GEM R481 Victoria User manual

GEMÜ R481 Victoria
Pneumatically operated butterfly valve
Operating instructions
EN
further information
webcode: GW-R481

All rights including copyrights or industrial property rights are expressly reserved.
Keep the document for future reference.
© GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
27.10.2020
www.gemu-group.com2 / 41GEMÜ R481

Contents
1 General information .................................................. 4
1.1 Information .......................................................... 4
1.2 Symbols used ...................................................... 4
1.3 Definition of terms .............................................. 4
1.4 Warning notes ..................................................... 4
2 Safety information .................................................... 5
3 Product description ................................................... 5
3.1 Construction ........................................................ 5
3.2 Description ........................................................... 6
3.3 Function ............................................................... 6
3.4 Product label ....................................................... 6
3.5 ATEX label ........................................................... 6
4 GEMÜ CONEXO ......................................................... 6
5 Correct use ............................................................... 7
5.1 Product without special function X .................... 7
5.2 Product with special function X ......................... 7
6 Order data ................................................................. 8
6.1 Order codes ......................................................... 8
6.2 Order example - standard version ...................... 9
7 Technical data .......................................................... 10
7.1 Medium ................................................................ 10
7.2 Temperature ........................................................ 10
7.3 Pressure ............................................................... 10
7.4 Product conformity ............................................. 11
7.5 Mechanical data .................................................. 11
8 Dimensions ............................................................... 14
8.1 Actuator dimensions ........................................... 14
8.2 Body dimensions ................................................. 18
9 Manufacturer's information ....................................... 25
9.1 Delivery ................................................................ 25
9.2 Transport ............................................................. 25
9.3 Storage ................................................................. 25
10 Installation in piping .................................................. 25
10.1 Preparing for installation .................................... 25
10.2 Installation location ............................................. 26
10.3 Installation of the standard version ................... 27
10.4 Installation of the ATEX version ......................... 28
11 Pneumatic connection ............................................... 28
11.1 Control functions ................................................. 28
11.2 Connecting the control medium ......................... 29
11.3 Optical position indicator .................................... 29
12 Setting the end positions ........................................... 29
13 Commissioning ......................................................... 30
14 Operation .................................................................. 30
15 Troubleshooting ........................................................ 31
16 Inspection and maintenance ...................................... 32
16.1 Cleaning the product ........................................... 32
16.2 ATEX version ....................................................... 32
16.3 Removing the butterfly valve from the piping ... 32
16.4 Presetting the butterfly valves ............................ 33
17 Spare parts ............................................................... 34
17.1 Ordering spare parts ........................................... 34
17.2 Lug ....................................................................... 35
17.3 Wafer .................................................................... 36
17.4 Replacement of spare parts ............................... 37
18 Removal from piping ................................................. 38
19 Disposal .................................................................... 38
20 Returns ..................................................................... 38
21 Declaration of Incorporation according to 2006/42/
EC (Machinery Directive) ........................................... 39
22 Declaration of conformity according to 2014/68/EU
(Pressure Equipment Directive) ................................. 40
GEMÜ R481www.gemu-group.com 3 / 41

www.gemu-group.com4 / 41GEMÜ R481
1 General information
1 General information
1.1 Information
– The descriptions and instructions apply to the stand-
ard versions. For special versions not described in this
document the basic information contained herein ap-
plies in combination with any additional special docu-
mentation.
– Correct installation, operation, maintenance and repair
work ensure faultless operation of the product.
– Should there be any doubts or misunderstandings, the
German version is the authoritative document.
– Contact us at the address on the last page for staff
training information.
– A supplement to Directive 2014/34/EU (ATEX Direct-
ive) is included with the product, provided that it was
ordered in accordance with ATEX.
1.2 Symbols used
The following symbols are used in this document:
Symbol Meaning
Tasks to be performed
Response(s) to tasks
– Lists
1.3 Definition of terms
Working medium
The medium that flows through the GEMÜ product.
Control function
The possible actuation functions of the GEMÜ product.
Control medium
The medium whose increasing or decreasing pressure causes
the GEMÜ product to be actuated and operated.
1.4 Warning notes
Wherever possible, warning notes are organised according to
the following scheme:
SIGNAL WORD
Type and source of the danger
Possible
symbol for the
specific
danger
Possible consequences of non-observance.
Measures for avoiding danger.
Warning notes are always marked with a signal word and
sometimes also with a symbol for the specific danger.
The following signal words and danger levels are used:
DANGER
Imminent danger!
▶Non-observance can cause death or
severe injury.
WARNING
Potentially dangerous situation!
▶Non-observance can cause death or
severe injury.
CAUTION
Potentially dangerous situation!
▶Non-observance can cause moderate
to light injury.
NOTICE
Potentially dangerous situation!
▶Non-observance can cause damage to
property.
The following symbols for the specific dangers can be used
within a warning note:
Symbol Meaning
Danger of explosion!
Corrosive chemicals!
GEMÜ products without an operator!
Hot plant components!
Use as end-of-line valve!
Danger – bodily injury!

www.gemu-group.com 5 / 41 GEMÜ R481
2 Safety information
The safety information in this document refers only to an indi-
vidual product. Potentially dangerous conditions can arise in
combination with other plant components, which need to be
considered on the basis of a risk analysis. The operator is re-
sponsible for the production of the risk analysis and for com-
pliance with the resulting precautionary measures and re-
gional safety regulations.
The document contains fundamental safety information that
must be observed during commissioning, operation and main-
tenance. Non-compliance with these instructions may cause:
– Personal hazard due to electrical, mechanical and
chemical effects.
– Hazard to nearby equipment.
– Failure of important functions.
– Hazard to the environment due to the leakage of dan-
gerous materials.
The safety information does not take into account:
– Unexpected incidents and events, which may occur
during installation, operation and maintenance.
– Local safety regulations which must be adhered to by
the operator and by any additional installation person-
nel.
Prior to commissioning:
1. Transport and store the product correctly.
2. Do not paint the bolts and plastic parts of the product.
3. Carry out installation and commissioning using trained
personnel.
4. Provide adequate training for installation and operating
personnel.
5. Ensure that the contents of the document have been fully
understood by the responsible personnel.
6. Define the areas of responsibility.
7. Observe the safety data sheets.
8. Observe the safety regulations for the media used.
During operation:
9. Keep this document available at the place of use.
10. Observe the safety information.
11. Operate the product in accordance with this document.
12. Operate the product in accordance with the specifications.
13. Maintain the product correctly.
14. Do not carry out any maintenance work and repairs not de-
scribed in this document without consulting the manufac-
turer first.
In cases of uncertainty:
15. Consult the nearest GEMÜ sales office.
3 Product description
3.1 Construction
1
4
5
9
0-2
0-1
11
7
8
8
2
3
6
10
Item Name Materials
1 Body SG iron 5.3106, epoxy
coated (RAL 5021)
2 Shaft 1.4021
3 Axis 1.4021
4 Disc Various materials (see
order data)
5 Liner Various materials (see
order data)
6 Threaded plug 1.4021
7 O-ring NBR
8 Support rings PTFE
9 Hexagon head bolts Stainless steel A2-70
0 Earthing kit
0-1 Cable lug
0-2 Stranded wire
10 Pneumatic actuator Aluminium
3 Product description

www.gemu-group.com6 / 41GEMÜ R481
4 GEMÜ CONEXO
3.2 Description
The GEMÜ R481 Victoria soft seated metal butterfly valve has
a metal actuator and is pneumatically operated. Normally
Closed, Normally Open and Double Acting control functions
are available. Various pneumatic actuators are available. The
butterfly valve is available in nominal sizes DN 50 to 300 and
in standard installation lengths ISO 5752/20 | EN 558-1/20 |
API 609 category A (DIN 3202 K1) in wafer and lug body ver-
sions.
3.3 Function
The product controls a flowing medium by being closed or
opened by a control medium.
3.4 Product label
The product label is located on the valve body. Product label
data (example):
Design in accordance with order data
Device-specific data
Year of manufacture
Item number
The month of manufacture is encoded in the traceability num-
ber and can be obtained from GEMÜ. The product was manu-
factured in Germany.
The operating pressure stated on the product label applies to
a media temperature of 20 °C. The product can be used up to
the maximum stated media temperature. You can find the
pressure/temperature correlation in the technical data.
3.5 ATEX label
The product with special function X is intended for use in po-
tentially explosive areas and is equipped with an ATEX label.
On the butterfly valve there is an additional adhesive label
with the ATEX marking for the butterfly valve with bare shaft:
480 50W332A1ELF05 D09 X
II -/2 G 88326775
II -/2 D
Ex h -/IIB T6 …T3 -/Gb X
Ex h -/IIIC T150°C -/Db X
The ATEX marking applies only to the butterfly valve with bare
shaft. The overall evaluation must be carried out by the plant
operator.
4 GEMÜ CONEXO
The interaction of valve components that are equipped with
RFID chips and an associated IT infrastructure actively in-
crease process reliability.
Thanks to serialization, every valve and every relevant valve
component such as the body, actuator or diaphragm, and
even automation components, can be clearly traced and read
using the CONEXO pen RFID reader. The CONEXO app, which
can be installed on mobile devices, not only facilitates and im-
proves the "installation qualification" process, but also makes
the maintenance process much more transparent and easier
to document. The app actively guides the maintenance techni-
cian through the maintenance schedule and directly provides
him with all the information assigned to the valve, such as
test reports, testing documentation and maintenance histor-
ies. The CONEXO portal acts as a central element, helping to
collect, manage and process all data.
For further information on GEMÜ CONEXO please visit:
www.gemu-group.com/conexo

www.gemu-group.com 7 / 41 GEMÜ R481
5 Correct use
DANGER
Danger of explosion!
▶Risk of severe injury or death.
●Do not use the product in potentially
explosive zones.
●Only use the product in potentially ex-
plosive zones confirmed in the declara-
tion of conformity.
WARNING
Improper use of the product
▶Risk of severe injury or death.
▶Manufacturer liability and guarantee will be void.
●Only use the product in accordance with the operating
conditions specified in the contract documentation and in
this document.
The product is designed for installation in piping systems and
for controlling a working medium.
●Use the product in accordance with the technical data.
5.1 Product without special function X
The product is not intended for use in potentially explosive
areas.
5.2 Product with special function X
With the special version X order option, the product is inten-
ded for use in potentially explosive areas in zone 1 with gases,
mists or vapours and zone 21 with combustible dusts in ac-
cordance with EU Directive 2014/34/EU (ATEX).
The product has the following explosion protection marking:
Gas: II -/2 G Ex h -/IIB T6 …T3 -/Gb X
Dust: II -/2 D Ex h -/IIIC T150°C -/Db X
The product has been developed in compliance with the fol-
lowing harmonized standards:
– EN 1127-1:2011
– ISO 80079-36:2016
– ISO 80079-37:2016
The product can be used in the following ambient temperat-
ure ranges: -10 °C to +70 °C
For use in potentially explosive areas, the following special
conditions or operation limits must be observed:
Index X is applied to the ATEX marking.
The following special conditions must be complied with:
– Temperature class depending on the temperature of
the conveyed medium and the clock frequency
– Not permissible as an end-of-line valve
5 Correct use

6 Order data
Other configurations available on request.Please check the availability with GEMÜ before ordering.
Products ordered with bold marked ordering options are so-called preferred series. Depending on the nominal size, these are
available more quickly.
Order codes
1 Type Code
Butterfly valve, pneumatically operated R481
2 DN Code
DN 50 50
DN 65 65
DN 80 80
DN 100 100
DN 125 125
DN 150 150
DN 200 200
DN 250 250
DN 300 300
3 Body configuration Code
Flange-mounted design (lug),
face-to-face dimension FTF EN 558 series 20
L
Intermediate flange design (wafer),
face-to-face dimension FTF EN 558 series 20
W
4 Operating pressure Code
3 bar 0
6 bar 1
10 bar 2
16 bar 3
5 Connection type Code
PN 6 / flange EN 1092, face-to-face dimension FTF
EN 558 series 20
1
PN 10 / flange EN 1092, face-to-face dimension
FTF EN 558 series 20
2
PN 16 / flange EN 1092, face-to-face dimension
FTF EN 558 series 20
3
ANSI B16.5, Class 150, face-to-face dimension FTF
EN 558 series 20
D
Flange BS 10 Table "D", face-to-face dimension
FTF EN 558, series 20
H
Flange BS 10 Table "E", face-to-face dimension FTF
EN 558, series 20
S
Flange AS 2129 Table "D", face-to-face dimension
FTF EN 558, series 20
T
Flange AS 2129 Table "E", face-to-face dimension
FTF EN 558, series 20
U
6 Body material Code
EN-GJS-400-15 (GGG-40), epoxy-coated 250 μm 2
6 Continuation of Body material Code
EN-GJS-400-18-LT (GGG-40.3), epoxy coated 250
µm
3
7 Disc material Code
1.4408 A
1.4408, polished, roughness Ra 0.6-3.2, except
disc marking
B
1.4408, Halar coated C
1.4469, super duplex D
EN-GJS-400-15 (GGG-40), epoxy coated E
EN-GJS-400-15 (GGG-40), HALAR coated P
EN-GJS-400-15 (GGG-40), RILSAN PA11 coated R
2.0975 / CC333G G
1.4435 / ASTM A351 / CF3M / AISI 316L I
8 Shaft material Code
1.4021 1
9 Shut-off seal material Code
EPDM E
SBR-AB/P (abrasion resistant) F
NBR (DVGW gas certification) J
EPDM (FDA certification), white M
NBR N
FPM (FKM) V
EPDM (ACS, WRAS, DVGW water, BELGAQUA
certification)
W
EPDM-HT (FDA certification) Z
ECO C
CSM H
Silicone (MVQ-S, steam) R
Silicone (MVQ) S
NBR (FDA certification), white U
10 Liner fixing Code
Liner bonded into body B
Loose liner L
11 Type of design Code
Without
Media wetted area cleaned to ensure suitability for
paint applications, parts sealed in plastic bag
0101
Valve free of oil and grease, media wetted area
cleaned and packed in PE bag
0107
6 Order data
www.gemu-group.com8 / 41GEMÜ R481

11 Continuation of Type of design Code
Butterfly valve body powder coated, RAL 5015, sky
blue
1892
Thermal separation between actuator and valve
body via dew point barrier
5226
12 Special version Code
Without
ACS certification A
BELGAQUA certification B
WRAS certification W
ATEX certification X
ATEX certification (in the piping system) Y
13 Control function Code
Normally closed (NC) 1
Normally open (NO) 2
Double acting (DA) 3
14 Actuator version Code
Actuator version
15 CONEXO Code
without
Integrated RFID chip for electronic identification
and traceability
C
Order example - standard version
Order option Code Description
1 Type R481 Butterfly valve, pneumatically operated
2 DN 80 DN 80
3 Body configuration W Intermediate flange design (wafer),
face-to-face dimension FTF EN 558 series 20
4 Operating pressure 3 16 bar
5 Connection type 3 PN 16 / flange EN 1092, face-to-face dimension FTF EN 558 series 20
6 Body material 2 EN-GJS-400-15 (GGG-40), epoxy-coated 250 μm
7 Disc material A 1.4408
8 Shaft material 1 1.4021
9 Shut-off seal material E EPDM
10 Liner fixing L Loose liner
11 Type of design Without
12 Special version Without
13 Control function 1 Normally closed (NC)
14 Actuator version SU10KC Actuator, pneumatic, single acting, clockwise rotation, spring closing,
SC0100U 6F05/07S17D11
15 CONEXO without
6 Order data
www.gemu-group.com 9 / 41 GEMÜ R481

7 Technical data
7.1 Medium
Working medium: Gaseous and liquid media which have no negative impact on the physical and chemical properties
of the disc and seat material.
7.2 Temperature
Ambient temperature: -10 to 70 °C
Media temperature: -10 to 150 °C
Depending on the liner and disc material or the type of liner fixing
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
14 32 50 68 86 104 122 140 158 176 194 212 230 248 266 284 302
°C
°F
Disc material (code R)
Bonded liner (code B)
NBR (code J)
SBR (AB/P) (code F)
EPDM (code M)
EPDM (code W)
NBR (code N)
EPDM (code E)
EPDM (code Z)
FPM (code V)
Disc material (code E)
Liner material
Temperature
FPM material not suitable for water/steam applications above 100 °C,
Observe Pressure/Temperature diagram.
Storage temperature: 5 to 40 °C
7.3 Pressure
Control pressure: 6 to 8 bar
Operating pressure: 0 to 16 bar
Use (installation) as end-of-line valve
DN 50 – 200: 10 bar
DN 250, 300: 6 bar
Pressure/temperature
diagram:
DN 50 - 200
DN 250, 300
-20 200 40 60 80 100 120 140 160 180 200
0
2
4
6
8
10
12
14
16
18
Pressure [bar]
Temperature [°C]
Pressure rating: PN 6
PN 10
PN 16
www.gemu-group.com10 / 41GEMÜ R481
7 Technical data

Kv values: DN Kv values at opening angle
20° 30° 40° 50° 60° 70° 80° 90°
50 3 9 20 33 65 110 124 125
65 9 15 30 64 118 195 214 222
80 19 40 66 117 196 321 353 363
100 29 75 137 213 316 487 584 618
125 48 100 185 315 550 895 1060 1120
150 60 150 281 450 789 1280 1630 1730
200 110 281 472 759 1480 2880 3710 3900
250 200 444 738 1190 2110 3880 5180 5410
300 250 682 1060 1670 3120 6360 8620 8930
Kv values in m³/h
When the opening angle is below 30° no regulation should be made!
7.4 Product conformity
Machinery Directive: 2006/42/EC
Pressure Equipment
Directive:
2014/68/EU
Food: FDA
Drinking water: ACS
WRAS
Belgaqua
Explosion protection: ATEX (2014/34/EU), order code Special version X and Y
ATEX marking: Special function code X
Gas: II -/2 G Ex h -/IIB T6...T3 -/Gb X
Dust: II -/2D Ex h -/IIIC T150°C -/Db X
Special function code Y
Gas: II 2 G Ex h /IIC T6...T3 Gb X
Dust: II 2D Ex h /IIIC T150°C Db X
7.5 Mechanical data
Torques: DN PS
3 bar 10 bar 16 bar
50 - - 9
65 - - 15
80 - - 25
100 - - 40
125 - - 60
150 - - 100
200 145 - 242
250 152 310 -
300 245 330 -
Torques in Nm
Working medium water (20 °C) and optimal operating conditions
Butterfly valves with bonded liner: the torques must be multiplied by the factor 1.3
GEMÜ R481www.gemu-group.com 11 / 41
7 Technical data

Weight: Butterfly valve
DN Wafer Lug
50 1.70 2.22
65 2.47 2.91
80 3.18 4.40
100 4.36 6.20
125 5.87 8.10
150 7.73 10.13
200 13.9 18.35
250 19.64 28.74
300 27.26 36.75
Weights in kg
Actuator type ADA/ASR
Type ADA ASR
0020U 1.4 1.5
0040U 2.1 2.3
0080U 3 3.7
0130U 3.8 4.8
0200U 5.6 7.3
0300U 8.5 10.8
0500U 11.2 15.4
0850U 16.9 22.2
1200U 25.8 34.3
Weights in kg
Actuator DR/SC
Type DR SC
0015U 1.0 1.1
0030U 1.6 1.7
0060U 2.7 3.1
0100U 3.7 4.3
0150U 5.2 6.1
0220U 8.0 9.3
0300U 9.8 12.0
0450U - 17.0
0600U - 22.0
0900U - 33.0
Weights in kg
www.gemu-group.com12 / 41GEMÜ R481
7 Technical data

Weight: Actuator type GDR/GSR
Type GDR GSR
0050 1.1 1.2
0065 1.5 1.8
0075 2.6 3.2
0085 3.4 4.3
0100 5.1 6.6
0115 8 10.6
0125 10 13.4
0140 11 17.2
0160 19.5 24.4
0180 26 37.5
Weights in kg
GEMÜ R481www.gemu-group.com 13 / 41
7 Technical data

8 Dimensions
8.1 Actuator dimensions
8.1.1 ADA/ASR
M5x12
L1
B
B1
A3
A
12
24
16
32
G
80
30
80
130
30
24
12
16
32
G
ØM
T
S
4
4
Z
M6
V
Typ 00010 - 4000U
Typ 00010 - 0850U
4 x M5x12
Typ 01200 - 4000U
L
4 x M5x12
4 x M5x12
Typ 00010 - 4000U
x
x
x
Typ 00010 - 1750U
Typ 02100 - 4000U
Typ 00010 - 4000U
M5x12
M5x12
Type 00010 - 4000U Type 00010 - 1750U
Type 00010 - 0850U
Type 01200 - 4000U
Type 00010 - 4000U
Type 02100 - 4000U
Type 00010 - 4000U
Type A A3 B B1 V G P Z L L1
0040U 115.0 85.0 91.0 56.0 40.0 G1/4" 30.0 30.0 158.0 195.0
0200U 165.0 135.0 135.5 78.0 40.0 G1/4" 30.0 30.0 225.0 299.0
0500U 199.0 169.0 173.0 96.0 40.0 G1/4" 30.0 30.0 304.0 397.0
0850U 221.0 191.0 191.5 106.0 40.0 G1/4" 30.0 30.0 372.0 473.0
1200U 249.0 219.0 212.5 116.0 65.0 G1/4" 30.0 30.0 439.0 560.0
1750U 280.0 250.0 242.5 131.0 65.0 G1/4" 30.0 30.0 461.0 601.0
2100U 313.0 283.0 276.5 148.0 65.0 G1/4" 30.0 30.0 510.0 702.0
2500U 383.0 353.0 356.0 177.5 65.0 G1/4" 30.0 30.0 518.0 738.0
4000U 434.0 404.0 415.0 213.0 65.0 G1/4" 30.0 30.0 630.0 940.0
Dimensions in mm
www.gemu-group.com14 / 41GEMÜ R481
8 Dimensions

8.1.2 DR/SC
G
L
V
B
A3
B1
A
x
x
x
x
Typ 0015U - 1200U
Typ 2000U - 4000U
Typ 5000U
45
32
24
4 x M5x8
4 x M6x10
G
40
4 x M5x8
30
VL
30
4
4
Y
4 x M6x10
G
45
40
P
Connector 2
Connector 4
Connector 4
Connector 4
Connector 2
Connector 2
Type 2000U - 4000U
Type 0015U - 1200U
Type 5000U
Type A A3 B B1 V G P L Y
0015U 89.0 69.0 72.0 43.0 42.0 G1/8" 20.0 136.0 11.0
0030U 105.0 85.0 84.5 48.5 42.0 G1/8" 20.0 153.5 11.0
0060U 122.0 102.0 93.0 50.5 42.0 G1/8" 20.0 203.5 17.0
0100U 135.0 115.0 106.0 56.5 42.0 G1/8" 20.0 241.0 17.0
0150U 147.0 127.0 118.5 63.0 42.0 G1/4" 20.0 259.0 17.0
0220U 175.0 145.0 136.0 72.0 58.0 G1/4" 30.0 304.0 27.0
0300U 187.0 157.0 146.5 77.0 58.0 G1/4" 30.0 333.0 27.0
0450U 207.0 177.0 166.0 86.0 67.5 G1/4" 30.0 394.5 27.0
0600U 226.0 196.0 181.0 93.0 67.5 G1/4" 30.0 422.5 27.0
0900U 270.5 220.5 200.0 101.0 80.0 G1/4" 50.0 474.0 36.0
Dimensions in mm
GEMÜ R481www.gemu-group.com 15 / 41
8 Dimensions

8.1.3 GDR/GSR
8.1.3.1 Type G0032
32
(16)
32
(16)
G
L
B1
B
A3
A
VL
25
4
Z
4,5
P
V
x
x
6 x M5x7
4 x M5x8
Connector 2
Connector 4
Type A A3 B B1 V G P VL Z L
G0032 67.5 45.5 49.0 26.5 40.0 G1/8" 22.0 50.0 20.0 115.0
Dimensions in mm
www.gemu-group.com16 / 41GEMÜ R481
8 Dimensions

8.1.3.2 Type G0050 – G0180
L
G0050 - 0180
B
A3
B1
A
80
VL1
30
G0115 - G0180
80
30
G0050 - G0100
P
V
xx
24
(12)
32
(16)
4 x M5x8
4 x M5x8
8 x M5x8
G
4
Z
4,5
Connector 2
Connector 4
Type A A3 B B1 V G P VL Z L VL1
G0050 92.0 70.0 71.0 30.0 40.0 G1/8" 22.0 80.0 20.0 141.0 -
G0065 102.5 80.5 80.5 35.5 40.0 G1/8" 22.0 80.0 20.0 162.0 -
G0075 119.0 97.0 94.5 42.0 40.0 G1/8" 22.0 80.0 20.0 208.0 -
G0085 130.5 108.5 106.0 47.5 40.0 G1/8" 22.0 80.0 20.0 237.0 -
G0100 143.5 121.5 123.0 55.0 40.0 G1/8" 22.0 80.0 20.0 271.5 -
G0115 174.0 142.0 137.0 64.0 65.0 G1/4" 32.0 80.0 30.0 337.0 130.0
G0125 185.5 153.5 148.0 68.0 65.0 G1/4" 32.0 80.0 30.0 366.0 130.0
G0140 207.9 175.9 164.0 76.5 65.0 G1/4" 32.0 80.0 30.0 428.5 130.0
G0160 225.0 193.0 188.0 88.0 65.0 G1/4" 32.0 80.0 30.0 512.0 130.0
G0180 251.0 219.0 212.5 96.5 65.0 G1/4" 32.0 80.0 30.0 573.0 130.0
Dimensions in mm
GEMÜ R481www.gemu-group.com 17 / 41
8 Dimensions

8.2 Body dimensions
8.2.1 Actuator flange
E
a
b2
b1
G
y1
y2
DN 80 - 100 DN 50 - 65,
DN 125 - 300
G
y1
a
b1
DN □G øa ISO 5211 øb1 øy1 øb2 øy2 E
50 9.0 65.0 F03 | F05 36.0 6.0 50.0 7.0 17.0
65 11.0 65.0 F03 | F05 36.0 6.0 50.0 7.0 17.0
80 11.0 65.0 F05 36.0 7.0 - - 17.0
100 14.0 65.0 F05 50.0 7.0 - - 17.0
125 17.0 90.0 F05 | F07 50.0 7.0 70.0 9.0 23.0
150 17.0 90.0 F05 | F07 50.0 7.0 70.0 9.0 23.0
200 22.0 125.0 F07 | F10 70.0 9.0 102.0 11.0 34.0
250 22.0 125.0 F07 | F10 70.0 9.0 102.0 11.0 34.0
300 22.0 125.0 F07 | F10 70.0 9.0 102.0 11.0 34.0
Dimensions in mm
www.gemu-group.com18 / 41GEMÜ R481
8 Dimensions

8.2.2 Body
8.2.2.1 Wafer body configuration
Ø
D
B1
A
B
F
C
ØS
H
I
Ø
D1
DN PS A B B1 C ØD ØD1 F H ØS I
50 16 120.0 182.0 62.0 43.0 90.0 118.0 7.0 29.0 52.0 5.0
65 16 137.0 218.0 81.0 46.0 108.0 133.0 7.0 48.0 67.0 10.0
80 16 145.0 231.0 87.0 46.0 130.0 141.0 7.0 68.0 82.0 18.0
100 16 166.0 271.0 105.0 52.0 150.0 163.0 7.0 88.0 102.0 25.0
125 16 187.0 304.0 117.0 56.0 175.0 120.0 9.0 114.0 127.0 35.0
150 16 200.0 332.0 132.0 56.0 207.0 129.0 9.0 141.0 152.0 48.0
200 16 240.0 413.0 173.0 60.0 263.0 157.0 11.0 193.0 202.0 71.0
250 10 265.0 466.0 201.0 68.0 317.0 185.0 11.0 242.0 252.0 92.0
300 10 290.0 531.0 241.0 78.0 366.0 164.0 11.0 291.0 302.0 112.0
Dimensions in mm
GEMÜ R481www.gemu-group.com 19 / 41
8 Dimensions

8.2.2.1.1 Connections
ØG
ØG
W°
W°
ø
y
Connection EN1092, EN1759
DN INCH Connection (code)
EN1092-1 PN6
(code 1)
EN1092-1 PN10
(code 2)
EN1092-1 PN16
(code 3)
EN1759/CL150
(code D)
DIN ASME w° n ØG y w° n ØG y w° n ØG y w° n ØG y
50 2" 90 4 110.0 14.0 90 4 125.0 18.0 90 4 125.0 18.0 90 4 120.6 19.0
65 2½" 90 4 130.0 14.0 90 4 145.0 18.0 90 4 145.0 18.0 90 4 139.7 19.0
80 3" 90 4 150.0 18.0 45 8 160.0 18.0 45 8 160.0 18.0 90 4 152.4 19.0
100 4" 90 4 170.0 18.0 45 8 180.0 18.0 45 8 180.0 18.0 45 8 190.5 19.0
125 5" 45 8 200.0 18.0 45 8 210.0 18.0 45 8 210.0 18.0 45 8 215.9 22.2
150 6" 45 8 225.0 18.0 45 8 240.0 22.0 45 8 240.0 22.0 45 8 241.3 22.2
200 8" 45 8 280.0 18.0 45 8 295.0 22.0 30 12 295.0 22.0 45 8 298.5 22.2
250 10" 30 12 335.0 18.0 30 12 350.0 22.0 30 12 355.0 26.0 30 12 362.0 25.4
300 12" 30 12 395.0 22.0 30 12 400.0 22.0 30 12 410.0 26.0 30 12 431.8 25.4
Dimensions in mm
Connection AS2129, BS10
DN INCH Connection (code)
AS 2129 D (code T) AS 2129 E (code U) BS10 D (code H) BS10 E (code S)
DIN ASME w° n ØG y w° n ØG y w° n ØG y w° n ØG y
50 2" 90 4 114.0 18.0 90 4 114.0 18.0 90 4 114.3 17.5 90 4 114.3 17.5
65 2½" 90 4 127.0 18.0 90 4 127.0 18.0 90 4 127.0 17.5 90 4 127.0 17.5
80 3" 90 4 146.0 18.0 90 4 146.0 18.0 90 4 146.1 17.5 90 4 146.1 17.5
100 4" 90 4 178.0 18.0 45 8 178.0 18.0 90 4 177.8 17.5 45 8 177.8 17.5
125 5" 45 8 210.0 18.0 45 8 210.0 18.0 45 8 209.6 17.5 45 8 209.6 17.5
150 6" 45 8 235.0 18.0 45 8 235.0 22.0 45 8 235.0 17.5 45 8 235.0 20.6
200 8" 45 8 292.0 18.0 45 8 292.0 22.0 45 8 292.1 17.5 45 8 292.1 20.6
250 10" 45 8 356.0 22.0 30 12 356.0 22.0 45 8 355.6 22.2 30 12 355.6 22.2
300 12" 30 12 406.0 22.0 30 12 406.0 26.0 30 12 406.4 22.2 30 12 406.4 25.4
Dimensions in mm
www.gemu-group.com20 / 41GEMÜ R481
8 Dimensions
Other manuals for R481 Victoria
1
Table of contents
Other GEM Control Unit manuals