Dinel CLM-36 User manual

Before level meters usage please read instructions in this service manual and keep it for further use. Service
manual is for all types of level meters series CLM-36. Producer reserves the right to make changes without any
previous announcement.
INSTRUCTIONS MANUAL
průmyslová elektronika
CapaCitive level meters Clm – 36


Obsah
1 . Measuring principle .................................................................................................................3
2 . Range of applications..............................................................................................................3
3 . Features of variants .................................................................................................................4
4 . Dimensions drawings ..............................................................................................................5
5 . Inuence of the tank shape on a linearity of measurement.................................................7
6 . Installation and putting into operation...................................................................................8
7 . Installation ................................................................................................................................8
8. Electrical connection ...............................................................................................................11
9. Preparing of level meter for measuring..................................................................................12
10. Setting .....................................................................................................................................13
11 . Use, manipulation and maintenance....................................................................................15
12 . Order code ..............................................................................................................................16
13 . Correct specication examples ............................................................................................16
14 . Accessories ............................................................................................................................16
15 . Safety, protections, compatibility and explosion proof .....................................................17
16 . Marking of labels....................................................................................................................18
17 . Specication...........................................................................................................................20
18 . Table of relative permittivity .................................................................................................24

CLM–36 © Dinel, s.r.o.
3
1 . Measuring principle
Capacitive level meters CLM® are designed for continuous level measurement of liquids, powders
and bulk-solid materials in vessels, tanks, sumps, containers, silos, etc. CLM consists of the stainless
steel housing with electronic module and the measuring electrode. Type of measuring electrode is
dened by kind of use and type of measured media. The electronic part converts the capacity into
the current signal (4 ... 20 mA) or voltage signal (0 ... 10 V). Sensitivity (SPAN) and initial capacity
compensation (ZERO) can be uently set. CLMs are offered in version (N) for non-hazardous
environments or (Xi) version to explosive areas up to zone 0 or zone 20, high temperature performance
and several types of process coupling are also available.
2 . range of applications
Capacitive level meters are suitable for continuous level measurement of liquid and bulk-solid
materials. CLMs are resistant to any changes in the atmosphere above the surface (vacuum,
pressure, vapours, dust). It is also partially resistant to the formation of foam on the surface.
All operations described in this instruction manual have to be carried out only by trained
personnel or an accredited person. Warranty and post warranty service must be exclusively
carried out by the manufacturer.
Improper use, installation or set-up of the level meter can result in crashes in the application
(overlling of the tank or damage of system components).
The manufacturer is not responsible for improper use, losses of work caused by either direct
or indirect damage, and for expenses incurred during installation or use of the level meter.
safety
used syMbols
To ensure maximum safety of control processes, we have dened the following safety instructions
and information. Each instruction is labeled with the appropriate pictogram.
Alert, warning, danger
This symbol informs you about particularly important instructions for installation and
operation of equipment or dangerous situations that may occur during the installa-
tion and operation. Not observing these instructions may cause disturbance, dam-
age or destruction of equipment or may cause injury
Information
This symbol indicates particularly important characteristics of the device.
Note
This symbol indicates helpful additional information.
Valid for:
In the border are the types CLM, for which is intended the chapter.
all types

4
© Dinel, s.r.o. CLM–36
3 . features of variants
CLM –36_–10 With uncoated rod electrode for level measurement of non-conductive
liquids (oils, diesel, petrol) and powder or bulk-solid materials (our, sand,
cement, plastic granulates, etc.). Max. length 5m.
CLM –36_–11 With fully (PFA) coated rod electrode for level measurement of water and
conductive liquids incl. wasted liquids in metallic vessels, concrete sumps,
reservoirs, etc., better behaviour against aggressive media, lower adhesion
to some complicated media, chemical resistance. Max. length 3m.
CLM –36_–12 With fully (FEP) coated rod electrode for level measurement of water and
conductive liquids incl. wasted liquids in metallic vessels, concrete sumps,
reservoirs, etc., better behaviour against aggressive media, lower adhesion
to some complicated media, chemical resistance. Max. length 3m.
CLM –36_–20 With uncoated rod electrode and reference tube for accurate level meas-
urement of clean non-conductive liquids (oils, diesel, petrol). By means of
reference tube the output signal does not depend on the dimensions and
shapes of a vessel. Max. length 3m.
CLM –36_–22 With fully FEP coated rod electrode and reference tube for accurate level
measurement of conductive liquids. Main use is for measurement in plastic
vessels or tanks. Impossible to use for waste and high viscosity liquids and
bulk-solid materials. Max. length 3m.
CLM –36_–30 With uncoated stainless steel rope electrode and uncoated weight
for level measurement of bulk-solid materials (grains, sand, our, cement,
etc.). Max. length 20m.
CLM –36_–31 With uncoated stainless steel rope electrode and coated dynamic
anchorage for level measurement of bulk-solid materials in higher silos.
Max. length 20m.
CLM –36_–32 With fully coated rope electrode and coated weight (rope insulation FEP,
weight insulation PTFE), for level measurement of electrically conductive
and non-conductive liquids. Max. length 20m.
CLM –36_–40 With two coated electrodes (rode insulation FEP, head fully PTFE), for
level measurement of aggressive liquids. Performance for non-explosive
areas only. Max. length 2m.

CLM–36 © Dinel, s.r.o.
5
CLM–36_–30
4 . diMensions drawings
CLM–36_–10, 11, 12 CLM–36_–20, 22 CLM–36_–32 CLM–36_–40
Thread*
* Threads : M36x2; G1"
Fig. 1: Dimensional drawings of the capacitive level meters

6
© Dinel, s.r.o. CLM–36
High temperature variants
CLM–36_T
CLM–36_–31
Rope electrode
Wall of container
(KV–31, PR–31)**
Spring
Anchor with
spherical joint
** Anchor welding cylinder KV–31 or Dust-tight
bushing PR–31 (see accessories)
Housing with
Tri-clamp coupling
Fig. 2: Dimensional drawings of the capacitive level meters

CLM–36 © Dinel, s.r.o.
7
5 . influence of the tank shape on a linearity of MeasureMent
• In a curved tanks (most frequently
horizontal cylinder) capacity change
during measuring of electrically
non-conductive material is non-linear.
• Linearity is done by reference tube
(CLM–36_–20, 22), or by reference
electrode (CLM–36_–40).
• In the tank with straight wall (for
example vertical cylinder) and with
the sensor placed parallely with the
wall capacity change is linear.
• For sensors with two electrodes (in
the tank with straight or curved wall)
is the capacity change linear.
CLM-36_-10, 11, 12
CLM-36_-30, 31, 32
CLM-36_-20, 22, 40
all types
CLM-36_-40
Fig. 3: Inuence of the tank shape on a linearity of measurement

8
© Dinel, s.r.o. CLM–36
BASIC INFORMATION
Level meters with coated electrode have protection cover at the end of electrode, which is necessary
take down before mounting.
Level meters mount in vertical position to upper lid of tank or reservoir by steel welding
ange ON-36x2 (steel 11375), stainless steel welding ange NN-36x2 (stainless steel 1.4301),
xing nut UM-36x2 (stainless steel 1.4301) or Clamp ange.
For mounting level meter to the metal tank or reservoir is not necessary to ground housing
again.
In case of installation in concrete sumps or silos it is properly to install level meter at metallic
auxiliary construction (console, lid, etc.) and then connect with metal all the time submerged object,
eventually with steel armouring.
For measuring of material in plastic and glass vessels by level meter without reference tube
is necessary to connect grounding screw at housing with auxiliary electrode which is xed by the
appropriate method to the outer casing of vessels (or at inner wall). Material of auxiliary electrode
is necessary to choose with consideration to the working environment and properties of measured
material.
Please follow next 4 steps:
• installation
• electrical connection
• preparing of level Meter for Measuring
6 . installation and putting into operation
7 . installation
CLM-36_-10, 11, 12
METAL AND NON-METAL VESSESLS
E- the length of electrode
[mm] - the end of the electrode
has to be dipped min. 20 mm
below the lowest measured level
h- the distance from the
bottom - min. 50 mm
a- the distance from the wall -
min. approx. E/20
d- the diameter of auxiliary
tube vessel - min. 40 + E/20
(smaller dimension has to be
discussed with producer)
auxiliary electrode
width = min. 30 mm
(necessary only for
non-metal vessels)
Fig. 4: Installation of level meter with rod electrode
• setting

CLM–36 © Dinel, s.r.o.
9
VARIANTS WITH REFERENCE TUBE
CLM-36_-20, 22
h- the distance from the bottom
- min. 50 mm with respect on
possibility of presence of heavy
fraction (water) in oil products
k- the distance from the wall -
optional
DEEP VESSELS, CONTAINERS AND SILOS
CLM-36_-30, 32
connection to the armouring
E– The length of electrode - the lower end of the electrode has to be
dipped - min. 20 mm below the lowest measured level
h– The distance from the bottom - min. 100 mm
a– The distance from the wall - at least E/20, as far as possible
from the walls, to the middle between the wall and the vertical inlet
concrete silo
metal tank
Fig. 5: Installation of level meter with reference tube
Fig. 6: Installation of level meter with rope electrode

10
© Dinel, s.r.o. CLM–36
ROPE ELECTRODE WITH ANCHOR
CLM-36_-31
E- the length of electrode [mm]
c- the distance from the centre line of
the silo - has to be as minimal as possible
t- the length of the conduction rod -
approx. 500 mm
p- the length of the press spring -
approx. 200 mm
steel anchor welding cylinder
(mat. 11375) or
dust-tight bushing
to be welded into the conical
bottom wall
AGGRESSIVE LIQUIDS, NON-METALLIC VESSELS
CLM-36N_-40
E– The length of electrodes
the lower end of the electrodes
have to be dipped min. 20 mm
below the lowest measured level.
h– The distance from the bottom
min. 30 mm
a– The distance from the wall
(min. ca. E/20)
Fig. 7: Installation of rope electrode with anchor
Fig. 8: Installation of level meter with reference electrode
Forcorrectfunctionof level type CLM-36N_-40 isnecessarytoensurethe impedance between
of the measured medium and ground. This can be provided by:
1) The medium is isolated from all devices that may cause temporary grounding of the medium
(pumps, valves, connection with the grounded tank by owing medium).
2) If the rst option is not possible, it is necessary to ground the medium permanently.

CLM–36 © Dinel, s.r.o.
11
8 . electrical connection
The level meter is designed to be connected to supply unit or to controller through a cable with the
outer diameter of 6 ÷ 8mm (recommended cross-section of cores 0.5 ÷ 0.75 mm2) by means of
connector which is included in delivery. The scheme and the inside of the connector are on pictures.
Procedure to connect the cable to the level
meter:
1. Unscrew connector from the body of the level
meter using a suitable screwdriver.
2. Use a at screwdriver to remove the inner
part of the connector (screwdriver into the
gap marked by arrow).
3. Unscrew the cable gland and put the cable
inside.
4. Connect the cable wires to the screw termi-
nals as shown in Fig. 10 (current output 4-20
mA) or Fig. 12 (voltage output 0-10 V). Tigh-
ten the terminals rmly.
5. Push the terminals back into the connector so
that the terminal no. 3 is oriented toward the
cable entry. Tighten the cable gland.
6. Check the seal on the connector and connect
the connector back to the body of the sensor.
Electrical connection must be done in de-energized state!
The voltage source should be preferably realized as a stabilized power supply unit with safe voltage from
18 to 36 V DC (18 ÷30 V DC at version Xi(XiT)), which can be a part of the evaluation or display device.
In case of strong electromagnetic interferences (EMI), parallel cable ducting with power lines, or when
cable length exceeds 30 m we recommended to use shielded cable.
Fig. 9: Connection scheme with current
output
Shielding
(Green-Yellow)
+U (Brown)
0V (Blue)
Fig. 10: Connection scheme with
current output
Uout (Black)+U (Brown)
Shielding
(Green-Yellow)
0V (Blue)
Fig. 11: Connection scheme with voltage
output
Fig. 12: Connection scheme with
voltage output

12
© Dinel, s.r.o. CLM–36
9 . preparing of level Meter for Measuring
PREPERING OF LEVEL METER
1. For access to the adjustment elements disconnect a connector and unscrew a nut
(attention for inside connecting wires). Connector connect again.
2. Level meter connect to the supply unit through miliampermeter (controller, etc.).
3. Trimmer1) 20 mA bring into the basic position (this position is set by producer):
a) Turn out trimmer totally right wards (in clockwise).
b) Return back for 3 turns left wards.
1) The trimmers are without backstops - approx. 15 turns.
ADJUSTMENT ELEMENTS OF LEVEL METER
Fig. 13: The top view on the internal electronic module with
current outptu (variant –I)
DIP switches
(for range select)
trimmer 4 mA
(for compensation
of initial capacity)
trimmer 20 mA
(for sensitive span
adjustment)
blue wire
(-) brown wire
(+)
green-yellow wire
( )
brass tie
(for pull out of
elecronic module)
DIP switches
(for range select)
trimmer 0 V
(for compensation of
initial capacity) trimmer 10 V
(for sensitive span
adjustment)
green-yellow wire
( )
black wire
(Uout)
brass tie
(for pull out of
elecronic module)
0V 10V
Fig. 14: The top view on the internal electronic module with
voltage outptu (variant –U)
blue wire
(-)
brown wire
(+)

CLM–36 © Dinel, s.r.o.
13
10 . setting
1. Empty tank to the minimum level.
2. By DIP switches on level meter set range3) No. 2 (250 pF).
3. Turn by screwdriver in trimmer 4 mA and set quiescent current of the level meter to
4 mA. Turning right wards (in clockwise) increase the current, turning left wards
decrease the current. When is impossible to set required current to 4 mA, then switch
DIP switches to the nearest higher range and set up of current 4 mA perform at this range.
4. Fill the tank to the maximum level. When it is impossible ll the tank to the maximum
state then we use some known (measurable) level and current for next setting
calculate according to formula:
I
out = 4 + (0,16 x level in %) [mA]
5. If the output current is less than 20 mA (or the value of I out), set to the lowest
range No. 1. by DIP switches and continue to step 7. When the output current reaches
20 mA, continue on step 6.
6. By DIP switches step wise switch to higher ranges till the current is greater then
20 mA (or calculated value I out), through level meter then ows current e.g. 21 mA4).
Trimmer 20 mA is still in basic position.
7. Then set by trimmer 20 mA current of level meter to 20 mA (or to calculated value I out
- see bellow).
8. To reach a maximum accuracy is useful to check over the setting of 4 mA
(compensation of initial capacity - quiescent current).
2) Sensitivity - minimal capacity change of electrode to reach output range 4 ÷ 20 mA or 0 ÷10 V.
3) Range = capacity of housing + activated electrode to reach output range 4 ÷ 20 mA or 0 ÷10 V.
(For example.: uncoated electrode 1000 mm immersion in fuel: 20 pF + 30 pF,
coated electrode 1000 mm immersion in water: 20 pF + 500 pF)
4) In case of short of electrode on housing or setting of a very sensitive range can caused to current
restriction of level meter on value max. 30 mA.
CURRENT OUTPUT 4 ... 20 mA
VOLTAGE OUTPUT 0 ... 10 V
1. Empty tank to the minimum level.
2. By DIP switches on level meter set range3) No. 2 (250 pF).
3. Turn by screwdriver in trimmer 0 V and set voltage output of the level meter to
0 V. Turning right wards (in clockwise) increase the voltage, turning left wards
decrease the voltage. When is impossible to set required voltage to 0 V, then switch
DIP switches to the nearest higher range and set up of voltage 0 V perform at this range.
4. Fill the tank to the maximum level. When it is impossible ll the tank to the maximum
state then we use some known (measurable) level and voltage for next setting
calculate according to formula:
U
out = 0,1 x level in % [V]
5. If the output voltage is less than 10 V (or the value of U out), set to the lowest
range No. 1. by DIP switches and continue to step 7. When the output voltage reaches
10 V, continue on step 6.

14
© Dinel, s.r.o. CLM–36
Medium Sand, grains Cement Flour
Type 1 m 5 m 1 m 5 m 1 m 5 m
10232413
12232413
30232413
Medium Water Benzine, petroleum, diesel, oile
Type 1 m 2 m 1 m 2 m
10 - - 1 2
12 3 4 1 2
20 - - 2 3
22 3 4 2 3
32 3 4 1 2
Note: Types 10, 12, 30, 31, 32 in distance 250 mm from conducting wall.
Showned ranges are orientation. Exact range for existing conguration electrode / tank must be
set directly in application on mearured medium.
Tab. 2: Tables of recommended ranges depending on the medium and
the type of level meter
No. Sensitivity 2)
(S)
Range 3)
(R)
Position of
DIP switch
11) 20 pF 70 pF
2 30 pF 250 pF
3 50 pF 600 pF
4 100 pF 1 200 pF
5 150 pF 3 000 pF
6 300 pF 7 000 pF
7 500 pF 18 000 pF
8 1 000 pF 36 000 pF
1) Range No. 1 (70 pF) is very sensitive and we recommend to use it only at level meters with short
electrode (approx. to 500 mm) and measured media with low permittivity.
Tab. 1: Table of ranges
6. By DIP switches step wise switch to higher ranges till the voltage is greater then
10 V (or calculated value U out), output voltage of the level meter is then e.g. 10,5 V.
Trimmer 10 V is still in basic position.
7. Then set by trimmer 10 V voltage of level meter to 10 V (or to calculated value U out
- see bellow).
8. To reach a maximum accuracy is useful to check over the setting of 0 V.

CLM–36 © Dinel, s.r.o.
15
11 . use, Manipulation and Maintenance
MAINTAINCE OF LEVEL METER
Maintenance of this equipment consists in verication of integrity of the level meter and of the sup-
ply cable. Depending on the character of the substance measured, we recommend to verify at least
once per year the clarity of the ultrasound transducer emitting eld and to clean it, respectively. In
case any visible defects are discovered, the manufacturer or reseller of this equipment must be
contacted immediately.
REPLACEMENT OF DEFECTIVE ELECTRONIC
In case of detected electronic failure it is possible to replace the electronic module directly in
process place of level meter by following procedure:
1. Disconnect connector and unscrew a nut (attention for inside connecting wires).
2. Defective electronic module pick up by pliers onto brass tie and remove by tensile
from housing of level meter.
3. Check placing of white seal O-ring in housing and on pressure ring.
4. Repaired or new electronic module return back into housing of level meter and press
down by clamping ring (attention that contact pin will be a little open before insertion
and contact springs were not pressed under level of electronic casing).
5. Check placing of black seal O-ring on connector.
6. Screw a nut back (attention for inside connecting wires) and connect the connector.
contact pin
contact springs
brass tie
electronic
module cover
trimmers
The level meter does not require any personnel for its operation. Follow-up displaying device is
used to inform the technological entity operating personnel on the measured substance level height
during the operation.
It is forbidden to perform any modications or interventions into the CLM–36 level meter
without manufacturer's approval. Potential repairs must be carried out by the manufacturer
or by a manufacturer authorized service organization only.
Installation, commissioning, operation and maintenance of the CLM–36 level meter has to
be carried out in accordance with this instruction manual; the provisions of regulations in
force regarding the installation of electrical equipment have to be adhered to.
The level meter must be installed to prevent tensile overload of the rope electrode.
Fig. 15: Side view of the electronic module

16
© Dinel, s.r.o. CLM–36
12 . order code
Standard – included in the level meter price
• 1x of seal, other seals are on request (PTFE,
Al, etc.)
• 1x connector socket
13 . correct specification exaMples
Electrode performance:
10 – Uncoated St. steel rod electrode
11 – Fully coated St. steel rod electrode (PFA)
12 – Fully coated St. steel rod electrode (FEP)
20 – Uncoated St. steel rod electrode with reference tube
22 – Coated St. steel rod electrode with reference tube (FEP)
30 – Uncoated St. steel rope electrode and weight (max. 20 m)
31 – Uncoated St. steel rope electrode with anchor (max. 20 m)
32 – Fully coated rope electrode and weight (FEP + PTFE)
40 – Two fully coated St. steel rod electrode (FEP) (max. 2 m)
CLM – 36 – – – E Length electrode in mm
Process connection:
M– thread M36x2
G – thread G1" (G1½" for CLM–36_–40)
Cl – Tri-clamp
Output type:
I– current (4 ... 20 mA)
U – voltage (0 ... 10 V)
Performance:
N– normal (for non-explosive areas)
Xi – Explosion proof - intrisically safe for hazardous (explos
ive) areas, only with "I" output (except CLM-30_-40)
NT, XiT – High temperature performance
14 . accessories
CLM–36N–10–G–I E1100 CLM–36NT–12–M–I E1500
CLM–36Xi–20–M–I E900 CLM–36Xi–30–M–I E12000
CLM – 36N–32–G–U E6000 CLM– 36N–12–Cl–I E2000
• 1x screwdriver for adjustment (each
5 pcs)
• Distance element for rods longer
than 50cm (for CLM–36_–40)

CLM–36 © Dinel, s.r.o.
17
Optional (see datasheets "Accessories")
• Connector with protection class IP67
(GAN–DADE 7A) with 5m cable (current
output)
• Connector with protection class IP67
(GAN–DAAE 7A) with 5m cable (voltage
output)
• Steel welding ange ON–36x2
• St. steel welding ange NN–36x2
Level meter CLM–36 is equipped with protection against electric shock on electrode, reverse polarity,
output current overload, short circuit and short time over voltages.
Protection against dangerous contact is secured by low safety voltage that complies with
EN 33 2000-4-41.
Electromagnetic compatibility is provided by conformity with standards: EN 55022/B, EN 61326-1,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6.
Explosion proof of CLM–36Xi is examined by FTZÚ-AO 210 Ostrava - Radvanice certicate No.:
FTZÚ 02 ATEX 0235X.
Special conditions for safe use of variant CLM–70Xi
Equipment is designed to be connected to isolating repeater IRU-420
If other approved apparatus is used, which output parameters comply with above mentioned input
parameters it is necessary to have an galvanic separation or in a case of apparatus without galvanic
separation (Zener barriers) it is necessary to provide equipotential equalizing between sensor and
barrier earthing point.
Design CLM-36Xi can be used in zone 0 or zone 20. With design CLM-36XiT can be only used in
zone 0 and zone 20 electrode part and head with electronics can be used only in zone 1 or zone 21.
Maximum temperature of electrodes is equal to temperature of measured medium.
When used in zone 0 the present explosive atmosphere of air mixture and gases, vapours or mists
must comply with: - 20°C < Tamb < 60°C 0,8 bar < p < 1,1 bar
15 . safety, protections, coMpatibility and explosion proof
• St. steel xing nut UM–36x2
• Anchor welding cylinder KV–31
(only CLM–36–31)
• Dust-tight bushing PR–31
(only CLM–36–31)

18
© Dinel, s.r.o. CLM–36
Level meters label data
CLM–36N(T)–_ _–_–I:
16 . Marking of labels
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷10V
out
U=16÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷5V
out
U=11÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
I = 4 ... 20 mAU=9...36V
Dinel U
t = -40 ... +85 °C
a
IP65
IP67
0V
1
2
II1D ICT83°CDaExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36Xi-__-__-I E_____ No.: ______
IP65
IP67
1026
II1G BT5GaExiaII
II1/2D ICT83°CDa/DbExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36XiT-__-__-I E_____ No.: ______
IP65
IP67
1026
II1/2G BT5Ga/GbExiaII
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-I E_____ No.: ______
Symbol of producer
:
logo Dinel®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-N_-__-_-I, P/N include length of electrode: E in mm
Serial number: Ser. No.:
______
-
(
from the left: production year, serial production number
)
Supply voltage: Ui= 9 ÷ 36 V DC
Output current range: I = 4 ÷ 20 mA
Ambient temperature range: ta= -40 ... +85 °C
Protection class: IP 65 / IP 67
Compliance mark:
Electro-waste take-back system mark:
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
U =0÷10V
out
U=16÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷5V
out
U=11÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
I = 4 ... 20 mAU=9...36V
Dinel U
t = -40 ... +85 °C
a
IP65
IP67
0V
1
2
II1D ICT83°CDaExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36Xi-__-__-I E_____ No.: ______
IP65
IP67
1026
II1G BT5GaExiaII
II1/2D ICT83°CDa/DbExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36XiT-__-__-I E_____ No.: ______
IP65
IP67
1026
II1/2G BT5Ga/GbExiaII
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-I E_____ No.: ______
Level meters label data
CLM–36N(T)–_ _–_–U:
Symbol of producer
:
logo Dinel®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: Ui, Uout, 0V, GND
Type of level meter: CLM-36-N_-__-_-U, P/N include length of electrode: E in mm
Serial number: Ser. No.:
______
-
(
from the left: production year, serial production number
)
Supply voltage: Ui= 9 ÷ 36 V DC
Output voltage range: Uout = 0 ÷ 10 V (or 0 ÷ 5 V)
Ambient temperature range: ta= -40 ... +85 °C
Protection class: IP 65 / IP 67
Compliance mark:
Electro-waste take-back system mark:

CLM–36 © Dinel, s.r.o.
19
Level meters label data
CLM–36Xi:
Level meters label data
GRLM–70XiT:
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷10V
out
U=16÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷5V
out
U=11÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
I = 4 ... 20 mAU=9...36V
Dinel U
t = -40 ... +85 °C
a
IP65
IP67
0V
1
2
II1D ICT83°CDaExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
Czech Republic
CLM-36Xi-__-__-I E_____ No.: ______
IP65
IP67
1026
II1G BT5GaExiaII
II1/2D ICT83°CDa/DbExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36XiT-__-__-I E_____ No.: ______
IP65
IP67
1026
II1/2G BT5Ga/GbExiaII
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-I E_____ No.: ______
Symbol of producer
:
logo Dinel®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-Xi-__-_, P/N include length of electrode: E in mm
Serial number: Ser. No.:
______
-
(
from the left: production year, serial production number
)
Label of non-explosive device:
Performance: II 1 G Ex ia IIB T5 Ga, II 1 D Ex ia IIIC T83°C Da
No. of authorized person examining control of system quality
:
1026
Number of certicate of intrinsically safety
:
FTZÚ 02 ATEX 0235X
Limit operating parameters:
Ui= 30 V DC, Ii= 132 mA, Pi= 0,99 W, Ci= 370 nF,
Li= 0,9 mH
Ambient temperature range: ta= -40 ... +75 °C, ta = -20 ... +60 °C (zone 0)
Protection class: IP 65 / IP 67
Compliance mark:
Electro-waste take-back system mark:
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷10V
out
U=16÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
IP65
IP67
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
U =0÷5V
out
U=11÷36V
i
Dinel
U
3
2Uout
Ui
0V
Vt = -40 ... +85 °C
a
Dinel, s.r.o.
Zlín, Czech Republic
www.dinel.cz
dinel@dinel.cz
I = 4 ... 20 mAU=9...36V
Dinel U
t = -40 ... +85 °C
a
IP65
IP67
0V
1
2
II1D ICT83°CDaExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
dinel@dinel.cz
Czech Republic
CLM-36Xi-__-__-I E_____ No.: ______
IP65
IP67
1026
II1G BT5GaExiaII
II1/2D ICT83°CDa/DbExiaII
Dinel
FTZÚ 02 ATEX 0235X
U = 30V I = 132mA P = 0,99W
C = 370nF L = 0,9mH
t = -20 ... +60 °C (zone 0)
t = -40 ... +75 °C
a
a
i
i
i
ii
Ui
Dinel, s.r.o.
Zlín
www.dinel.cz
Czech Republic
CLM-36XiT-__-__-I E_____ No.: ______
IP65
IP67
1026
II1/2G BT5Ga/GbExiaII
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-U E_____ No.: ______
CLM-36N_-__-__-I E_____ No.: ______
Symbol of producer
:
logo Dinel®
Contact: Dinel, s.r.o., Zlín, Czech Republic, www.dinel.cz, [email protected]
Connection scheme and labelling of wires: U, 0V, GND
Type of level meter: CLM-36-XiT-__-_, P/N include length of electrode: E in mm
Serial number: Ser. No.:
______
-
(
from the left: production year, serial production number
)
Label of non-explosive device:
Performance: II 1/2 G Ex ia IIB T5 Ga/Gb, II1/2D Ex ia IIIC T83°C Da/Db
No. of authorized person examining control of system quality
:
1026
Number of certicate of intrinsically safety
:
FTZÚ 02 ATEX 0235X
Limit operating parameters:
Ui= 30 V DC, Ii= 132 mA, Pi= 0,99 W, Ci= 370 nF,
Li= 0,9 mH
Ambient temperature range: ta= -40 ... +75 °C, ta = -20 ... +60 °C (zone 0)
Protection class: IP 65 / IP 67
Compliance mark:
Electro-waste take-back system mark:
Other manuals for CLM-36
2
This manual suits for next models
33
Table of contents
Other Dinel Measuring Instrument manuals

Dinel
Dinel CLM-70 User manual

Dinel
Dinel MLM-35 User manual

Dinel
Dinel CLM-36 User manual

Dinel
Dinel ULM-55N User manual

Dinel
Dinel CLM-36-10 User manual

Dinel
Dinel ULM-70 Series User manual

Dinel
Dinel ULM-53L User manual

Dinel
Dinel CLM-36 User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel PDU-40-W Series User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel ULM -70 Series User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel DLM-35 User manual

Dinel
Dinel ULM -70 Series User manual

Dinel
Dinel GRLM-70 User manual

Dinel
Dinel ULM-53 series User manual

Dinel
Dinel ULM - 54 User manual