READ THIS FIRST:
Check the pack and make sure you have all of the
parts listed on the front of this booklet. If not,
contact the outlet where you bought this product.
As the buyer, installer and/or user of this product it
is your own responsibility to ensure that this tting
is t for the purpose for which you have intended
it. Eterna Lighting cannot accept any liability for
loss, damage or premature failure resulting from
inappropriate use.
Switch o the mains before commencing installation
and remove the appropriate circuit fuse or lock o
MCB.
Use only with the driver/inverter provided. Do not
connect directly to the mains.
This unit is suitable for indoor use only.
This product is designed for permanent connection
to xed wiring: this must be a suitable circuit
(protected with the appropriate MCB or fuse).
Do not cover the tting, battery and driver with any
insulating materials.
The driver should be placed where it cannot come
into contact with water or moisture.
You are advised at every stage of your installation to
double-check any electrical connections you have
made. After you have completed your installation
there are electrical tests that should be carried out,
these tests are specied in the current IEE wiring and
building regulations.
INSTALLATION:
Choose the location for the new tting taking the
above points into consideration.
1) Mark the locations of your downlight and then
using an appropriate hole cutter, make a 32mm
diameter hole. (See below).
2) Prepare the route for the mains cable and feed
through the hole and make the connections to the
input side of the driver/inverter.
3) Feed the driver/inverter through the hole,
followed by the battery pack, which can lay
adjacent to the hole.
4) Feed the excess cable through the hole and press
the down light into position (see below) until it is
retained by the springs. The tting may require
some manipulation in order to pass through the
hole. Do not enlarge the hole to make tting
easier.
5) Restore the power and check tting is working
correctly. The LED will illuminate green on normal
operation, which indicates the tting is charging.
On mains power failure the LED will illuminate
white light continuously for a minimum of 3 hour
SPECIFICATION:
EBLF: 0.92
OPERATION CHECKS:
Periodic testing should be carried out monthly by simulating a failure of supply, causing the tting to be
energised from its battery. Interruption of the supply should be carried out by the operation of a local key
switch or other isolation device. During this period all ttings should be examined visually to ensure that they
are functioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or
devices checked to ensure that the normal supply has been restored.
The duration of the simulated failure shall be:-
Each month:
Isolate the power supply and check the light is illuminated. This test should last for only a short period.
Endorse the test record form supplied.
Once each year:
Isolate the power supply and check that the light is still illuminated after 3 hours. Endorse the test record form.
IMPORTANT NOTE:
Please keep this instruction booklet and test record sheet with all recorded test data in a safe place.
A re ocer or other authorised person may want to see your record of inspection and testing.
DRIVER
L
E
N
BATTERY
INPUT 220-240VAC
50/60Hz
1.5W LED
Dia = 32mm
NEUTRAL
EARTH
LIVE
Ceiling
Ceiling
Clips will lock
fitting into place