
To eliminate false alarm hazards
1) It is recommended to close all doors, air-
vents, switch off fans, air-conditioners and other
sources of intense air flows in the room during
protection period.
2) It is not recommended to operate the detec-
tor in a room with high level of microwave inter-
ference (electro-magnetic signals, vibrating
metallic objects, sources of movement behind
thin partitions).
Not recommended installation place
7 INSTALLATION PROCEDURE
3a) Installation on the wall
3b)Installation in the corner
Detector`s base should be positioned
strictly as per figure!
3c) Installation using
bracket
4) Replace PCB and
perform wiring (see
sec.8).
5) perform testing of
MW-channel and PIR-
channel (see sec.9).
8 WIRING
Perform wiring to detector`s terminals in
accordance with control panel operating manual.
TMP –detector tampering control terminals;
RES –terminating resistor connection terminal;
RELAY –terminals for detector connection to
alarm loop (zone);
GND, +12V –power supply terminals.
9 TEST
MW - channel:
1) Install jumpers on Ind and Mode plugs.
Remove jumper from Mem
plug.
2) Power detector ON.
Red and blue indicators
shall alternatively blink for
not more than 60 sec.
3) During this time
4) Assemble the detector.
5) To detect sensitive zones carry out TEST-
pass in the secured zone with the speed of 1
m/sec. Stop upon detection (indicator is lighted
red twice for 0.25sec), mark position, then
make a step back and continue moving
forward.
Repeat TEST-pass inversely.
PIR- channel:
1) Install jumpers on Ind and Mode plugs.
Remove jumper from Mem plug.
2) Power detector ON. Red and blue indicators
shall alternatively blink for not more than 60
sec.
3) During this time
4) Assemble the detector.
5) To detect sensitive zones
carry out TEST-pass in the
secured zone with the speed
of 0,3 and 3 m/sec.
Stop upon detection
(indicator lights up for 2sec),
mark position, then make a
step back and continue
moving forward.
Repeat TEST-pass inversely.
10 WARRANTY
The operation warranty period is 5 years from
the date of operation start-up but no longer than
5 years 6 months from the date of manufactur-
ing subject to the requirements of Operating
Manual.