switch.
lCheck the link light on the hub/router/switch is ON. If link light is OFF,
start the hub/router/switch.
lIf DHCP is used, ensure that the unit has an assigned IP address from
the server. In Section [851] [992] verify a valid IP address is
programmed. If not, contact the network administrator.
11

Trouble indic-
ation
Trouble
Indicator Digit Possible Causes Trouble Possible Solution
lIf problem persists, replace the Ethernet cable and RJ45 connector.
Yellow LED
– 7 Flashes 07 Receiver Not
Available
lEnsure that the Ethernet path has Internet connectivity.
lIf using a static IP address, confirm that the gateway and subnet mask
are entered correctly.
lIf the network has a firewall, ensure the network has the programmed
outgoing ports open (default UDP port 3060 and port 3065).
lEnsure that all the receivers are programmed for DHCP or have the
proper IP address and port number.
lEnsure the cellular receiver APNs have been programmed with the
access point name provided by the cellular provider.
lIf Common Mode is used, and only one path is initialized while the
other path is not successful, generate a manual test transmission over
both paths or power cycle the communicator to recover the ‘Receiver
Not Available’ trouble.
Yellow LED
– 8 Flashes 08
Receiver
Supervision
Trouble
lThis trouble is indicated when supervision is enabled and the unit is
not able to successfully communicate with the receiver.
lIf this trouble persists, contact the central station.
Yellow LED -
9 Flashes 09 FTC Trouble
lThe unit has exhausted all communications attempts to all
programmed receivers for events generated by the communicator.
lRestart the system, if trouble persists, contact the dealer.
Yellow LED
– 12 Flashes 0C
Module
Configuration
Trouble
lThis indication appears when section [021] system account code or
sections [101]; [111]; [201]; and [211] receiver account code have not
been programmed. Ensure that a valid account code has been
entered in these sections.
All LEDs
flashing
together
N/A Boot Loader
Failed
lDisconnect power, then reconnect power to the communicator
module.
Red and
Yellow LEDs
flashing
together
N/A Initialization
Sequence
lThe unit is still initializing please wait while the unit gets its
programming and establishes a connection to all programmed
receivers.
NOTE: This process may take several minutes to complete.
Only Green
LEDs
flashing
N/A Hardware Default
Jumper
lThe hardware default jumper is installed and must be removed. See
Figure 3.
Green LEDs
alternating N/A Radio Reset or
Radio Initialization
lIf this status persists and the yellow LED shows 5 flashes, confirm that
the SIM card is active.
Ethernet/Cellular Programming Options
The programming sections described in this document can be viewed at the keypad LCD.To start programming enter: [*][8]
[installer code] [851] [section number] , where section number is the 3-digit section number referenced in this section. The
programming worksheets at the end of this document can be used to record the new values when programming changes have
been made from the default values.
12

Ethernet Cellular Programming
Worksheets
System Options
[001] Ethernet IP Address
Default (000.000.000.000)
[002] Ethernet IP Subnet Mask
Default (255.255.255.000)
[003] Ethernet Gateway IP Address
Default (000.000.000.000)
[004] Receiver Supervision Interval
Default (0087/135) Valid range: 0000 - FFFF.
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised Default (OFF).
[2] Cellular Receiver 1 Supervised Default (OFF).
[3] Supervision Type Default (OFF).
[4] Primary Communications Path.
Default [OFF] TL2803G(R); [ON] 3G2080(R).
[5] Redundant Communications Default (OFF).
[6] Remote Firmware Upgrade Default (ON).
[7] Alternate Test Transmission Default (OFF).
[8] Cellular Low Signal Trouble Default (OFF).
[006] System Toggle Options 2
[1] Ethernet Receiver 1 Enabled Default (ON).
[2] Ethernet Receiver 2 Enabled Default (ON).
[4] Cellular Receiver 1 Enabled Default (ON).
[5] Cellular Receiver 2 Enabled Default (ON).
[7] DLS Over Cellular Default (ON).
[8] Network Trouble Suppression Default (OFF).
[007] DNS Server IP 1
Default (000.000.000.000)
[008] DNS Server IP 2
Default (000.000.000.000)
[009] Language
Default (01); Program label language 01-29
Programming Options
[010] System Toggle Options 3
[1] Reserved
[2] Visual Verification Default (OFF).
[3] Reserved
[011] Installer Code
Default (CAFE) Valid range: 0000 - FFFF.
[012] DLS Incoming Port
Default (0BF6/3062) Valid range: 0000 - FFFF.
[013] DLS Outgoing Port
Default (0BFA/3066) Valid range: 0000 - FFFF.
[015] DLS Call-Up IP
Default (000.000.000.000)
[016] DLS Call-Up Port
Default (0000) Valid range: 0000 - FFFF.
[020] Time Zone
Default (00) Valid range: 00 - 99.
[021] Account Code
Default (FFFFFF) Valid range: 000001 - FFFFFE.
[022] Communications Format
Default (04) Program 03 (CID), 04 (SIA).
[023] Panel Absent Trouble
Default (FF); Program 00 disable or FF enable.
[024] Panel Absent Trouble Restore
Default (FF) Program 00 disable or FF enable.
[025] Radio Activation Restore
Default (FF) Program 00 disable or FF enable.
System Test Options
[026] Ethernet 1 Transmission
Default (FF) Program 00 disable or FF enable.
[027] Ethernet 2 Transmission
Default (00) Program 00 disable or FF enable.
13

[028] Cellular 1 Transmission
Default (FF) Program 00 disable or FF enable.
[029] Cellular 2 Transmission
Default (00) Program 00 disable or FF enable.
[030] FTC Restore
Default (FF) Program 00 disable or FF enable.
[037] Panel Firmware Update Fail
Default (FF) Program 00 disable or FF enable.
[095] SA Incoming Local Port
Default (0000) Valid range: 0000 - FFFF.
[096] SA Outgoing Local Port
Default (0000) Valid range: 0000 - FFFF.
[097] SA Call Up IP
Default (000.000.000.000)
[098] SA Call Up Port
Default (0000) Valid range: 0000 - FFFF.
[099] SA Password
Default (FFFFFFFF) Valid range: 00000000 - FFFFFFFF.
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
[102] Ethernet Receiver 1 DNIS
Default (000000) Valid range: 000000 - FFFFFF.
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
[104] Ethernet Receiver 1 UDP Remote Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
[105] Ethernet Receiver 1 UDP Local Port
Default (0BF4/3060)Valid range: 0000 - FFFF.
[106] Ethernet Receiver 1 Domain Name
Default ( ) 32 ASCII characters.
________________________________
Ethernet Receiver 2 Options
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
[112] Ethernet Receiver 2 DNIS
Default (000000) Valid range: 000000 - 0FFFFF.
[113] Ethernet Receiver 2 Address
Default (000.000.000.000)
[114] Ethernet Receiver 2 UDP Remote Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
[115] Ethernet Receiver 2 UDP Local Port
Default (0BF9/3065) Valid range: 0000 -FFFF.
[116] Ethernet Receiver 2 Domain Name
Default ( )
____________________________________
Ethernet Options
[124] Ethernet Test Transmission Time
Default (9999) Valid: 00-23(HH); 00-59(MM)
[125] Ethernet Test Transmission Cycle
Default (000000)
Valid range:000000 - 999999 minutes.
Cellular Receiver 1 Options
[201] Cellular Receiver 1 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
[202] Cellular Receiver 1 DNIS
Default (000000) Valid range: 000000 - 0FFFFF.
[203] Cellular Receiver 1 Address
Default (000.000.000.000)
[204] Cellular Receiver 1 Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
14

[205] Cellular Receiver 1 APN Default ( )
32 ASCII characters.
____________________________________
[206] Cellular Receiver 1 Domain Name
Default ( )
32 Character ASCII characters.
____________________________________
Cellular Receiver 2 Options
[211] Cellular Receiver 2 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
[212] Cellular Receiver 2 DNIS
Default (000000)
Valid range: 000000 - 0FFFFF.
[213] Cellular Receiver 2 Address
Default (000.000.000.000)
[214] Cellular Receiver 2 Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
[215] Cellular Receiver 2 APN
Default ( ) 32 ASCII characters.
____________________________________
[216] Cellular Receiver 2 Domain Name
Default ( )
32 ASCII characters.
____________________________________
Cellular Options
[221] Cellular Public Access Point Name
Default ( ) 32 ASCII characters
____________________________________
[222] Cellular Login User Name
Default ( ) 32 ASCII characters.
____________________________________
[223] Cellular Login Password
Default ( ) 32 ASCII characters.
____________________________________
[224] Cellular Test Transmission Time of Day
Default (9999) Valid range: 00 - 23 hrs. (HH) 00 - 59 min.
(MM).
[225] Cellular Test Transmission Cycle
Default (000000)
Valid range:000000 - 999999 minutes.
[226] Network Trouble Delay
Default (0F)
Valid entries from, 00 to FF.
Command and Control Options
[301] Command and Control Toggle Options
[1] SMS Notification (ON).
[2] Reserved
[3] SMS Command and Control Default (ON).
[4] Reserved
[5] SMS Character Format (OFF)
[6] Long SMS Message Handling Default (OFF).
[7] Reserved
[8] Reserved
[311]-[342] SMS Phone Number 1-32
______________________________________________
[343]-[374] SMS Phone Number 1-32 Toggle
Options
[1] SMS Notification Alarm/Restore Default (OFF).
[2] Reserved
[3]SMSNotificationOpening/ClosingDefault(OFF).
[4] Reserved
[5] SMS Notification System Test Default (OFF)
[6] SMS Notification Internal Events Default (OFF).
[7] SMS Notification Enabled Default (OFF).
[8] SMS Command and Control Enabled Default
(ON).
[375]-[406] SMS Phone Number 1-32 Partition
Options
Default (00) Valid range: 00 - FF.
00 - Global; 01-32 - Partition; FF - Disabled
External Event Label Programming
[451] Burglary Alarm
Default (Burglary Alarm)
______________________________________________
[452] Burglary Alarm Restore
Default (Burglary Alarm Restore)
______________________________________________
[453] Fire Alarm
Default (Fire Alarm)
______________________________________________
[454] Fire Alarm Restore
Default (Fire Alarm Restore)
______________________________________________
15

[455] 24 Hour Alarm
Default (24 Hour Alarm)
______________________________________________
[456] 24 Hour Alarm Restore
Default (24 Hour Alarm Restore)
______________________________________________
[457] Holdup Alarm
Default (Holdup Alarm)
______________________________________________
[458] Holdup Alarm Restore
Default (Holdup Alarm Restore)
______________________________________________
[459] Gas Alarm
Default (Gas Alarm)
______________________________________________
[460] Gas Alarm Restore
Default (Gas Alarm Restore)
______________________________________________
[461] High Temperature Alarm
Default (High Temperature Alarm)
______________________________________________
[462] High Temperature Alarm Restore
Default (High Temperature Alarm Restore)
______________________________________________
[463] Medical Alarm
Default (Medical Alarm)
______________________________________________
[464] Medical Alarm Restore
Default (Medical Alarm Restore)
______________________________________________
[465] Panic Alarm
Default (Panic Alarm)
______________________________________________
[466] Panic Alarm Restore
Default (Panic Alarm Restore)
______________________________________________
[467] Emergency Alarm
Default (Emergency Alarm)
______________________________________________
[468] Emergency Alarm Restore
Default (Emergency Alarm Restore)
______________________________________________
[469] Sprinkler Alarm
Default (Sprinkler Alarm)
______________________________________________
[470] Sprinkler Alarm Restore
Default (Sprinkler Alarm Restore)
______________________________________________
[471] Water Level Alarm
Default (Water Level Alarm)
______________________________________________
[472] Water Level Alarm Restore
Default (Water Level Alarm Restore)
______________________________________________
[473] Low Temperature Alarm
Default (Low Temperature Alarm)
______________________________________________
[474] Low Temperature Alarm Restore
Default (Low Temperature Alarm Restore)
______________________________________________
[475] Fire Supervisory
Default (Fire Supervisory)
______________________________________________
[476] Fire Supervisory Restore
Default (Fire Supervisory Restore)
______________________________________________
[477] CO Alarm
Default (CO Alarm)
______________________________________________
[478] CO Alarm Restore
Default (CO Alarm Restore)
______________________________________________
[479] Flood Alarm
Default (Flood Alarm)
______________________________________________
[480] Flood Alarm Restore
Default (Flood Alarm Restore)
______________________________________________
[481] Quick Bypass Alarm
Default (Quick Bypass Alarm)
______________________________________________
[482] Quick Bypass Alarm Restore
Default (Quick Bypass Alarm Restore)
______________________________________________
[483] Aux Alarm
Default (Aux Alarm)
______________________________________________
[484] Aux Alarm Restore
Default (Aux Alarm Restore)
______________________________________________
[485] Zone Expander Supervisory Alarm
Default (Zone Expander Supervisory Alarm)
______________________________________________
[486] Zone Expander Sup. Alarm Restore
Default (Zone Expander Sup. Alarm Restore)
______________________________________________
[487] Duress Alarm
Default (Duress Alarm)
______________________________________________
[500] Account Label
Default (Security System)
______________________________________________
[501] General System Tamper
Default (General System Tamper)
______________________________________________
[502] General System Tamper Restore
Default (General System Tamper Restore)
______________________________________________
16

[503] General System Trouble
Default (General System Trouble)
______________________________________________
[504] General System Restore
Default (General System Restore)
______________________________________________
[505] Panel AC Power Trouble Label
Default (AC Power Trouble)
______________________________________________
[506] Panel AC Power Restore Label
Default (AC Power Restore)
______________________________________________
[507] Panel Auxiliary Power Trouble
Default (Auxiliary Power Trouble)
______________________________________________
[508] Panel Auxiliary Power Restore
Default (Auxiliary Power Restore)
______________________________________________
[509] Panel Battery Trouble
Default (Battery Trouble)
______________________________________________
[510] Panel Battery Restore
Default (Battery Trouble Restore)
______________________________________________
[511] Panel Bell Circuit Trouble
Default (Bell Circuit Trouble)
______________________________________________
[512] Panel Bell Circuit Restore
Default (Bell Circuit Restore)
______________________________________________
[513] Panel Telephone Line Trouble
Default (Telephone Line Failure)
______________________________________________
[514] Panel Telephone Line Restore
Default (Telephone Line Restore)
______________________________________________
[515] Fail to Communicate Trouble
Default (Fail to Communicate Trouble)
______________________________________________
[516] Fail to Communicate Restore
Default (Fail to Communicate Restore)
______________________________________________
[517] Fire Trouble
Default (Fire Trouble)
______________________________________________
[518] Fire Trouble Restore
Default (Fire Trouble Restore)
______________________________________________
[519] Zone Tamper
Default (Zone Tamper)
______________________________________________
[520] Zone Tamper Restore
Default (Zone Tamper Restore)
______________________________________________
[521] Zone Fault
Default (Zone Fault)
______________________________________________
[522] Zone Fault Restore
Default (Zone Fault Restore)
______________________________________________
[523] Alternate Communicator Trouble
Default (Alternate Communicator Trouble)
______________________________________________
[524] Alternate Communicator Restore
Default (Alternate Communicator Restore)
______________________________________________
[525] Module Trouble
Default (Module Trouble)
______________________________________________
[526] Module Trouble Restore
Default (Module Trouble Restore)
______________________________________________
[527] Wireless/AML Device Trouble
Default (Device Trouble)
______________________________________________
[528] Wireless/AML Device Restore
Default (Device Trouble Restore)
______________________________________________
[551] Disarmed By
Default (Disarmed By)
______________________________________________
[552] Armed By
Default (Armed By)
______________________________________________
[553] Disarmed
Default (Disarmed)
______________________________________________
[554] Armed
Default (Armed)
______________________________________________
[555] Automatic Disarming
Default (Automatic Disarming)
______________________________________________
[556] Automatic Arming
Default (Automatic Arming)
______________________________________________
[557] Automatic Arming Cancelled
Default (Automatic Arming Cancelled)
______________________________________________
[558] Late to Open
Default (Late to Open)
______________________________________________
[559] Late to Close
Default (Late to Close)
______________________________________________
[560] Disarmed After Alarm
Default (Disarmed After Alarm)
______________________________________________
17

[561] Alarm Ocurred After Arming
Default (Alarm Ocurred After Arming)
______________________________________________
[562] Exit Fault
Default (Exit Fault)
______________________________________________
[563] Cold Start
Default (Cold Start)
______________________________________________
[564] Armed With Zones Bypassed
Default (Armed With Zones Bypassed)
______________________________________________
[565] Zone Bypassed
Default (Zone Bypassed)
______________________________________________
[566] Zone Unbypassed
Default (Zone Unbypassed)
______________________________________________
[567] Burglary Verified
Default (Burglary Verified)
______________________________________________
[568] Burglary Not Verified
Default (Burglary Not Verified)
______________________________________________
[569] Alarm Cancelled
Default (Alarm Cancelled)
______________________________________________
[570] Holdup Verified
Default (Holdup Verified)
______________________________________________
[571] Walk Test Begin
Default (Walk Test Begin)
______________________________________________
[572] Walk Test End
Default (Walk Test End)
______________________________________________
[573] System Test
Default (Test Message)
______________________________________________
[574] Periodic Test Transmission
Default (Periodic Test)
______________________________________________
[575] Periodic Test With Trouble
Default (Periodic Test With Trouble)
______________________________________________
[576] DLS Remote Programming Begin
Default (Remote Programming Begin)
______________________________________________
[577] DLS Remote Programming End
Default (Remote Programming End)
______________________________________________
[578] SA Remote Programming Begin
Default (Remote Programming Begin)
______________________________________________
[579] SA Remote Programming End
Default (Remote Programming End)
______________________________________________
[580] Installer Lead In
Default (Local Programming Begin)
______________________________________________
[581] Installer Lead Out
Default (Local Programming End)
______________________________________________
[582] Firmware Update Begin
Default (Firmware Update Begin)
______________________________________________
[583] Firmware Update Successful
Default (Firmware Update Successful)
______________________________________________
[584] Firmware Update Fail
Default (Firmware Update Fail)
______________________________________________
[585] Delinquency
Default (Delinquency)
______________________________________________
[586] Keypad Lockout
Default (Keypad Lockout)
______________________________________________
[587] Event buffer 75% full
Default (Event Buffer Near Full)
______________________________________________
[591] FTC Trouble
Default (fail to communicate trouble)
______________________________________________
[592] FTC Restore
Default (fail to communicate restore)
______________________________________________
[593] Panel Absent Trouble
Default (Panel Communications Trouble)
______________________________________________
[594] Panel Absent Trouble Restore
Default (Panel Communications Restore)
______________________________________________
[595] Module Reprogramming
Default (Communicator Programming Updated)
______________________________________________
[596] Firmware Update
Default (Communicator Programming Updated)
______________________________________________
[600] Module
Default (Module)
______________________________________________
[601] Stay Arm
Default (Stay Arm)
______________________________________________
[602] Away Arm
Default (Away Arm)
______________________________________________
18

[603] Night Arm
Default (Night Arm)
______________________________________________
[604] Disarm
Default (Disarm)
______________________________________________
[605] Activate Command Output 1
Default (Activate Command Output 1)
______________________________________________
[606] Activate Command Output 2
Default (Activate Command Output 2)
______________________________________________
[607] Activate Command Output 3
Default (Activate Command Output 3)
______________________________________________
[608] Activate Command Output 4
Default (Activate Command Output 4)
______________________________________________
[609] Deactivate Command Output 1
Default (Deactivate Command Output 1)
______________________________________________
[610] Deactivate Command Output 2
Default (Deactivate Command Output 2)
______________________________________________
[611] Deactivate Command Output 3
Default (Deactivate Command Output 3)
______________________________________________
[612] Deactivate Command Output 4
Default (Deactivate Command Output 4)
______________________________________________
[613] Bypass
Default (Bypass)
______________________________________________
[614] Unbypass
Default (Unbypass)
______________________________________________
[615] Status Request
Default (Status Request)
______________________________________________
[616] Alarm Memory Request
Default (Alarm Memory Request)
______________________________________________
[617] Help
Default (Help)
______________________________________________
[618] Pay As You Go Balance Request
Default (Balance Request)
______________________________________________
[619] Keypad Message
Default (Keypad Message)
______________________________________________
[621] Function Successful
Default (Successful)
______________________________________________
[622] Function Failure
Default (Unsuccessful)
______________________________________________
[623] Invalid Command
Default (Invalid Command)
______________________________________________
[624] System Stay Armed
Default (Stay Armed)
______________________________________________
[625] System Away Armed
Default (Away Armed)
______________________________________________
[626] System Night Armed
Default (Night Armed)
______________________________________________
[627] System Disarmed Ready
Default (Disarmed Ready)
______________________________________________
[628] System Disarmed, Not Ready
Default (Disarmed Not Ready)
______________________________________________
[629] System In Alarm
Default (is in Alarm)
______________________________________________
[630] Trouble Label
Default (Service is Required)
______________________________________________
[631] No Alarms in Memory
Default (No Alarms in Memory)
______________________________________________
[632] Pay As You Go Balance
Default (Pay as you go balance:)
______________________________________________
[633] Pay As You Go Message
Default (*123#)
______________________________________________
[634] Response Code
Default (Response Code)
______________________________________________
[651] Integration Identification Number
Default ()
[652] Integration Access Code
Default ()
[663] Integration Toggle Options 2
[1] Integration Over Serial Port (ON)
[2] Integration Over Cellular (OFF)
[3] Integration Over Ethernet (OFF)
[4] Reserved
19

[5] Integration Protocol (ON)
[6] Reserved
[7] Reserved
[8] Reserved
[664] Integration Toggle Options 3
[1] UDP Polling (OFF)
[2] TCP Polling (OFF)
[3] Real-time Notification (OFF)
[4] Notification Follows Pool (OFF)
[5] Reserved
[6] Reserved
[7] Reserved
[8] Reserved
[665] Interactive Polling Interval in Seconds
Default (000A) Valid range: 0000 - FFFF.
[693] Integration Server IP
Default (000.000.000.000)
[694] Integration Notification Port
Default (0C00/00372) Valid range: 0000 - FFFF.
[695] Integration Polling Port
Default (0C01/3073) Valid range: 0000 - FFFF.
[697] Integration Server DNS
32 ASCII characters.
____________________________________
[698] Integration Outgoing Port
Default (0C04/3076) Valid range: 0000 - FFFF.
[699] Integration Incoming Port
Default (0BFF/3071) Valid range: 0000 - FFFF.
Receiver Diagnostic Testing
[901] Diagnostic Test Transmission
[1] Ethernet 1 Default (OFF).
[2] Ethernet 2 Default (OFF).
[3] Cellular 1 Default (OFF).
[4] Cellular 2 Default (OFF).
System Information (Read Only)
[983] Firmware Update Diagnostics Section
[984] Communicator Status
[985] Radio Initialization Status
[987] Language Version
[988] DNS 1 IP Address
[989] DNS 2 IP Address
[990] Boot Loader Version
[991] Firmware Version
[992] Ethernet IP Address
[993] Ethernet Gateway Address
[994] Cellular IP Address
[995] SIM Number
____________________________________
[996] Cellular Telephone Number
This number is required for DLS and Firmware upgrades.
____________________________________
[997] IMEI Number
____________________________________
[998] MAC Address
System Reset Defaults
[999] Software Default
Default (99); Valid entries are 00, 11 or 55
20
Other manuals for 3G2080
1
This manual suits for next models
3
Table of contents
Other DSC Cell Phone manuals

DSC
DSC 3G2075 User manual

DSC
DSC 3G4010 User manual

DSC
DSC Skyroute CL3050 Operating instructions

DSC
DSC GS3125 Series User manual

DSC
DSC T-Link TL300 User manual

DSC
DSC 3G3070 User manual

DSC
DSC TL280R Operating and maintenance instructions

DSC
DSC T-LINK TL250 User manual

DSC
DSC 3G2060 User manual

DSC
DSC PowerSeries Neo LE2080 User manual